Toshiba 2000 User Manual page 27

Integrated controller
Hide thumbs Also See for 2000:
Table of Contents

Advertisement

Status LED
ONL
(green)
OFL
(red)
DIAG
(red)
ACC
(green)
LED under ONL LED is always OFF.
Transmission cable terminating resistor specification switch (TERM)
TERM (terminating resistor)
Turn on at nodes on both ends.
Transmission cable connector (PROFIBUS-DP)
PROFIBUS-DP transmission cable connector.
Reset switch (RESET)
Press when the PF612 is abnormal or when initializing the PF612 independent of the
controller.
6F8C1147
2.5 Name of PF612 Module Components and Parts
Table 2-6 Status LED
ON
Communicating
OFF
Other than communicating
ON
Non-communicating
OFF
Other than non-communicating
Cyclic flash
Setup (configuration information) error
(1 Hz)
Cyclic flash
Setup (user parameter) error
(2 Hz)
Cyclic flash
PROFIBUS ASIC initialization error
(4 Hz)
OFF
No diagnostic information
ON
Controller accessing
OFF
Controller not accessing
ON: Terminated with terminating resistor.