SERVICE FUNCTIONS

MFZ-KJ25VE MFZ-KJ25VE2
MFZ-KJ35VE MFZ-KJ35VE2
MFZ-KJ50VE MFZ-KJ50VE2
8-1. TIMER SHORT MODE
• For service, the following set time can be shortened by bridging the timer short mode point on the electronic control P.C.
board. (Refer to 10-7.)
• The set time for the ON/OFF timer can be reduced to 1 second for each minute.
• After the breaker is turned on, the time for starting the compressor, which normally takes 3 minutes, can be reduced to 1
minute. Restarting the compressor, which takes 3 minutes, cannot be reduced.
8-2. HOW TO SET REMOTE CONTROLLER EXCLUSIVELY FOR A PARTICULAR INDOOR UNIT
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
To operate the indoor units individually with each remote controller, assign a number to each remote controller according
to the number of the indoor unit.
This setting can be set only when all the following conditions are met:
• The remote controller is powered OFF.
• Weekly timer is not set.
• Weekly timer is not being edited.
1. How to modify the electronic control P.C. board
Turn OFF the power supply before modification. To assign a number to each indoor unit , cut off "JR05" and "JR06" on the
electronic control P.C. board as shown in Table 1. (Refer to 10-7.)
Table 1
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
2. How to set the remote controller
(1) Hold down
button on the remote controller for 2 seconds to enter the pairing mode.
(2) Press
button again and assign a number to each remote controller.
Each press of
(3) Press
button to complete the pairing setting.
After the setting, turn ON the power supply and with the remote controller headed towards the indoor unit, press the
OPERATE/STOP (ON/OFF)(MFZ-KJ25/35/50VE)/ STOP/OPERATE (OFF/ON)(MFZ-KJ25/35/50VE2) button. If 1 or 2
beeps is heard from the indoor unit, the setting is completed correctly.
The remote controller that first sends a signal to an indoor unit will be regarded as the remote controller for the indoor
unit.
Once they are set, the indoor unit will only receive the signal from the assigned remote controller afterwards.
OBH666C
JR05
No modification
Cut off JR05
No modification
Cut off JR05
button advances the number in the following order: 1 → 2 → 3 → 4.
JR06
No modification
No modification
VARISTOR (NR11)
Cut off JR06
Cut off JR06
10
Indoor electronic
control P.C. Board
Fuse (F11)
R111
CN211
JR05
JR06
CN151