Additional Refrigerant Charge - Mitsubishi Electric PURY-(E)P-YLM-A (-BS) Installation Manual

Air-conditioners for building application
Table of Contents

Advertisement

Available languages

Available languages

9-9. Additional refrigerant charge

Charge refrigerant in a liquid state.
- Charging refrigerant in the gaseous state will change the composition of the refrigerant and lead
to a performance drop.
Do not use a charging cylinder when charging refrigerant.
- The use of a charging cylinder may change the composition of the refrigerant and lead to a
performance drop.
The amount of refrigerant that is shown in the table below is factory-charged in the outdoor units. The amount
necessary for extended piping is not included and needs to be added on site.
Unit model
Factory-charged amount [kg (oz)]
P200
P250
P300
P350
P400
P450
P500
The amount of refrigerant that is shown in the table below is the maximum amount to be added on site.
Unit model
Maximum amount to be added [kg (oz)]
P200YLM
P250YLM
P300YLM
P350YLM
P400YLM
P400YSLM
P450YLM
P450YSLM
P500YLM
P500YSLM
P550YSLM
P600YSLM
P650YSLM
P700YSLM
P750YSLM
P800YSLM
P850YSLM
P900YSLM
Both refrigerant overcharge and undercharge will cause problems. Charge the system with the proper amount of
refrigerant.
Record the added refrigerant amount on the label attached to the control box panel for future servicing.
9-9-1. Calculation of the amount of additional refrigerant
・The amount of refrigerant to be added depends on the size and the total length of the high-pressure piping and
liquid piping.
・Calculate the amount of refrigerant to be charged according to the formula below.
・Round up the calculation result to the nearest 0.1 kg (0.1 oz).
・Refer to the HBC controller Installation Manual for the additional amount of refrigerant for a Hybrid City Multi
system.
・The refrigerant does not need to be added for the indoor units in a Hybrid City Multi system.
WT07282X01
9.5 (335)
9.5 (335)
10.3 (363)
10.3 (363)
10.3 (363)
11.8 (416)
11.8 (416)
27.5 (970)
33.5 (1182)
37.0 (1305)
39.0 (1376)
45.0 (1587)
52.0 (1834)
49.0 (1728)
52.0 (1834)
49.0 (1728)
52.0 (1834)
59.0 (2081)
62.5 (2205)
75.0 (2646)
79.5 (2804)
79.5 (2804)
79.5 (2804)
84.0 (2963)
89.0 (3139)
GB-35
Unit model
Factory-charged amount [kg (oz)]
EP200
EP250
EP300
EP350
EP400
EP450
EP500
Unit model
Maximum amount to be added [kg (oz)]
EP200YLM
EP250YLM
33.5 (1182)
EP300YLM
37.0 (1305)
EP350YLM
39.0 (1376)
EP400YLM
45.0 (1587)
EP450YLM
49.0 (1728)
EP500YLM
49.0 (1728)
EP500YSLM
52.0 (1834)
EP550YSLM
59.0 (2081)
EP600YSLM
62.5 (2205)
EP650YSLM
75.0 (2646)
EP700YSLM
79.5 (2804)
EP750YSLM
79.5 (2804)
EP800YSLM
79.5 (2804)
EP850YSLM
84.0 (2963)
EP900YSLM
89.0 (3139)
8.5 (299)
8.5 (299)
9.3 (328)
9.3 (328)
11.8 (416)
11.8 (416)
11.8 (416)
27.5 (970)

Hide quick links: