Mitsubishi Electric AE-200A Installation Manual page 34

Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

(5) Recommended circuit
(A) Level signal
CN5
AE-200/AE-50
(B) Pulse signal
CN5
Red
9
Gray
8
Blue
7
Yellow
6
Orange
5
1
Max.
10 m (32 ft)
AE-200/AE-50
Note
● The relays, external power supply, and extension cables are not supplied.
● The total length of the lead wire and extension cable should not exceed 10 m (32 ft). (Use an extension cable of 0.3 mm
thicker.)
● Cut the excess cable near the connector, and insulate the end of the unused cable with tape.
WT07137X01
External power supply
Red
9
Y2
Gray
8
Y1
Blue
7
X2
Yellow
6
X1
Orange
5
1
Max.
10 m (32 ft)
External power supply
*1
(12 or 24 VDC)
Y2
Y1
X1 X2 Y1 Y2
X2
X1
ON
Prohibit
OFF
Permit
Use relays X1, X2, Y1, and Y2 that meet the
*1
(12 or 24 VDC)
following specifications.
Demand level 4
Y2
Demand level 3
Y1
Contact rating
Demand level 2
X2
Rated voltage: 12 VDC or above
ON/OFF or Emergency
X1
stop
Rated current: 0.1 A or above
Demand level 1
Minimum applied load: DC 1 mA
*1 Select an external power supply suitable for the
relays used. (12 or 24 VDC)
Connect the external power supply in the correct
polarity to input and output the signals.
Connect ⑤–⑧ (see the figure at left) to the negative
side.
Important
● Be sure to use an external power supply (12
or 24 VDC) to avoid malfunctions.
● Connect the external power supply in the
correct polarity to avoid malfunctions.
34