Panasonic U-36LE1U6 Technical Data Manual

Panasonic U-36LE1U6 Technical Data Manual

Mini vrf system
Hide thumbs Also See for U-36LE1U6:
Table of Contents

Advertisement

U-36LE1U6
U-36LE1U6E
U-52LE1U6
U-52LE1U6E
Model No.
Outdoor Unit
Class
U-36LE1U6
Model Name
U-36LE1U6E*
Refrigerant R410A is used in the outdoor units.
* Salt-Air Damage Resistant Specifications.
Indoor Units
Class
U1
4-Way Cassette
Y1
4-Way Cassette 60×60
D1
1-Way Cassette
S-07MD1U6 S-09MD1U6 S-12MD1U6
F1
Low Silhouette Ducted
S-07MF1U6 S-09MF1U6 S-12MF1U6 S-15MF1U6 S-18MF1U6
M1
Slim Low Static Ducted
S-07MM1U6 S-09MM1U6 S-12MM1U6
High Static Pressure
E1
Ducted
T1
Ceiling
K1
Wall Mounted
S-07MK1U6 S-09MK1U6 S-12MK1U6
P1
Floor Standing
S-07MP1U6 S-09MP1U6 S-12MP1U6 S-15MP1U6 S-18MP1U6
Concealed Floor
R1
S-07MR1U6 S-09MR1U6 S-12MR1U6 S-15MR1U6 S-18MR1U6
Standing
**
Necessary to install the External Electronic Expansion Valve Kit (Optional:CZ-P56SVK1U)
85464869256000
*
*
36
52
U-52LE1U6
U-52LE1U6E*
7
9
12
S-12MU1U6
S-12MY1U6
S-15MM1U6 S-18MM1U6
S-12MT1U6
MINI VRF System
15
18
19
S-18MU1U6
S-24MU1U6 S-36MU1U6
S-18MY1U6
S-24MF1U6
S-18MT1U6
S-24MT1U6
**
S-18MK1U6 S-19MS1U6
S-24MK1U6
S-24MP1U6
S-24MR1U6
24
36
48
S-36MF1U6 S-48MF1U6
S-54MF1U6
S-36ME1U6 S-48ME1U6
TD831156-00
REFERENCE NO.
Section
1
Section
1
2
2
3
3
4
4
54
5
5
6
6
7
7
8
8

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic U-36LE1U6

  • Page 1 MINI VRF System U-36LE1U6 U-36LE1U6E Section U-52LE1U6 Section U-52LE1U6E Model No. Outdoor Unit Class U-36LE1U6 U-52LE1U6 Model Name U-36LE1U6E* U-52LE1U6E* Refrigerant R410A is used in the outdoor units. * Salt-Air Damage Resistant Specifications. Indoor Units Class 4-Way Cassette S-12MU1U6 S-18MU1U6 S-24MU1U6 S-36MU1U6 4-Way Cassette 60×60...
  • Page 2: Special Precautions

    IMPORTANT! Please Read Before Starting This air conditioning system meets strict safety and oper- When Installing… ating standards. As the installer or service person, it is an Select an installation location which is rigid and strong important part of your job to install or service the system so enough to support or hold the unit, and select a location it operates safely and efficiently.
  • Page 3: Check Of Density Limit

    • Do not touch the air inlet or the When Servicing CAUTION sharp aluminum fins of the • Turn the power OFF at the main power box (mains) outdoor unit. You may get injured. before opening the unit to check or repair electrical •...
  • Page 4: Precautions For Installation Using New Refrigerant

    Precautions for Installation Using New Refrigerant 1.Care regarding tubing 1-1.Process tubing Material:Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.” Tubing size:Be sure to use the sizes indicated in the table below. Use a tube cutter when cutting the tubing, and be sure to remove any flash.This also applies to distribution joints (optional).
  • Page 5 3-2.Use R410A exclusive cylinder only. Valve Single-outlet valve (with siphon tube) Liquid refrigerant should be recharged with the cylinder standing on end as shown. Liquid New refrigerant R410A cannot be used for earlier models 1.Compressor specifications are different. If recharging a R22 or R407C compressor with R410A, durability will significantly decrease since some of the materials used for compressor parts are different.
  • Page 6: Table Of Contents

    Contents Section 1: OUTLINE OF MINI VRF SYSTEM ................. Line-up ......................Salt-Air Damage Resistant Specifications ............Section 2: DESIGN OF MINI VRF SYSTEM ................Model Selecting and Capacity Calculator ............System Design ..................... 2-13 Electrical Wiring .................... 2-22 Installation Instructions ................. 2-30 HOW TO PROCESS TUBING ..............
  • Page 7: Section 1: Outline Of Mini Vrf System

    Outline of Mini VRF SYSTEM Contents 1. OUTLINE OF MINI VRF SYSTEM 1. Line-up ..........................1-2 2. Salt-Air Damage Resistant Specifications................. 1 - 1...
  • Page 8: Line-Up

    Outline of Mini VRF SYSTEM 1. Line-up Indoor units Type 4-Way Cassette (U1 Type) S-12MU1U6 S-18MU1U6 S-24MU1U6 S-36MU1U6 4-Way Cassette 60 X 60 (Y1 Type) S-12MY1U6 S-18MY1U6 1-Way Cassette (D1 Type) S-07MD1U6 S-09MD1U6 S-12MD1U6 Low Silhouette Ducted (F1 Type) S-07MF1U6 S-09MF1U6 S-12MF1U6 S-15MF1U6 S-18MF1U6 S-24MF1U6...
  • Page 9: Line-Up

