Toshiba RAV-SM564UT-E Installation Manual

Split type
Hide thumbs Also See for RAV-SM564UT-E:

Advertisement

+00EH99858901_01EN_4-way_IM_printOnly.book Page 1 Tuesday, December 4, 2007 2:31 PM
AIR CONDITIONER (SPLIT TYPE)
Installation Manual
Indoor Unit
Model name:
4-way Air Discharge Cassette Type
RAV-SM564UT-E
RAV-SM804UT-E
RAV-SM1104UT-E
RAV-SM1404UT-E
Not accessible to the general public
Vente interdite au grand public
Kein öffentlicher Zugang
Non accessibile a clienti generici
No destinado al público en general
Installation Manual
Air conditioner
(Split type)
Manuel d'installation
Climatiseur
(Type split)
Installations-handbuch
Klimagerät
(Split-typ)
Manuale di installazione
Condizionatore d'aria
(Tipo split)
Manual de instalación
Aire acondicionado
(Tipo split)
English
1
Français
39
Deutsch
77
Italiano
115
Español
153
Toshiba XXXXXXX(X/X)
Toshiba XXXXXXX(X/X)

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAV-SM564UT-E

  • Page 1 Not accessible to the general public Vente interdite au grand public Kein öffentlicher Zugang Model name: Non accessibile a clienti generici No destinado al público en general 4-way Air Discharge Cassette Type RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E Installation Manual English Air conditioner (Split type) Manuel d’installation...
  • Page 2: Table Of Contents

    11 TROUBLE SHOOTING ..........35 – 1 – 1-EN Toshiba XXXXXXX(X/X)
  • Page 3: Accessory Parts

    • The wireless type remote controller is designed to be installed by attaching a wireless remote controller kit (sold separately) to the standard panel. (The wireless remote controller kit consists of a wireless remote controller and adjust corner caps with a receiver section.) – 2 – 2-EN Toshiba XXXXXXX(X/X)
  • Page 4: Precautions For Safety

    If the refrigerant pipe is disconnected while the compressor is working with the valve open, the compressor sucks air and the refrigeration cycle is overpressurized, which may cause a burst or injury. – 3 – 3-EN Toshiba XXXXXXX(X/X)
  • Page 5 Excessive tightening of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage. • Wear heavy gloves during the installation work to avoid injury. – 4 – 4-EN Toshiba XXXXXXX(X/X)
  • Page 6: Selection Of Installation Place

    • Place where organic solvent is used. • Place near a door or window exposed to humid outside air (Dew droping may form.). • Place where special spray is used frequently. – 5 – 5-EN Toshiba XXXXXXX(X/X)
  • Page 7: Installation Space

    Therefore, it is necessary to change the setup value of the high ceiling switch or discharge direction. The high-ceiling setting is also necessary when installing separately sold filters. – 6 – 6-EN Toshiba XXXXXXX(X/X)
  • Page 8 3 directions 2 directions • Use a shielding plate kit (sold separately) to change discharge directions. Discharge directions are limited. Follow the Installation Manual supplied with the shielding plate kit. Shielding plate (sold separately) – 7 – 7-EN Toshiba XXXXXXX(X/X)
  • Page 9: Installation

    Ceiling panel (sold separately) Knockout square hole for divide duct For Ø150 Knockout square hole for humidifier (mm) Model RAV SM56 Type Ø6.4 Ø12.7 SM80 Type Ø9.5 Ø15.9 SM110 Type Ø9.5 Ø15.9 SM140 Type Ø9.5 Ø15.9 – 8 – 8-EN Toshiba XXXXXXX(X/X)
  • Page 10 Use a hole-in anchors, hole-in plugs, or a hole-in bolts. the panel fixing screws of the indoor unit. • When hanging a ceiling, open the ceiling along the outside dimensions of the installation pattern. Indoor unit Panel fixing screw Installation pattern (Accessory) hole – 9 – 9-EN Toshiba XXXXXXX(X/X)
  • Page 11 * Install with the marking shown in the figure. “UP” facing up. Nut (M10 or W3/8) Be sure to remove the cushion for transportation between the fan and the bell mouth. – 10 – 10-EN Toshiba XXXXXXX(X/X)
  • Page 12 Be sure to pass the remote controller cord through upper side of the refrigerant pipe and drain pipe. • Do not leave the remote controller at a place exposed to the direct sunlight and near a stove. – 11 – 11-EN Toshiba XXXXXXX(X/X)
  • Page 13: Drain Piping Work

