LG ARNU363SVA4 Engineering Manual

LG ARNU363SVA4 Engineering Manual

Multi v; art cool mirror wall-mounted; standard wall-mounted; art cool gallery; wall-mounted indoor unit
Hide thumbs Also See for ARNU363SVA4:

Advertisement

EM_MultiV_WallMounted_IndoorUnits_3_16
WALL-MOUNTED INDOOR UNIT
ENGINEERING MANUAL
Art Cool™ Mirror Wall-Mounted
Standard Wall-Mounted
5,500 to 24,200 Btu/h
5,500 to 35,500 Btu/h
Art Cool™ Gallery
9,600 and 12,300 Btu/h

Advertisement

Table of Contents
loading

Summary of Contents for LG ARNU363SVA4

  • Page 1 EM_MultiV_WallMounted_IndoorUnits_3_16 WALL-MOUNTED INDOOR UNIT ENGINEERING MANUAL Art Cool™ Mirror Wall-Mounted Standard Wall-Mounted 5,500 to 24,200 Btu/h 5,500 to 35,500 Btu/h Art Cool™ Gallery 9,600 and 12,300 Btu/h...
  • Page 2 A summary list of safety precautions is on page 3. For more technical materials such as submittals, catalogs, installation, owner’s, and service manuals, visit www.lghvac.com. For continual product development, LG Electronics U.S.A., Inc. reserves the right to change specifications without notice. © LG Electronics U.S.A., Inc.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS Unit Nomenclature ................. 4 Standard Wall-Mounted Indoor Units ........... 41-66 ..............42 LATS Overview ..................5 ................43-44 ................... 45 Art Cool™ Gallery Indoor Units ............7-18 ..............46-48 ..............8 ............. 49-50 ..................9 ..............51 ..................
  • Page 4: Unit Nomenclature

    UNIT NOMENCLATURE Family ARN = Multi V Indoor Unit (Refrigerant R410A) Type U = DC Inverter Heat Pump Indoor Unit Nominal Capacity 05 = 5,000 Btu/h 18 = 18,000 Btu/h 42 = 42,000 Btu/h 07 = 7,000 Btu/h 24 = 24,000 Btu/h 48 = 48,000 Btu/h 09 = 9,000 Btu/h 28 = 28,000 Btu/h...
  • Page 5: Lats Overview

    ® To ensure that the refrigerant piping design meets LG’s quality standards, a LATS refrigerant piping design must be provided with every Multi V order. Following the installation, if any changes or variations to the design are necessary, a new LATS file must be created and provided to LG prior to system commissioning to ensure the proper pipe size has not changed.
  • Page 6 © 6 | INTRODUCTION...
  • Page 7: Art Cool™ Gallery Indoor Units

    ART COOL GALLERY Mechanical Specifications on page 8 General Data on page 9 Electrical Data on page 9 External Dimensions on page 10 Electrical Wiring Diagram on page 11 Refrigerant Flow Diagrams on page 12 Acoustic Data on page 13 Air Velocity / Temperature Distribution on page 15 Capacity Tables on page 16...
  • Page 8: Art Cool Gallery

    Handling Condensate Microprocessor Control The unit is designed for gravity draining of condensate. LG provides a factory insulated flexible drain hose. If condensate lift/pumps are The unit is provided with an integrated microprocessor controller ca- needed for the application, they are to be field provided.
  • Page 9: General Data

    ART COOL GALLERY General Data / Electrical Data Table 1: Art Cool Gallery (SF Frames) Indoor Unit General Data. Model No. ARNU093SFA4 ARNU123SFA4 Capacity (Btu/h) 9,600 12,300 Power Input Capacity (Btu/h) 10,900 13,600 Power Input Cooling Max (°F WB) Heating Min (°F DB) Refrigerant Type R410A R410A...
  • Page 10: External Dimensions

    ART COOL GALLERY SF Frame Figure 2: ARNU093SFA4 and ARNU123SFA4 Dimensions. Air Inlet Grille 5-3/4 23-5/8 Air Outlet Grille Air Outlet Grille Piping Access Hole Air Outlet Grille Attachment Hole 19-11/16 Unit: inches Note: All measurements Attachment Hole have a tolerance of 1/4 in. ©...
  • Page 11: Electrical Wiring Diagram

    ART COOL GALLERY Electrical Wiring Diagram SF Frame Figure 3: ARNU093SFA4 and ARNU123SFA4 Wiring Diagram. Table 3: SF Frame Wiring Diagram Legend. PCB Connection Purpose Function CN-TH3 Pipe out thermistor Pipe out thermistor connection CN-TH2 Pipe in thermistor Pipe in thermistor connection CN-TH1 Return air thermistor Return air thermistor connection...
  • Page 12: Refrigerant Flow Diagrams

