System Configuration - Mitsubishi Electric PURY-EP200 Service Handbook

Hide thumbs Also See for PURY-EP200:
Table of Contents

Advertisement

[ II Restrictions ]
II Restrictions

[1] System configuration

1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
(1) Standard combinations
Outdoor
Composing units
units
P250
-
P300
-
P350
-
P400
-
P500
P250
P550
P250
P600
P300
P650
P300
P700
P300
P750
P350
P800
P400
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
(2) High COP combinations
Outdoor
Composing units
units
EP200
-
EP300
-
EP400
EP200
EP450
EP200
EP500
EP200
EP550
(E)P250
EP600
EP300
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
HWE0713A
Maximum total capacity
of connectable indoor
units
-
125 - 375
-
150 - 450
-
175 - 525
-
200 - 600
P250
250 - 750
P300
275 - 825
P300
300 - 900
P350
325 - 975
P400
350 - 1050
P400
375 - 1125
P400
400 - 1200
Maximum total capacity
of connectable indoor
units
-
100 - 300
-
150 - 450
EP200
200 - 600
(E)P250
225 - 675
EP300
250 - 750
EP300
275 - 825
EP300
300 - 900
Maximum number
of connectable in-
door units
25
R410A series indoor units
30
35
40
50
Maximum number
of connectable in-
door units
20
P15 - P250 models
R410A series indoor units
30
40
45
50
- 17 -
Types of connectable in-
door units
Types of connectable in-
door units
GB