    It may cause an abnormal sound. 1.5m to 2m Support Socket for VP25 vinyl chloride pipe bracket (To be local procure) 1/100 or more Heat insulator downward – 12 – 12-EN Toshiba XXXXXXX(X/X)
  • Page 14 If doing so, the drain pump motor operates. • Test water drain while checking the operation sound of the drain pump motor. (If the operation sound changes from continuous sound to intermittent sound, water is normally drained.) – 13 – 13-EN Toshiba XXXXXXX(X/X)
  • Page 15 Heat insulator of the Heat insulator (to drain connecting be procured locally) section (Accessory) * Direct the slits and seams of the heat insulator upward to avoid water leakage. – 14 – 14-EN Toshiba XXXXXXX(X/X)
  • Page 16: Refrigerant Piping And Evacuating

    * In case of flaring for R410A with the conventional flare tool, pull it out approx. 0.5 mm more than that for R22 to adjust to the specified flare size. The copper pipe gauge is useful for adjusting projection margin size. – 15 – 15-EN Toshiba XXXXXXX(X/X)
  • Page 17: Air Purge

    • Shape of valve differs according to the outdoor Use a leak detector manufactured exclusively for unit. HFC refrigerant (R410A, R134a, etc.). For details of installation, refer to the Installation Manual of the outdoor unit. – 16 – 16-EN Toshiba XXXXXXX(X/X)
  • Page 18 (The pipe exposed to the outside causes water leak.) • Wrap heat insulator with its slits facing up (ceiling side). Indoor unit Union Heat Heat insulation pipe insulator of Flare nut (Accessory) the pipe – 17 – 17-EN Toshiba XXXXXXX(X/X)
  • Page 19: Electrical Work

    The coating may melt resulting in an accident. • After connecting wires to the terminal blocks, provide a trap and fix wires with the cord clamp. • Run the refrigerant piping line and control wiring line in the same line. – 18 – 18-EN Toshiba XXXXXXX(X/X)
  • Page 20 When twin system are connected, clamp two cables Remote with one cable clamp. controller terminal Wire Cable clamping block Specification type position Cabtyre 4-core stranded Side D cable wire 2.5mm² Cabtyre 4-core stranded Side C cable wire 1.5mm² Cord clamp – 19 – 19-EN Toshiba XXXXXXX(X/X)
  • Page 21: Remote Controller Wiring

    Indoor side Connecting wire Indoor/Outdoor connecting wires Indoor power inter-unit wiring Outdoor side 220-240V~ * For details of wiring/installation of the remote controller, refer to the Installation Manual enclosed to in the remote controller. – 20 – 20-EN Toshiba XXXXXXX(X/X)
  • Page 22: Applicable Controls

    Select the indoor unit you want to change settings for. The fan of the selected unit runs and the louvers start swinging. You can confirm the indoor unit for which you want to change settings. – 21 – 21-EN Toshiba XXXXXXX(X/X)
  • Page 23 High Efficiency Filter (65%) and then set the data of CODE No. [5d] to “0000” 0003 High Efficiency Filter (90%) in “When installing separately sold filters” on this page. – 22 – 22-EN Toshiba XXXXXXX(X/X)
  • Page 24: Filter Sign

