D603/D604/D605
Installation Instructions
1.0
Notice
These instructions cover the installation of the D603, D604 and D605 Heat Detectors in a fire system supervised
by a compatible Fire Alarm Control Panel (FACP).
Install, test and maintain the D603, D604 and D605 according to these instructions, NFPA 72, Local Codes and
the Authority Having Jurisdiction (AHJ). Failure to follow these instructions may result in failure of the device to
operate properly. Bosch Security Systems, Inc. is not responsible for improperly installed, tested or maintained
devices.
These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.
Test the D603, D604, D605 and the FACP in accordance with NFPA 72.
1.1
FCC Compliance Notice
This device complies with Part 15 of the FCC Rules and with RSS-21 of Industry and Science Canada. Operation
is subject to the following two conditions:
(1) this device may not cause harmful interferences, and
(2) this device must accept any interference received, including interference that may cause undesirable operation.
Changes or modifications not expressly approved by Bosch Security Systems can void the user's authority to
operate the equipment.
2.0
Device Description
The D603, D604 and D605 are Electronic Rate-of-Rise/Fixed Temperature Heat Detectors. They are designed to
work with the D200 Series bases to provide general property protection.
When properly installed using the D200 Series bases, 2-wire supervision is provided by IN/OUT wiring of the
positive (+) power line. This causes the FACP to initiate a trouble signal when a detector head is removed from its
base. 4-wire system supervision is provided by an EOL power supervision device, such as the D275, or a D293E
and an EOL resistor as specified by the FACP manufacturer.
The D603, D604 and D605 are not life-safety devices.
Heat Detectors