Power supply harmonics
• Harmonic content (Values of the fundamental current is 100%)
Reactor
Used (DC side)
Used (AC, DC sides)
• Calculation of equivalent capacity P0 of harmonic generating equipment
"Equivalent capacity" is the capacity of a 6-pulse converter converted from the capacity of consumer's harmonic generating
equipment and is calculated by the following equation: If the sum of equivalent capacities is higher than the limit (Refer to
page
75), harmonics must be calculated with the following procedure:
P0 = ∑ (Ki  Pi) [kVA]
Ki: Conversion coefficient (Refer to
Pi: Rated capacity of harmonic generating equipment
i: Number indicating the conversion circuit type
• Calculation of outgoing harmonic current
Outgoing harmonic current = fundamental wave current (value converted from received power voltage)  operation ratio 
harmonic content
• Operation ratio: Operation ratio = actual load factor  operation time ratio during 30 minutes
• Harmonic content: Refer to
• Rated capacities and outgoing harmonic currents of inverter-driven motors
Rated
current (A)
Applicable
motor (kW)
400 V
0.4
0.81
0.75
1.37
1.5
2.75
2.2
3.96
3.7
6.50
5.5
9.55
7.5
12.8
11
18.5
15
24.9
18.5
30.7
22
36.6
30
49.0
37
60.4
45
73.5
55
89.9
75
123
90
147
110
179
132
216
160
258
220
355
250
403
280
450
315
506
355
571
400
643
450
723
500
804
560
900
630
1013
76
PRECAUTIONS FOR USE OF THE INVERTER
5th
7th
30
13
8.4
28
9.1
7.2
page
75)
page
76.
Fundamental
wave current
Rated
converted
capacity
from 6.6 kV
(kVA)
(mA)
49
0.57
83
0.97
167
1.95
240
2.81
394
4.61
579
6.77
776
9.07
1121
13.1
1509
17.6
1860
21.8
2220
25.9
2970
34.7
3660
42.8
4450
52.1
5450
63.7
7455
87.2
8909
104
10848
127
13091
153
15636
183
21515
252
24424
286
27273
319
30667
359
34606
405
38970
456
43818
512
48727
570
54545
638
61394
718
11th
13th
17th
5.0
4.7
4.1
3.2

[kVA]

Outgoing harmonic current converted from 6.6 kV (mA)
(With a DC reactor, 100% operation ratio)
5th
7th
11th
14.7
6.37
4.116
24.9
10.79
6.972
50.1
21.71
14.03
72
31.20
20.16
118.2
51.22
33.10
173.7
75.27
48.64
232.8
100.9
65.18
336.3
145.7
94.16
452.7
196.2
126.8
558
241.8
156.2
666
288.6
186.5
891
386.1
249.5
1098
475.8
307.4
1335
578.5
373.8
1635
708.5
457.8
2237
969.2
626.2
2673
1158
748.4
3254
1410
911.2
3927
1702
1100
4691
2033
1313
6455
2797
1807
7327
3175
2052
8182
3545
2291
9200
3987
2576
10382
4499
2907
11691
5066
3273
13145
5696
3681
14618
6335
4093
16363
7091
4582
18418
7981
5157
19th
23rd
3.2
3.0
2.4
1.6
Rated capacity: Determined by the capacity of the
applied motor and found in Table 5. The rated
capacity used here is used to calculate the generated
harmonic amount and is different from the power
supply capacity required for actual inverter drive.
13th
17th
19th
2.45
2.303
1.568
4.15
3.901
2.656
8.35
7.849
5.344
12
11.28
7.68
19.7
18.52
12.61
28.95
27.21
18.53
38.8
36.47
24.83
56.05
52.69
35.87
75.45
70.92
48.29
93
87.42
59.52
111
104.3
71.04
148.5
139.6
95.04
183
172
117.1
222.5
209.2
142.4
272.5
256.2
174.4
372.8
350.4
238.6
445.5
418.7
285.1
542.5
509.9
347.1
654.6
615.3
418.9
781.8
734.9
500.4
1076
1011
688.5
1221
1148
781.6
1364
1282
872.7
1533
1441
981.3
1730
1627
1107
1949
1832
1247
2191
2059
1402
2436
2290
1559
2727
2564
1745
3070
2886
1965
25th
2.2
1.4
23rd
25th
1.47
1.078
2.49
1.826
5.01
3.674
7.2
5.28
11.82
8.67
17.37
12.74
23.28
17.07
33.63
24.66
45.27
33.2
55.8
40.92
66.6
48.84
89.1
65.34
109.8
80.52
133.5
97.9
163.5
119.9
223.7
164
267.3
196
325.4
238.7
392.7
288
469.1
344
645.5
473.3
732.7
537.3
818.2
600
920
674.7
1038
761.3
1169
857.3
1315
964
1462
1072
1636
1200
1842
1351