    (left side of the button). Each time you push the button, unit numbers change as follows: Unit No. Unit No. Unit No. Unit No. display The fan of the selected unit runs and the louvers start swinging. – 23 – 23-EN Toshiba XXXXXXX(X/X)
  • Page 25 Refrigerant pipe When the setting has been determined, lights up. 6. Push button to complete the setting. Drain pipe 0001-0005 (Louver lock position code) 4. Push button. 5. Push button to complete the setting. – 24 – 24-EN Toshiba XXXXXXX(X/X)
  • Page 26 This function is available to call the service hours (x100h) monitor mode from the remote controller during a test run to acquire temperatures of sensors of the remote controller, indoor unit, and outdoor unit. – 25 – 25-EN Toshiba XXXXXXX(X/X)
  • Page 27 For this reason, Indoor address (Example of address setup change) change the setting to match line addresses with indoor addresses. After setup change of Address: 1-1-1 Address: 2-1-2 Address: 2-2-2 manual address – 26 – 26-EN Toshiba XXXXXXX(X/X)
  • Page 28 (CODE No. [12]: Line address) 2. Using timer time buttons, change the line address from [3] to [2]. 3. Push button. In this time, the setup finishes when the display changes from flashing to lighting. – 27 – 27-EN Toshiba XXXXXXX(X/X)
  • Page 29 1 To recognize the position of the minute.) corresponding indoor unit though the indoor unit No. is known Check the position during operation stop. (Be sure to stop operation of the set.) – 28 – 28-EN Toshiba XXXXXXX(X/X)
  • Page 30 Push button.(Setup is determined.) When pushing button, the display disappears and the status Becomes the usual stop status. (When pushing button the operation from the remote controller is not accepted for approx. 1 minute.) – 29 – 29-EN Toshiba XXXXXXX(X/X)
  • Page 31: Test Run

    (Display part is same as procedure 1.) Procedure Push check button to cancel (release from) the test run mode. ([TEST] disappears on the display and the status returns to a normal.) – 30 – 30-EN Toshiba XXXXXXX(X/X)
  • Page 32 10 seconds, and the air conditioner starts operation. If any of these indicators does not flash, repeat procedures Procedure Upon completion of the test run, push “ON/OFF” button to stop operation. – 31 – 31-EN Toshiba XXXXXXX(X/X)
  • Page 33 “ ” disappears and “SETTING” flashes. (It takes 5 minutes.) Remote controller Indoor unit 5. When “SETTING” disappears, re-setting is completed and the air conditioner enter the Outdoor unit normal operation standby mode. – 32 – 32-EN Toshiba XXXXXXX(X/X)
  • Page 34: Maintenance

    Preparation : 1. Stop the operation by remote controller. 2. Dismount the air filter. Strap to prevent falling Air filter – 33 – 33-EN Toshiba XXXXXXX(X/X)
  • Page 35 If a commercially available detergent (strong alkaline or acid) cleaning agent is used, the surface treatment of the heat exchanger will be marred, which may degrade the self cleaning performance. For details, contact the dealer. – 34 – 34-EN Toshiba XXXXXXX(X/X)
  • Page 36: Trouble Shooting

    • [01 : Order of trouble history] is displayed in CODE No. window. • [Check code] is displayed in CHECK window. • [Indoor unit address in which an error occurred] is displayed in Unit No. – 35 – 35-EN Toshiba XXXXXXX(X/X)
  • Page 37 Entire stop of the IGBT heat sink. Temp. sensor Outdoor Temp. sensor (TE/TS) may be connected incorrectly. Entire stop connection error Indoor unit, other P.C. Indoor Indoor P.C. board --- EEPROM error Auto-reset board error – 36 – 36-EN Toshiba XXXXXXX(X/X)
  • Page 38 Entire stop protective operation Outdoor unit fan motor, outdoor unit P.C. board --- An Outdoor unit fan error Outdoor error (overcurrent, locking, etc.) was detected in the Entire stop outdoor unit fan drive circuit. – 37 – 37-EN Toshiba XXXXXXX(X/X)
  • Page 39 : The air conditioner automatically enters the auto-address setting mode. ALT: When two LEDs are flashing, they flash alternately. SIM: When two LEDs are flashing, they flash in synchronization. Receiving unit display OR: Orange GR: Green – 38 – 38-EN Toshiba XXXXXXX(X/X)
  • Page 40 +00EH99858901_01EN_4-way_IM_printOnly.book Page 39 Tuesday, December 4, 2007 2:31 PM EH99858901 Toshiba XXXXXXX(X/X)