    Outline of Mini VRF SYSTEM 1. Line-up Indoor units DC inverter unit Type Capacity: 38,200 (11.2) 52,900 (15.5) BTU/h (kW) Cooling / / 42,700 (12.5) / 60,000 (17.6) Heating U-36LE1U6/U-52LE1U6 U-36LE1U6E*/U-52LE1U6E* 25-31/32 11/16 5/16 8-5/8 5-29/32 Air intake discharge Outdoor Unit intake discharge...
  • Page 10: Salt-Air Damage Resistant Specifications

    Outline of Mini VRF SYSTEM 2. Salt-Air Damage Resistant Specifications Specifications Salt-Air Damage Resistant Specifications Relevant Parts Material Standard Specifications Outdoor unit model name ended with letters "U6E". Outer box/side plate/ Hot-dip zinc-coated Polyester powder double coating Polyester powder double coating drain pan steel sheet (both sides) ( 120 m)
  • Page 11: Section 2: Design Of Mini Vrf System

    Design of Mini VRF SYSTEM Contents 2. DESIGN OF MINI VRF SYSTEM 1. Model Selecting and Capacity Calculator ................. 2-2 1-1. Operating Range ......................1-2. Procedure for Selecting Models and Calculating Capacity ........... 1-3. Calculation of Actual Capacity of Indoor Unit ..............1-4.
  • Page 12: Model Selecting And Capacity Calculator

    Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator 1-1. Operating Range Heating Cooling Operating Operating range range –4 Indoor air intake temp. °F (DB) Indoor air intake temp. °F (WB) 2 - 2...
  • Page 13 Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator 1-2. Procedure for Selecting Models and Calculating Capacity ■ Model Selection Procedure Select the model and calculate the capacity for each refrigerant system according to the procedure shown below. Calculation of the indoor air-conditioning load ●...
  • Page 14 Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator 1-3. Calculation of Actual Capacity of Indoor Unit ■ Calculating the actual capacity of each indoor unit Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length, elevation difference and other factors, select the correct model after taking into account the various correction values.
  • Page 15 Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator <Heating> ● Outdoor unit corrected heating capacity (5) = Outdoor unit rated heating capacity × Correction coefficient for outdoor temperature conditions ((1) Page 2-6) × Correction coefficient for tubing length and elevation difference ((2) Page 2-8) ×...
  • Page 16 Note: When Ruc or Ruh is less than or equal to 1.0, the indoor unit capacity correction coefficient for both Ruc and Ruh is 1.0. 5. Graph of capacity correction coefficients ■ Graph of outdoor unit capacity characteristics (1 – (1)) Outdoor unit cooling capacity characteristics (1) U-36LE1U6, U-36LE1U6E 71°F WB 66°F WB (2) U-52LE1U6, U-52LE1U6E 60°F WB...
  • Page 17 Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator Outdoor unit heating capacity characteristics U-52LE1U6, U-52LE1U6E U-36LE1U6, U-36LE1U6E (°F DB) (°F DB) –4 –4 Outdoor air intake temp. (°F DB) Outdoor air intake temp. (°F DB) ■ Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (2)) Outdoor intake air –4...
  • Page 18 Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator ■ Graph of indoor unit capacity characteristics (2 – (1)) Indoor unit cooling capacity characteristics Indoor unit heating capacity characteristics indicates the rating point. indicates the rating point. 59 60 62 64 66 68 69 71 73 75 77 78 80 57 59 60 62 64 66 68 69 71 73 75 77 Indoor air intake temp.
  • Page 19 1-4. Capacity Correction Graph According to Temperature Condition ■ Capacity characteristics (The corrected capacity for specific temperature conditions can be found from the graphs below and next page.) <COOLING> (1) U-36LE1U6, U-36LE1U6E 71°F WB 66°F WB (2) U-52LE1U6, U-52LE1U6E 60°F WB Outdoor air intake temp.
  • Page 20 Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator <HEATING> U-52LE1U6, U-52LE1U6E U-36LE1U6, U-36LE1U6E (°F DB) (°F DB) –4 –4 Outdoor air intake temp. (°F DB) Outdoor air intake temp. (°F DB) 2 - 10...
  • Page 21 Power capacity consumption capacity consumption Model BTU/h(kW) BTU/h(kW) BTU/h(kW) BTU/h(kW) U-36LE1U6, U-36LE1U6E 38,200 (11.2) 9,400 (2.76) 42,700 (12.5) 9,800 (2.88) U-52LE1U6, U-52LE1U6E 52,900 (15.5) 16,600 (4.57) 60,000 (17.6) 15,600 (4.58) ■ Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (3)) Outdoor intake air –4...
  • Page 22 Design of Mini VRF SYSTEM 1. Model Selecting and Capacity Calculator For U-36LE1U6(E) units ■ If the maximum tubing length (L1) exceeds 295 ft. (equivalent length), increase the tubing size of the main gas tube (LM) by one rank. * The size increase is applied to the gas tube only. In addition, for a 6 HP unit it is not necessary to increase the tubing size.
  • Page 23: System Design

