S4 ELEMENTS
5.6.12 Harmonics
5.6.12.1 Main Menu
HARMONICS
5.6.12.2 THD Level
W1 THD LEVEL [
5–88
PATH: SETPOINTS
S4 ELEMENTS

[
]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
This section contains the settings to configure the total harmonic distortion monitoring
elements. Included are a THD level element for each winding and each phase.
PATH: SETPOINTS
S4 ELEMENTS

]
W1 THD LEVEL
FUNCTION: Disabled
W1 THD LEVEL
MESSAGE
RLYS (1-8): --------
W1 THD LEVEL
MESSAGE
TARGET: Self-Reset
MINIMUM OPERATING
MESSAGE
CURRENT: 0.10 x CT
W1 THD LEVEL
MESSAGE
PICKUP: 50.0% f0
W1 THD LEVEL
MESSAGE
DELAY: 10 s
W1 THD LEVEL
MESSAGE
BLOCK: Disabled
MINIMUM OPERATING CURRENT: Enter the minimum value of current (in units of relay
nominal current) required to allow the THD level element to operate.
W1(3) THD PICKUP LEVEL: Enter the total harmonic distortion (in %ƒ
the winding 1(3) total harmonic distortion element level will pickup and start the delay
timer.
W1(3) THD LEVEL DELAY: Enter the time that the total harmonic distortion must
remain above the pickup level before the element operates.
HARMONICS

W1 THD LEVEL [
]
W2 THD LEVEL [
]
W3 THD LEVEL [
]
W1 HARMONIC
[
]
DERATING
W2 HARMONIC
[
]
DERATING
W3 HARMONIC
[
]
DERATING
HARMONICS

745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
See page 5–88
See page 5–88
See page 5–88
See page 5–89
See page 5–89
See page 5–89
W1(3) THD LEVEL
Range:
Enabled, Disabled
Range:
1 to 8
Range:
Self-Reset, Latched, None
Range:
0.03 to 1.00 x CT in steps of
0.01
Range:
0.1 to 50.0% f
in steps of 0.1
0
Range:
0 to 60000 s in steps of 1
Range:
Logc Inpt 1 to 16, Virt Inpt 1 to
16, Output Rly 2 to 8, SelfTest
Rly, Vir Outpt 1 to 5, Disabled
) above which
0