Mitsubishi Electric PUHZ-SHW80VHA Service Manual page 6

Heat pump air conditioner
Hide thumbs Also See for PUHZ-SHW80VHA:

Advertisement

3- 3. P R E C A U T I O N S W HE N R E U S I N G
( 1 ) F lowc h art
T he ex i sting pipe thickness meets speci-
f ications and the pipes are not damaged.
Check if ex isting air conditioner can operate.
Ex i sting air conditioner can
operate.
Perf orm cooling operation
f or about 30 minutes and
then do a pump down work.
Disconnect ex i sting air con-
ditioner f rom piping.
Ex isting pipes can be reused.
Connect a new air conditioner.
C onnecti ng a new
1 Flaring work should be done so that f lare meets the dimension f or R 410A.
Use f lare nut provided with indoor and outdoor unit.
2 W hen using gas piping of [19. 05mm f or SH W 112, 140.
Make sure that DI P SW 8-1 on outdoor unit controller board is set to ON. T his is to keep
the pressure on pipes within permissible range.
3
Make sure that DI P SW 8-1 on outdoor unit controller board is set to ON. T his is to
prevent oil f low ratio f rom lowering due to the decrease in f lowing ref rigerant.
4
T he pipes can be reused.
OCH526C
E X I S T I N G
Measure the ex i sting pipe thickness and check f or damage.
Ex i sting air conditioner
cannot operate.
Use a ref rigerant recovery
eq uipment to recover the
ref rigerant.
Note:
I n case ex i sting pipes were used
f or gas or oil heat pump system,
be sure to clean the pipes.
ai r condi ti oner
R 2 2 R E F R I G E R A N T P I P E S
T he ex isting pipe thickness does not meet
specif ications or the pipes are damaged.
Ex i sting pipes cannot be
reused. Use new pipes.
S H W · H A