QFM81.2, QFM81.21 Duct Hygrostats

Product Description

These instructions explain how to install a QFM81.2
or QFM81.21 Duct Hygrostat.
Product Numbers
QFM81.2 Duct Hygrostat with external setpoint
QFM81.21 Duct Hygrostat

Required Tools

Screwdriver
Electric drill
7 mm Wrench
Expected Installation Time
15 minutes
Installation
Air Duct Mounting
If the duct hygrostat is used for control, mount in the
exhaust air duct after the room to be controlled.
If the duct hygrostat is used for monitoring the
maximum or minimum humidity level, mount in the
supply air duct.
Mounting Positions
The immersion sensor stem must be mounted either
horizontally or vertically with the stem pointing
downward. Do not mount with the stem pointing
upward. (See Figure 1.)
Figure 1. Acceptable Mounting Positions.
Item Number 129-606, Rev. AA
Installation Instructions
Ensure that the air to be measured is sufficiently
mixed at the point of measurement for accurate
humidity measurements.
The mounting orientation is dependent on the air
velocity in the ductwork: at < 5 m/s, the holes in the
stem must face the airflow; at > 5 m/s, they must be
perpendicular to the direction of airflow. (See
Figure 2.)
Figure 2. Mounting Orientations.
Minimum Immersion Length
NOTE: When mounting the hygrostat in air ducts,
the minimum immersion length of the stem
is 5.12 inches (130 mm).
The mounting flange supplied with the unit allows
the immersion length to be adjusted between
5.12 inches (130 mm) and 6.14 inches (156 mm).
Figure 3. Mounting Flange.
Document No. 129-606
July 15, 2010
Page 1 of 2

Advertisement

loading

Summary of Contents for Siemens QFM81.21

  • Page 1: Product Description

    Installation Instructions Document No. 129-606 July 15, 2010 QFM81.2, QFM81.21 Duct Hygrostats Ensure that the air to be measured is sufficiently Product Description mixed at the point of measurement for accurate humidity measurements. These instructions explain how to install a QFM81.2 The mounting orientation is dependent on the air or QFM81.21 Duct Hygrostat.
  • Page 2: Wall Mounting

    Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. © 2010 Siemens Industry, Inc. Siemens Industry, Inc.

This manual is also suitable for:

Qfm81.2