    Table 2-2 (Outdoor Unit) 2-4. Additional Materials Required for Installation Q'ty 1. Refrigeration (armored) tape Patr name Figure U-36LE1U6 U-52LE1U6 2. Insulated staples or clamps for connecting wire U-36LE1U6E U-52LE1U6E (4 hp) (6 hp) (See your local codes.) 3.
  • Page 24 Design of Mini VRF SYSTEM 2. System Design 2-5. Tubing Size Table 2-3 Main Tubing Size (LA) BTU/h (kW) 38,200 (11.2) 52,900 (15.5) System horsepower Gas tubing ø5/8" (ø15.88) ø 3/4" (ø19.05) Liquid tubing ø 3/8" (ø9.52) Unit: in. (mm) Note: If the system consists of only one indoor unit with an outdoor 6HP (Type 52), the main tube of the unit (LA) should be ø19.05.
  • Page 25 + (...) + (...) ø3/8” (ø9.52) 0.602 *Always charge accurately using a scale for weighing. Table 2-9 Refrigerant Charge Amount at Shipment (for outdoor unit) Heat pump unit U-36LE1U6 U-52LE1U6 (Single-phase)(oz) U-36LE1U6E U-52LE1U6E 2-8. System Limitations Table 2-10 System Limitations...
  • Page 26 Design of Mini VRF SYSTEM 2. System Design Table 2-11 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights Items Marks Contents Length (ft.) > Actual length Max. tubing length > Equivalent length Difference between max. length and min. Allowable tubing >...
  • Page 27 (indoor unit 2) (indoor unit 3) (indoor unit 4) Selected model Type 12 Type 7 Type 7 Type 7 U-36LE1U6 (U-36LE1U6E) Air condition 91.0 / 72.0 78.0 / 64.0 78.0 / 64.0 78.0 / 64.0 78.0 / 64.0 (DB/WB) Cooling...
  • Page 28 Design of Mini VRF SYSTEM 2. System Design Indoor unit changes The indoor unit in room 4, where the corrected indoor unit capacity is less than the maximum load, is increased by one rank. Room 1 Room 2 Room 3 Room 4 Outdoor unit (indoor unit 1)
  • Page 29 Design of Mini VRF SYSTEM 2. System Design 2-12. Example of Tubing Size Selection and Refrigerant Charge Amount Additional refrigerant charging Based on the values in Tables 2-3, 2-4, 2-5 and 2-8, use the liquid tubing size and length, and calculate the amount of additional refrigerant charge using the formula below.
  • Page 30 Design of Mini VRF SYSTEM 2. System Design Example: Main tube of unit 1st branch model 18 n–1 Unit distribution tube model 7 model 9 model 12 model 18 ● Example of each tubing length Main tubing Distribution joint tubing LA = 131 ft.
  • Page 31 Design of Mini VRF SYSTEM 2. System Design 2-13. Installing Distribution Joint Tube branching methods (horizontal use) (1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT” enclosed with the optional distribution joint kit (CZ-P160BK1U). (2) In order to prevent accumulation of refrigerant oil Arrow view D in stopped units, if the main tubing is horizontal Arrow view C...
  • Page 32: Electrical Wiring

    3-2. Recommended Wire Length and Wire Diameter for Power Supply System Outdoor unit Time delay fuse or Type circuit capacity U-36LE1U6 30 A U-36LE1U6E U-52LE1U6 50 A U-52LE1U6E Indoor unit...
  • Page 33 Design of Mini VRF SYSTEM 3. Electrical Wiring 3-3.Wiring System Diagram Indoor unit (No. 1) Outdoor unit Power supply INV unit 208 / 230V, 60Hz, 1-PH Power supply Ground 208 / 230V, 60Hz, 1-PH Remote Controller Ground * Disconnect switch (Field Supply) Indoor unit (No.
  • Page 34 Design of Mini VRF SYSTEM 3. Electrical Wiring CAUTION (1) When linking outdoor units in a network, disconnect the terminal extended from the short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units.
  • Page 35 Design of Mini VRF SYSTEM 3. Electrical Wiring Loose wiring may cause Stranded wire the terminal to overheat or WARNING result in unit malfunction. A fire hazard may also Ring exist. Therefore, ensure pressure that all wiring is tightly terminal connected.
  • Page 36 Design of Mini VRF SYSTEM 3. Electrical Wiring 3-4. Important Note When Wiring for Common Type U1 Type Connect the wires referring to the diagram. Note that the control wirings (Low voltages) shall be segregated from the power supply wires (High voltage) as follows: Connect the Inter-unit control wiring to U1/U2 Earth screw...
  • Page 37 Design of Mini VRF SYSTEM 3. Electrical Wiring Important Note When Wiring for Common Type (Continued) E1 Type T1 Type Remote control wiring and Inter-unit control wiring (field supplied) Clamping Remote control wiring clip (field supplied) Clamping clip Conduit (field supplied) Earth screw Power wiring Conduit...
  • Page 38 Design of Mini VRF SYSTEM 3. Electrical Wiring Important Note When Wiring for Common Type (Continued) K1 Type Model : S-07MK1U6 Clamping Connection for Solenoid S-09MK1U6 strap Valve Kit (for 3WAY) S-12MK1U6 Power wiring (field supplied) Remote control wiring Conduit and Inter-unit control (field supplied) wiring (field supplied)
  • Page 39 Design of Mini VRF SYSTEM 3. Electrical Wiring 3-5. Important Note When Wiring for Y1 Type Connect the wires referring to the diagram. Y1 Type Note that the control wirings (Low Voltages) shall be segregated from the power supply wires (High Voltage) Connection for Solenoid as follows: Valve Kit (for 3WAY)
  • Page 40: Installation Instructions

