[ IX Troubleshooting ]
1. Error Code
6607
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. System configuration
(1) System with one heat source unit
Error
Error dis-
Detection
source
play
address
Heat
ME re-
No ac-
source
mote con-
knowl-
unit (OC)
troller
edgement
(RC)
(ACK) at
MA re-
IC trans-
mote con-
mission to
troller
OC
(MA)
BC con-
ME re-
No ac-
troller
mote con-
knowl-
(BC)
troller
edgement
(RC)
(ACK) at
MA re-
IC trans-
mote con-
mission to
troller
BC
(MA)
Indoor
ME re-
No ac-
unit (IC)
mote con-
knowl-
troller
edgement
(RC)
(ACK) at
MA re-
RC trans-
mote con-
mission to
troller
IC
(MA)
LOSS-
ME re-
No ac-
NAY
mote con-
knowl-
(LC)
troller
edgement
(RC)
(ACK) at
MA re-
IC trans-
mote con-
mission to
troller
LC
(MA)
ME re-
ME re-
No ac-
mote
mote con-
knowl-
control-
troller
edgement
ler (RC)
(RC)
(ACK) at
MA re-
IC trans-
mote con-
mission to
troller
RC
(MA)
HWE09080
method
(1)
Contact failure of transmission line of OC or IC
(2)
Decrease of transmission line voltage/signal by ex-
ceeding acceptable range of transmission wiring.
Farthest:200 m [656ft] or less
Remote controller wiring:
10m [32ft] or less
(3)
Erroneous sizing of transmission line (Not within the
range below). Wire diameter:
2
1.25mm
[AWG16] or more
(4)
Heat source unit control board failure
(1)
When BC controller address is changed or modified
during operation.
(2)
Faulty or disconnected transmission wiring of BC
controller
(3)
Disconnected connector of BC controller (CN02)
(4)
Faulty control board of BC controller
(1)
When IC unit address is changed or modified during
operation.
(2)
Faulty or disconnected IC transmission wiring
(3)
Disconnected IC connector
(CN2M)
(4)
Indoor unit controller failure
(5)
ME remote controller failure
(1)
The power source of LOSSNAY has been shut off.
(2)
When the address of LOSSNAY is changed in the
middle of the operation
(3)
Faulty or disconnected transmission wiring of
LOSSNAY
(4)
Disconnected connector (CN1) on LOSSNAY
(5)
Controller failure of LOSSNAY
(1)
Faulty transmission wiring at IC unit side.
(2)
Faulty wiring of the transmission line for ME remote
controller
(3)
When the address of ME remote controller is
changed in the middle of the operation
(4)
ME remote controller failure
Cause
- 269 -
Check method and remedy
Turn off the power
source of the heat
source unit, and turn it
on again.
If the error is accidental,
it will run normally. If not,
check the causes (1) -
(4).
Turn off the heat source-
indoor units for 5 or
more minutes, and turn
them on again.
If the error is accidental,
they will run normally. If
not, check the causes
(1) - (4).
Turn off the heat source-
indoor units for 5 or
more minutes, and turn
them on again.
If the error is accidental,
they will run normally.
If not, check the causes
(1) - (5).
Turn off the power
source of LOSSNAY
and turn it on again.
If the error is accidental,
it will run normally.
If not, check the causes
(1) - (5).
Turn off the power
source of the heat
source unit for 5 minutes
or more, and turn it on
again.
If the error is accidental,
it will run normally.
If not, check the causes
(1) - (4).
GB