Mitsubishi Electric PUHY-200YMF-B Service Handbook page 155

Advertisement

1 PU(H)Y-(P)200·250YMF-B
E: E2 Contents stored in the E2PROM; M: Monitored by the IC through communications; E*: Stored in service memory.
No
SW1
Item
12345678910
0
0000000000
Relay Output
Display 1 (Lights
up to display)
Check Display 1
OC Error
1
1000000000
Relay Output
Display 2
2
0100000000
Check Display 2
(Including the IC)
3
1100000000
4
0010000000
5
1010000000
6
0110000000
External Signal
(Signal being
input)
7
1110000000
Outdoor Unit
Operation Display
8
0001000000
Indoor Unit Check
9
1001000000
10
0101000000
Indoor Unit
Operation Mode
11
1101000000
12
0011000000
Indoor Unit
Thermostat ON
13
1011000000
14
0111000000
15
1111000000
Outdoor Unit
Operation Mode
16
0000100000
Outdoor Unit
Control Mode
17
1000100000
Preliminary Error
in Outdoor Unit
18
0100100000
19
1100100000
20
0010100000
LD1
LD2
LD3
COMP
Crankcase
21S4
SV1
Operat-
Heater ON
ing
Address and error code reversed
Address and error code reversed
Auto
Auto
changeover
changeover
mode (cooling)
mode (heating)
Warm-
3 minutes,
Com-
up
restart
pressor
mode
protection mode
operating
Unit
Unit
Unit
Unit
No. 1
No. 2
No. 3
No. 4
Unit
Unit
Unit
Unit
No. 9
No. 10
No. 11
No. 12
Unit
Unit
Unit
Unit
No. 1
No. 2
No. 3
No. 4
Unit
Unit
Unit
Unit
No. 9
No. 10
No. 11
No. 12
Unit
Unit
Unit
Unit
No. 1
No. 2
No. 3
No. 4
Unit
Unit
Unit
Unit
No. 9
No. 10
No. 11
No. 12
Permis-
Standby
Defrost
Cooling
sible Stop
Cooling
Heating
Refrigerant
Refrigerant
Recovery
Recovery
High
Low
Discharge
Overcurrent
Pressure
Pressure
Tempera-
Protection
Error 1, 2
Error 1, 2
ture Error
Suction
Configuration
Comp.
Reverse
pressur
Detection
tempera-
Phase, Open
Error
Error
ture Error
Phase Error
TH1
TH2
TH3
TH4
Error
Error
Error
Error
TH7
TH8
TH9
TH10
Error
Error
Error
Error
–153–
Display
LD4
LD5
LD6
LD7
SV2
0 ~ 9999
SSR
0 ~ 9999
Prelimi-
Error
nary
Error
Unit
Unit
Unit
No. 5
No. 6
No. 7
Unit
Unit
Unit
No. 13
No.14
No. 15
Unit
Unit
Unit
No. 5
No. 6
No. 7
Unit
Unit
Unit
No. 13
No.14
No. 15
Unit
Unit
Unit
No. 5
No. 6
No. 7
Unit
Unit
Unit
No. 13
No.14
No. 15
Heating
Cooling
Cooling
Heating
High Oil
Low Oil
High Oil
Recovery
Recovery
Recovery
Heat Sink
Overcurrent
INV
Thermostat
Break
Error
Operating
TH5
TH6
HPS
Error
Error
Error
LPS
Error
Remarks
LD8
Lights for
LD8 is a relay output indicator which
Normal
lights up at all times when the
Operation
microcomputer's power is ON.
When sending of a monitoring re-
quest to IC/BC is terminated, if there
is no error, "- - - -" is displayed. E*
E*
If there is no error,
"- - - -" is displayed. E*
E*
E*
Unit
Lights up if an abnormal stop
No. 8
has occurred in the IC. The
indicator for Unit No. 1 goes off
Unit
when error reset is carried out
No. 16
from the smallest address. M
Unit
Lights up during
No. 8
cooling.
Blinks during heating.
Unit
Goes off during stop
No. 16
and blower operation. M
Unit
Lights up when
No. 8
thermostat is ON.
Goes off when
Unit
thermostat is OFF.
No. 16
M
E*
Heating
Low Oil
Recovery
Over-
The flag correspond-
charged
ing to the item where
Refrigerant
there is an error
delay lights up. E*
THHS
Error