    Design of Mini VRF SYSTEM 4. Installation Instructions 4-1. Selecting the Installation Site for Outdoor Unit Exhaust fan AVOID: Hot air heat sources, exhaust fans, etc.(Fig.2-6) damp, humid or uneven locations Heat source Out- door unit choose a place as cool as possible. choose a place that is well ventilated and outside air temperature does not exceed maximum 113°F constantly.
  • Page 41 Design of Mini VRF SYSTEM 4. Installation Instructions 4-2. Air Discharge Chamber for Top Discharge Be sure to install an air discharge chamber (field sup- Air discharge ply) in the field when: it is difficult to keep a space of min.20 in.between the air discharge outlet and an obstacle.
  • Page 42 Design of Mini VRF SYSTEM 4. Installation Instructions 4-5. Dimensions of Air-Discharge Chamber Reference diagram for air-discharge chamber (field supply) Unit front, air discharge chamber Unit left side, air discharge chamber Unit right side, air discharge chamber Reinforcement brackets, 4 locations 9-7/16 1-1/8 1-1/8...
  • Page 43 Design of Mini VRF SYSTEM 4. Installation Instructions Reference for air-discharge chamber (field supply) Required space around outdoor unit If an air discharge chamber is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating. (1) Single-unit installation Unit:in.
  • Page 44 Design of Mini VRF SYSTEM 4. Installation Instructions 4-7. Dimensions of Snow Ducting Reference diagram for snow-proof ducting (field supply) Fastened by screws at 13 locations 30-3/32 Unit top, snow-proof vent Unit left side Unit right side Unit reverse side Unit: in.
  • Page 45 Design of Mini VRF SYSTEM 4. Installation Instructions Reference diagram for snow-proof ducting – 1 Space requirements for setting – (1) [Obstacle to the front of unit] [Obstacle to the rear of unit] Top is open: Top is open: (1) Single-unit installation (2) Obstacles on both sides (1) Single-unit installation Min.
  • Page 46 Design of Mini VRF SYSTEM 4. Installation Instructions Reference diagram for snow-proof ducting – 2 Space requirements for setting – (2) [Obstacles to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit.
  • Page 47 Design of Mini VRF SYSTEM 4. Installation Instructions 4-9. Installing the Outdoor Unit Use concrete or a similar material to create the base, and ensure good drainage. Ordinarily, ensure a base height of 2" or more. If a drain pipe is used, or for use in cold-weather regions, ensure a height of 6"...
  • Page 48: How To Process Tubing

    Design of Mini VRF SYSTEM 5. HOW TO PROCESS TUBING 5. HOW TO PROCESS TUBING Deburring 5-1. Connecting the Refrigerant Tubing After Before Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units.In this method, the copper tubes are flared at each end and connected with flare nuts.
  • Page 49 Design of Mini VRF SYSTEM 5. HOW TO PROCESS TUBING Caution Before Connecting Tubes Tightly Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. Apply refrigerant Be sure to apply refrigerant lubricant to the matching lubricant surfaces of the flare and union before connecting them together.
  • Page 50 Design of Mini VRF SYSTEM 5. HOW TO PROCESS TUBING 5-3. Insulating the Refrigerant Tubing Tubing Insulation Thermal insulation must be applied to all unit tubing, Two tubes arranged together including distribution joint (purchased separately). Liquid tubing Gas tubing * For gas tubing, the insulation material must be heat resistant to 248°F or above.
  • Page 51 Design of Mini VRF SYSTEM 5. HOW TO PROCESS TUBING 5-4. Taping the Tubes At this time, the refrigerant tubes (and electrical wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To prevent the condensation from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing.
  • Page 52: Air Purging

    Design of Mini VRF SYSTEM 6. AIR PURGING 6. AIR PURGING Manifold gauge Air and moisture in the refrigerant system may have undesirable effects as indicated below. pressure in the system rises operating current rises cooling (or heating) efficiency drops moisture in the refrigerant circuit may freeze and block capillary tubing water may lead to corrosion of parts in the refrigerant...
  • Page 53 Design of Mini VRF SYSTEM 6. AIR PURGING Do a leak test of all joints of the tubing (both indoor and outdoor) and both gas tube and liquid tube service valves. Bubbles indicate a leak. Wipe off the soap with a Manifold valve clean cloth after the leak test.
  • Page 54 Design of Mini VRF SYSTEM 6. AIR PURGING Use a cylinder designed for CAUTION Manifold valve use with R410A. Pressure Charging additional refrigerant gauge Charging additional refrigerant (calculated from the liquid tube length as shown in Section 2-7 Valve “Additional Refrigerant Charge”) using the liquid tube service valve.
  • Page 55: Optional Parts

    Design of Mini VRF SYSTEM 7. Optional Parts 7-1. Distribution Joint Kits CZ-P160BK1U (for R410A) Size of connection point on each part How to Attach Distribution Joint (Shown are inside diameters of tubing) 1. Accompanying Parts Size Inch Check the contents of your distribution joint kit. Part A o19.05 2.
  • Page 56 – MEMO – 2 - 46...
  • Page 57: Section 3: Control Of Mini Vrf System

    Control of Mini VRF SYSTEM Contents 3. CONTROL OF MINI VRF SYSTEM 1. Main Operating Functions 2. Wireless Remote Controller 3. Timer Remote Controller 4. Simplifi ed Remote Controller 5. System Controller 6. Schedule Timer 7. Intelligent Controller (CZ-256ESMC1U) 8. Communication Adaptor (CZ-CFUNC1U) 9.
  • Page 58 – MEMO – 3 - 2...
  • Page 59: Way Cassette 60×60 Type (Y1 Type)

