• Number of modules connected to the bus conversion module
(Page 53 Connection to the bus conversion module (connection with FX3 extension devices))
Type
Total No. of intelligent function modules
Check on limitations when using extension devices
Check the use of the extension devices.
■Use of the bus conversion module
(Page 49 Bus conversion module)
Limitations
FX3 extension modules are connected on the right side of the bus conversion module.
FX5 extension modules are connected on the left side of the bus conversion module.
■Connection of intelligent function modules
(Page 49 Limitations on intelligent function modules)
Model
FX3U-128ASL-M
FX3U-64CCL
No. of modules used Limitations
5
Limitations
Only one module may be connected to the system.
Only one module may be connected to the system.
4.5 Rules of System Configuration and Examples of Reconfiguration
Up to 6
(When not using extension power supply modules)
4 SYSTEM CONFIGURATION
Judgment
OK
Judgment
4
OK
OK
Judgment
OK
OK
65