    ART COOL GALLERY Refrigerant Flow Diagram SF Frame Figure 4: SF Frame Piping Diagram. Table 4: SF Frame Refrigerant Pipe Connection Port Diameters. Model Liquid (inch) Vapor (inch) ARNU093SFA4 1/4 Flare 1/2 Flare ARNU123SFA4 1/4 Flare 1/2 Flare Table 5: SF Frame Thermistors. Thermistor Description Return air thermistor...
  • Page 13: Acoustic Data

    ART COOL GALLERY Figure 5: Sound Pressure Measurement Location. • Measurements are taken 3.3 ft away from the front of the unit. • Sound pressure levels are measured in dB(A) with a tolerance of ±3. • Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. Operating Conditions: •...
  • Page 14 ART COOL GALLERY Table 7: Art Cool Gallery Indoor Unit Sound Power Levels. • Data is valid under diffuse field conditions. • Data is valid under nominal operating conditions. Sound Power Levels dB(A) Model • Sound power level is measured using rated conditions, and tested High Fan Speed in a reverberation room per ISO 3741 standards.
  • Page 15: Air Velocity / Temperature Distribution

    ART COOL GALLERY ARNU093SFA4, ARNU123SFA4 Figure 8: ARNU093SFA4. Cooling Heating Discharge angle: 40° Discharge angle: 50° Air velocity (m/s [ft./s]) Air velocity (m/s [ft./s]) 2.7m (8.9 ft.) 2.7m (8.9 ft.) 2m (6.6 ft.) 2m (6.6 ft.) 2.0(6.6) 2.0(6.6) 1m (3.3 ft.) 1m (3.3 ft.) 1.5(4.9) 1.5(4.9)
  • Page 16: Capacity Tables

    ART COOL GALLERY ARNU093SFA4, ARNU123SFA4 Table 8: ARNU093SFA4, ARNU123SFA4 Cooling Capacity Table. Indoor Air Temperature (°F DB / WB) Outdoor Model No. / 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76 Air Temp.
  • Page 17 ART COOL GALLERY ARNU093SFA4, ARNU123SFA4 Table 9: ARNU093SFA4, ARNU123SFA4 Heating Capacity Table. Indoor Air Temperature (°F DB) Outdoor Air Temp. Model No. / Capacity Index °F DB °F WB -4.0 -4.4 -0.4 10.0 15.0 14.0 20.0 19.0 25.0 23.0 10.4 10.4 10.4 10.4...
  • Page 18 © 18 | ART COOL...
  • Page 19: Art Cool™ Mirror Wall-Mounted Indoor Units

    ART COOL MIRROR WALL-MOUNTED Mechanical Specifications on page 20 General Data on page 21 Electrical Data on page 22 External Dimensions on page 23 Electrical Wiring Diagram on page 25 Refrigerant Flow Diagrams on page 26 Acoustic Data on page 27 Air Velocity / Temperature Distribution on page 30 Capacity Tables on page 35...
  • Page 20: Mechanical Specifications

    Handling Condensate 18-24 MBh The unit is designed for gravity draining of condensate. LG provides The indoor unit is provided with a motorized sweeping guide vane a factory insulated flexible drain hose. If condensate lift / pumps are that automatically changes the direction of airflow from side-to-side needed for the application, they are to be field provided.
  • Page 21: General Data

    ART COOL MIRROR General Data Table 10: Art Cool Mirror Wall-Mounted (SB, SC Frames) Indoor Unit General Data. Model No. ARNU053SBR4 ARNU073SBR4 ARNU093SBR4 ARNU123SBR4 ARNU153SBR4 ARNU183SCR4 ARNU243SCR4 Capacity (Btu/h) 5,500 7,500 9,600 12,300 15,400 19,100 24,200 Power Input 39.5 39.5 Capacity (Btu/h) 6,100 8,500...
  • Page 22: Electrical Data

    ART COOL MIRROR Electrical Data Table 11: Art Cool Mirror Wall-Mounted Indoor Unit Electrical Data. Power Supply Power Input (W) Voltage Model Number Rated Amps (A) Range Volts Phase Cooling Heating ARNU053SBR4 0.16 ARNU073SBR4 0.16 ARNU093SBR4 187-253 0.16 208-230V ARNU123SBR4 0.16 ARNU153SBR4 0.16...
  • Page 23: External Dimensions