    Mini VRF SYSTEM Contents Unit Specifications 4. MINI VRF SYSTEM UNIT SPECIFICATIONS 1. Outdoor Unit ........................4-2 1-1. Specifications ......................4-2 1-2. AHRI Registration Values ..................4-4 1-3. Dimensional Data ...................... 4-5 1-4. Refrigerant Flow Diagram .................... 1-5. Sound Data ......................... 4-Way Cassette Type (U1 Type) 4-Way Cassette 60×60 Type (Y1 Type) 1-Way Cassette Type (D1 Type)
  • Page 60 Mini VRF SYSTEM 1. Outdoor Unit Unit Specifications 1-1. Specifi cations Unit specifi cations (A) MODEL No. Outdoor Unit U-36LE1U6, U-36LE1U6E* POWER SOURCE 208 - 230 V / 1ø / 60 Hz PERFORMANCE Cooling Heating BTU / h 38,200 42,700 Capacity 11.2...
  • Page 61 Mini VRF SYSTEM 1. Outdoor Unit Unit Specifications Unit specifi cations (B) MODEL No. Outdoor Unit U-52LE1U6, U-52LE1U6E* POWER SOURCE 208 - 230 V / 1ø / 60 Hz PERFORMANCE Cooling Heating BTU / h 52,900 60,000 Capacity 15.5 17.6 Air circulation (Hi) 3,530 ELECTRICAL RATINGS...
  • Page 62 Heating Outdoor Unit Indoor Unit SEER HSPF Capacity Capacity Models Types BTU/h 95°F BTU/h Ducted 37,000 9.60 13.1 38,500 U-36LE1U6(E) Non Ducted 39,000 11.50 17.0 43,000 Mixed Non-Ducted and Duced 38,000 10.55 15.05 40,750 Ducted 51,500 9.40 14.6 57,500 U-52LE1U6(E)
  • Page 63 Mini VRF SYSTEM 1. Outdoor Unit Unit Specifications 1-3. Dimensional Data U-36LE1U6, U-36LE1U6E U-52LE1U6, U-52LE1U6E 4 - 5...
  • Page 64 Mini VRF SYSTEM 1. Outdoor Unit Unit Specifications 1-4. Refrigerant Flow Diagram U-36LE1U6 U-36LE1U6E U-52LE1U6 U-52LE1U6E Suction 4 - 6...
  • Page 65 Mini VRF SYSTEM 1. Outdoor Unit Unit Specifications 1-5. Sound Data (1) Sound Power Level U-36LE1U6, U-36LE1U6E Model U-36LE1U6, U-36LE1U6E Sound Power 67 dB (A) Level Cooling Condition NC – 70 NC – 60 NC – 50 NC – 40 NC –...
  • Page 66 Mini VRF SYSTEM 1. Outdoor Unit Unit Specifications U-52LE1U6, U-52LE1U6E Model U-52LE1U6, U-52LE1U6E Sound Power 68 dB (A) Level Cooling Condition NC – 70 NC – 60 NC – 50 NC – 40 NC – 30 NC – 20 1000 2000 4000 8000...
  • Page 67 Mini VRF SYSTEM 1. Outdoor Unit Unit Specifications (2) Sound Pressure Level U-36LE1U6, U-36LE1U6E Model U-36LE1U6, U-36LE1U6E Sound Pressure Level Front 51 dB (A) Cooling Quiet Mode 48 dB (A) Condition 3.3 ft. in front at height of 4.9 ft.
  • Page 68 Mini VRF SYSTEM 1. Outdoor Unit Unit Specifications U-52LE1U6, U-52LE1U6E Model U-52LE1U6, U-52LE1U6E Sound Pressure Level Front 52 dB (A) Cooling Quiet Mode 49 dB (A) Condition 3.3 ft. in front at height of 4.9 ft. Front Quiet Mode NC – 70 NC –...
  • Page 69: Section 5: Test Run

    Test Run Contents 5. TEST RUN 1. Preparing for Test Run ................5-2 2.
  • Page 70: Preparing For Test Run

    Test Run 1. Preparing for Test Run ● Before attempting to start the air conditioner, check the following. (1) All loose matter is removed from the cabinet, especially steel filings, bits of wire, and clips. (2) The control wiring is correctly connected and all (Power must be turned ON electrical connections are tight.
  • Page 71: Test Run Procedure

    Test Run 2. Test Run Procedure Items to Check Before the Test Run 1. Turn the remote power switch on at least 5 hours before the test, in order to energize the crankcase heater. 2. Turn the outdoor service valves Recheck the items to check before the test run.
  • Page 72: Outdoor Unit Pcb Setting

    Test Run 3. Outdoor Unit PCB Setting CN33 CN51 CN50 S003 S002 D043 (LED2) S004 D042 (LED1) Fig. 5-4 5 - 4...
  • Page 73 Test Run 3. Outdoor Unit PCB Setting Examples of the No. of indoor units settings Indoor unit setting (S004) No. of indoor units (Rotary switch, red) 1 unit (factory setting) Set to 1 2 units Set to 2 9 units Set to 9 Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used) System address (S003)
  • Page 74: Auto Address Setting

    Test Run 4. Auto Address Setting Basic wiring diagram: Example (1) • If link wiring is not used (The inter-unit control wires are not connected to multiple refrigerant systems.) Indoor unit addresses can be set without operating the compressors. No. 1 unit settings (S004) System address No.
  • Page 75 Test Run 4. Auto Address Setting Basic wiring diagram: Example (2) • If link wiring is used • If link wiring is used * When multiple outdoor units exist, remove the socket that is used to short-circuit the terminal plug (CN33) from all outdoor unit PCBs except for 1.
  • Page 76 Test Run 4. Auto Address Setting Case 1 Automatic Address Setting (no compressor operation) ● Indoor and outdoor unit power can be turned ON for each system separately. Indoor unit addresses can be set without operating the compressors. Automatic Address Setting from Outdoor Unit 1.
  • Page 77 Test Run 4. Auto Address Setting Case 2 Automatic Address Setting in Heating Mode ● Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all refrigerant tubing work.
  • Page 78 Test Run 4. Auto Address Setting Case 3 Automatic Address Setting in Cooling Mode ● Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all refrigerant tubing work.
  • Page 79 Test Run 4. Auto Address Setting Display during automatic address setting ● On outdoor unit PCB * Do not short-circuit the automatic address setting pin (CN51) again while automatic address setting is in progress. Doing so will cancel the setting operation and will cause LEDs 1 and 2 to turn OFF.
  • Page 80: Remote Controller Test Run Settings

    Test Run 4. Auto Address Setting 5. Remote Controller Test Run Settings Request concerning recording the indoor/outdoor unit combination Nos. After automatic address setting has been completed, be sure to record them for future reference. List the outdoor unit system address and the addresses of the indoor units in that system in an easily visible location (next to the nameplate), using a permanent marking pen or similar means that cannot be erased easily.
  • Page 81: Caution For Pump Down

    Test Run 6. Caution for Pump Down 7. Meaning of Alarm Messages 6. Caution for Pump Down Pump down means refrigerant gas in the system is returned to the outdoor unit. Pump down is used when the unit is to be moved, or before servicing the refrigerant circuit.
  • Page 82 Test Run 7. Meaning of Alarm Messages Alarm Possible cause of malfunction message This alarm message shows when the indoor unit for multiple-use Serial Improper setting. is not connected to the outdoor unit. communication errors Duplication of main indoor unit address setting in group control. <L03>...
  • Page 83: Section 6: Electrical Data

    Electrical Data Contents 6. ELECTRICAL DATA 1. Outdoor Unit ........................Electric Wiring Diagram U-36LE1U6, U-36LE1U6E ..........Electric Wiring Diagram U-52LE1U6, U-52LE1U6E ..........2. Indoor Unit * Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157) 6 - 1...
  • Page 84: Outdoor Unit

    Electrical Data 1. Outdoor Unit (1) Electric Wiring Diagram U-36LE1U6, U-36LE1U6E 6 - 2...
  • Page 85 Electrical Data 1. Outdoor Unit Schematic Diagram U-36LE1U6, U-36LE1U6E 6 - 3...
  • Page 86 Electrical Data 1. Outdoor Unit (2) Electric Wiring Diagram U-52LE1U6, U-52LE1U6E 6 - 4...
  • Page 87 Electrical Data 1. Outdoor Unit Schematic Diagram U-52LE1U6, U-52LE1U6E 6 - 5...
  • Page 88 – MEMO – 6 - 6...
  • Page 89: Refer To The 2Way Vrf System Technical Data (Td831157)

    PCB and Functions Contents 7. PCB AND FUNCTIONS 1. Outdoor Unit Control PCB ....................1-1. Outdoor Unit Control PCB CR-CHX06052 ..............1-2. Outdoor Unit HIC Board HIC-CHDX14053 ..............1-3. Functions (for CR-CHX06052) ..................2. Indoor Unit Control PCB Switches and Functions * Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157) 7 - 1...
  • Page 90: Outdoor Unit Control Pcb

    PCB and Functions 1. Outdoor Unit Control PCB 1-1. Outdoor Unit Control PCB CR-CHX06052 7 - 2...
  • Page 91 PCB and Functions 1. Outdoor Unit Control PCB 1-2. Outdoor Unit HIC Board HIC-CHDX14053 7 - 3...
  • Page 92 PCB and Functions 1. Outdoor Unit Control PCB 1-3. Functions (for CR-CHX06052) CN51 2P plug (black): Automatic address setting pin • If the system address switch (S002: Factory setting is 0) is set to other than 0 (centralized control), press this switch once to automatically set the address of the indoor unit to the connected outdoor unit within the same system.
  • Page 93 PCB and Functions 1. Outdoor Unit Control PCB CN15 The control operations that are shown below are when you short-circuit this cooling inspection pin located on the outdoor unit control PCB. 1.Thermistor inspection Detection results Thermistor Normal Error Discharge temperature (TD) LED1 lights up Outdoor temperature (TO) LED2 lights up...
  • Page 94 PCB and Functions 1. Outdoor Unit Control PCB Table 7-1. Setting the System Address [S002: Rotary switch (black), S003: 2P DIP (green or blue)] S002 setting S003 setting Outdoor (System system address address No. (10s digit) (20s digit) switch) refrigerant system only Outdoor...
  • Page 95: Section 8: Capacity Table

    Capacity Table Contents 8. CAPACITY TABLE 1. Capacity Ratio of Outdoor Unit ..................1-1. U-36LE1U6, U-36LE1U6E (Cooling) ................1-2. U-36LE1U6, U-36LE1U6E (Heating) ................1-3. U-52LE1U6, U-52LE1U6E (Cooling) ................1-4. U-52LE1U6, U-52LE1U6E (Heating) ................2. Cooling Capacity of Indoor Unit ..................
  • Page 96: Capacity Ratio Of Outdoor Unit

    Capacity Table 1. Capacity Ratio of Outdoor Unit 1-1. U-36LE1U6, U-36LE1U6E (Cooling) MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW) Indoor air temp. : °CWB Combination(%): Outdoor 16.0 17.0 18.0 19.0 20.0 21.0 22.0 Indoor/outdoor air temp.
  • Page 97 Capacity Table 1. Capacity Ratio of Outdoor Unit MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW) Indoor air temp. : °CWB Combination(%): Outdoor 16.0 17.0 18.0 19.0 20.0 21.0 22.0 Indoor/outdoor air temp. capacity ratio °CDB -10.0 0.65...
  • Page 98: U-36Le1U6, U-36Le1U6E (Heating)

    Capacity Table 1. Capacity Ratio of Outdoor Unit 1-2. U-36LE1U6, U-36LE1U6E (Heating) MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW) Indoor air temp. : °CDB Combination(%): Outdoor 15.0 17.0 19.0 20.0 21.0 23.0 25.0 Indoor/outdoor air temp.
  • Page 99 Capacity Table 1. Capacity Ratio of Outdoor Unit MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW) Indoor air temp. : °CDB Combination(%): Outdoor 15.0 17.0 19.0 20.0 21.0 23.0 25.0 Indoor/outdoor air temp. capacity ratio -19.8 -20.0 2.36...
  • Page 100: U-52Le1U6, U-52Le1U6E (Cooling)

    Capacity Table 1. Capacity Ratio of Outdoor Unit 1-3. U-52LE1U6, U-52LE1U6E (Cooling) MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW) Indoor air temp. : °CWB Combination(%): Outdoor 16.0 17.0 18.0 19.0 20.0 21.0 22.0 Indoor/outdoor air temp.
  • Page 101 Capacity Table 1. Capacity Ratio of Outdoor Unit MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW) Indoor air temp. : °CWB Combination(%): Outdoor 16.0 17.0 18.0 19.0 20.0 21.0 22.0 Indoor/outdoor air temp. capacity ratio °CDB -10.0 1.03...
  • Page 102: U-52Le1U6, U-52Le1U6E (Heating)

    Capacity Table 1. Capacity Ratio of Outdoor Unit 1-4. U-52LE1U6, U-52LE1U6E (Heating) MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW) Indoor air temp. : °CDB Combination(%): Outdoor 15.0 17.0 19.0 20.0 21.0 23.0 25.0 Indoor/outdoor air temp.
  • Page 103 Capacity Table 1. Capacity Ratio of Outdoor Unit MINI VRF Capacity Ratio 50-130% TC: Total capacity (kW), PI: Power input (kW) Indoor air temp. : °CDB Combination(%): Outdoor 15.0 17.0 19.0 20.0 21.0 23.0 25.0 Indoor/outdoor air temp. capacity ratio -19.8 -20.0 3.03...
  • Page 104: Cooling Capacity Of Indoor Unit

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-1. 4-Way Cassette Type (U1 Type), 4-Way Cassette 60×60 Type (Y1 Type) S-12MU1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 15.5 m...
  • Page 105 Capacity Table 2. Cooling Capacity of Indoor Unit S-18MU1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW AIR FLOW 16.0 m /min RATING CAPACITY: CONDENSER EVAPORATOR AIR INTAKE.
  • Page 106 Capacity Table 2. Cooling Capacity of Indoor Unit S-24MU1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 7.3 kW AIR FLOW 20.0 m /min RATING CAPACITY: CONDENSER EVAPORATOR AIR INTAKE.
  • Page 107 Capacity Table 2. Cooling Capacity of Indoor Unit S-36MU1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 10.6 kW RATING CAPACITY: AIR FLOW 28.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 108 Capacity Table 2. Cooling Capacity of Indoor Unit S-12MY1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 9.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 109 Capacity Table 2. Cooling Capacity of Indoor Unit S-18MY1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW RATING CAPACITY: AIR FLOW 12.5 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 110: 1-Way Cassette Type (D1 Type)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-2. 1-Way Cassette Type (D1 Type) S-07MD1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.2 kW RATING CAPACITY: AIR FLOW 8.0 m /min CONDENSER...
  • Page 111 Capacity Table 2. Cooling Capacity of Indoor Unit S-09MD1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.8 kW RATING CAPACITY: AIR FLOW 8.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 112 Capacity Table 2. Cooling Capacity of Indoor Unit S-12MD1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 9.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 113: Wall Mounted Type (K1 Type)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-3. Wall Mounted Type (K1 Type) S-07MK1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.2 kW RATING CAPACITY: AIR FLOW 10.0 m /min CONDENSER EVAPORATOR...
  • Page 114 Capacity Table 2. Cooling Capacity of Indoor Unit S-09MK1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.8 kW RATING CAPACITY: AIR FLOW 10.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 115 Capacity Table 2. Cooling Capacity of Indoor Unit S-12MK1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 10.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 116 Capacity Table 2. Cooling Capacity of Indoor Unit S-18MK1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.3 kW RATING CAPACITY: AIR FLOW 16.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 117 Capacity Table 2. Cooling Capacity of Indoor Unit S-19MS1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW RATING CAPACITY: AIR FLOW 16.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 118 Capacity Table 2. Cooling Capacity of Indoor Unit S-24MK1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 7.3 kW RATING CAPACITY: AIR FLOW 16.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 119: Ceiling Type (T1 Type)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-4. Ceiling Type (T1 Type) S-12MT1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 12.0 m /min CONDENSER EVAPORATOR...
  • Page 120 Capacity Table 2. Cooling Capacity of Indoor Unit S-18MT1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW RATING CAPACITY: AIR FLOW 13.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 121 Capacity Table 2. Cooling Capacity of Indoor Unit S-24MT1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 7.3 kW RATING CAPACITY: AIR FLOW 18.5 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 122: Low Silhouette Ducted Type (F1 Type), Slim Low Static Ducted Type (M1 Type)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-5. Low Silhouette Ducted Type (F1 Type), Slim Low Static Ducted Type (M1 Type) S-07MF1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.2 kW RATING CAPACITY: AIR FLOW 10.0 m...
  • Page 123 Capacity Table 2. Cooling Capacity of Indoor Unit S-09MF1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.8 kW RATING CAPACITY: AIR FLOW 10.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 124 Capacity Table 2. Cooling Capacity of Indoor Unit S-12MF1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 10.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 125 Capacity Table 2. Cooling Capacity of Indoor Unit S-15MF1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 4.5 kW RATING CAPACITY: AIR FLOW 12.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 126 Capacity Table 2. Cooling Capacity of Indoor Unit S-18MF1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) RATING CAPACITY: 5.6 kW AIR FLOW 12.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 127 Capacity Table 2. Cooling Capacity of Indoor Unit S-24MF1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 7.3 kW RATING CAPACITY: AIR FLOW 19.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 128 Capacity Table 2. Cooling Capacity of Indoor Unit S-36MF1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 10.6 kW RATING CAPACITY: AIR FLOW 30.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 129 Capacity Table 2. Cooling Capacity of Indoor Unit S-48MF1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 14.0 kW RATING CAPACITY: AIR FLOW 33.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 130 Capacity Table 2. Cooling Capacity of Indoor Unit S-54MF1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 16.0 kW RATING CAPACITY: AIR FLOW 33.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 131 Capacity Table 2. Cooling Capacity of Indoor Unit S-07MM1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.2 kW RATING CAPACITY: AIR FLOW 8.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 132 Capacity Table 2. Cooling Capacity of Indoor Unit S-09MM1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.8 kW RATING CAPACITY: AIR FLOW 8.5 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 133 Capacity Table 2. Cooling Capacity of Indoor Unit S-12MM1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 9.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 134 Capacity Table 2. Cooling Capacity of Indoor Unit S-15MM1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 4.5 kW RATING CAPACITY: AIR FLOW 10.5 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 135 Capacity Table 2. Cooling Capacity of Indoor Unit S-18MM1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW RATING CAPACITY: AIR FLOW 12.5 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 136: High Static Pressure Ducted Type (E1 Type)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-6. High Static Pressure Ducted Type (E1 Type) S-36ME1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 10.6 kW RATING CAPACITY: AIR FLOW 30.0 m /min CONDENSER...
  • Page 137 Capacity Table 2. Cooling Capacity of Indoor Unit S-48ME1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 14.0 kW RATING CAPACITY: AIR FLOW 36.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 138: Floor Standing Type (P1 Type)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-7. Floor Standing Type (P1 Type) S-07MP1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.2 kW RATING CAPACITY: AIR FLOW 7.0 m /min CONDENSER...
  • Page 139 Capacity Table 2. Cooling Capacity of Indoor Unit S-09MP1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.8 kW RATING CAPACITY: AIR FLOW 7.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 140 Capacity Table 2. Cooling Capacity of Indoor Unit S-12MP1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 9.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 141 Capacity Table 2. Cooling Capacity of Indoor Unit S-15MP1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 4.5 kW RATING CAPACITY: AIR FLOW 12.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 142 Capacity Table 2. Cooling Capacity of Indoor Unit S-18MP1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW RATING CAPACITY: AIR FLOW 15.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 143 Capacity Table 2. Cooling Capacity of Indoor Unit S-24MP1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 7.1 kW RATING CAPACITY: AIR FLOW 17.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 144: Concealed Floor Standing Type (R1 Type)

    Capacity Table 2. Cooling Capacity of Indoor Unit 2-8. Concealed Floor Standing Type (R1 Type) S-07MR1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.2 kW RATING CAPACITY: AIR FLOW 7.0 m /min...
  • Page 145 Capacity Table 2. Cooling Capacity of Indoor Unit S-09MR1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 2.8 kW RATING CAPACITY: AIR FLOW 7.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 146 Capacity Table 2. Cooling Capacity of Indoor Unit S-12MR1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 3.6 kW RATING CAPACITY: AIR FLOW 9.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 147 Capacity Table 2. Cooling Capacity of Indoor Unit S-15MR1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 4.5 kW RATING CAPACITY: AIR FLOW 12.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 148 Capacity Table 2. Cooling Capacity of Indoor Unit S-18MR1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) 5.6 kW RATING CAPACITY: AIR FLOW 15.0 m /min CONDENSER EVAPORATOR AIR INTAKE.
  • Page 149 Capacity Table 2. Cooling Capacity of Indoor Unit S-24MR1U6 Power supply : 208 – 230V 1phase-60Hz TC : Total Cooling Capacity (kW) , SHC : Sensible Heat Capacity (kW) RATING CAPACITY: AIR FLOW 17.0 m /min CONDENSER EVAPORATOR AIR INTAKE. TEMP AMBIENT TEMP.
  • Page 150 201201...

This manual is also suitable for:

U-52le1u6U-52le1u6eU-36le1u6e

Table of Contents