    ART COOL MIRROR SB Frame Figure 10: ARNU053SBR4, ARNU073SBR4, ARNU093SBR4, ARNU123SBR4, ARNU153SBR4 Dimensions. 12-1/8 12-1/8 5-1/16 Air Inlet Grille 35-1/4 8-1/8 Front Panel 11-7/16 1-13/16 7-1/2 Access Display and Signal Receiver Access Hole Hole 26-5/8 12-7/8 Installation Plate 10-7/16 Unit: inches Note: All measurements 16-5/8 have a tolerance of 1/4 in.
  • Page 24 ART COOL MIRROR SC Frame Figure 11: ARNU183SCR4, ARNU243SCR4 Dimensions. 14-1/4 14-1/4 7-1/2 Air Inlet Grille 40-9/16 9-11/16 Front Panel 12-13/16 Access Access 1-13/16 Display and Signal Receiver Hole Hole Installation Plate Place a level on raised tab Unit Outline 18-1/8 22-7/16 2-13/16...
  • Page 25: Electrical Wiring Diagram

    ART COOL MIRROR Electrical Wiring Diagram Figure 12: ARNU053~153SBR4 and ARNU183-243SCR4 Wiring Diagram. Table 12: SB and SC Frame Wiring Diagram Legend. PCB Connection Purpose Function CN-POWER AC Power supply AC Power line input for indoor controller CN-MOTOR Fan motor output Motor output of BLDC CN-HVB* Air cleaner*...
  • Page 26: Refrigerant Flow Diagrams

    ART COOL MIRROR Refrigerant Flow Diagram Figure 13: SB, SC Frame Piping Diagram. Cooling Heat Exchanger Heating Filter C.F.F. Filter lndoor unit Table 13: SB, SC Frame Refrigerant Pipe Connection Port Diameters. Model Liquid (inch) Vapor (inch) ARNU053SBR4 ARNU073SBR4 ARNU093SBR4 1/4 Flare 1/2 Flare ARNU123SBR4...
  • Page 27: Acoustic Data

    ART COOL MIRROR Figure 14: Sound Pressure Measurement Location. • Measurements are taken 3.3 ft away from the front of the unit. • Sound pressure levels are measured in dB(A) with a tolerance of ±3. • Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. Operating Conditions: •...
  • Page 28 ART COOL MIRROR Figure 16: ARNU123SBR4 and ARNU153SBR4 Sound Pressure Level Diagrams. ARNU123SBR4 ARNU153SBR4 Figure 17: ARNU183SCR4 and ARNU243SCR4 Sound Pressure Level Diagrams. ARNU183SCR4 ARNU243SCR4 © 28 | ART COOL...
  • Page 29 ART COOL MIRROR Table 16: Art Cool Mirror Wall-Mounted Indoor Unit Sound Power Levels. • Data is valid under diffuse field conditions. • Data is valid under nominal operating conditions. Sound Power Levels dB(A) Model • Sound power level is measured using rated conditions, and tested High Fan Speed in a reverberation room per ISO 3741 standards.
  • Page 30: Air Velocity / Temperature Distribution

    ART COOL MIRROR Figure 19: ARNU123SBR4 and ARNU153SBR4 Sound Power Level Diagrams. ARNU123SBR4 ARNU153SBR4 Figure 20: ARNU183SCR4 and ARNU243SCR4 Sound Power Level Diagrams. ARNU183SCR4 ARNU243SCR4 © 30 | ART COOL...
  • Page 31 ART COOL MIRROR ARNU053SBR4, ARNU073SBR4 Figure 21: ARNU053SBR4. Cooling Heating Discharge angle : 40° Discharge angle : 15° Air velocity [m/s(ft/s)] Air velocity [m/s(ft/s)] 2.7m(8.9ft) 2.7m(8.9ft) 2m(6.6ft) 2m(6.6ft) 2.5(8.2) 2.5(8.2) 2.0(6.6) 1m(3.3ft) 1m(3.3ft) 2.0(6.6) 1.5(4.9) 1.5(4.9) 1.0(3.3) 1.0(3.3) 5m(16.4ft) 4m(13.1ft) 3m(9.8ft) 2m(6.6ft) 1m(3.3ft)
  • Page 32 ART COOL MIRROR ARNU093SBR4, ARNU123SBR4 Figure 23: ARNU093SBR4. Cooling Heating Discharge angle : 40° Discharge angle : 15° Air velocity [m/s(ft/s)] Air velocity [m/s(ft/s)] 2.7m(8.9ft) 2.7m(8.9ft) 2m(6.6ft) 2m(6.6ft) 3.0(9.8) 2.0(6.6) 2.5(8.2) 1m(3.3ft) 1m(3.3ft) 1.5(4.9) 2.0(6.6) 1.5(4.9) 1.0(3.3) 1.0(3.3) 1.5(4.9) 5m(16.4ft) 4m(13.1ft) 3m(9.8ft) 2m(6.6ft)
  • Page 33 ART COOL MIRROR ARNU153SBR4, ARNU183SBR4 Figure 25: ARNU153SBR4. Cooling Heating Discharge angle : 40° Discharge angle : 15° Air velocity [m/s(ft/s)] Air velocity [m/s(ft/s)] 2.7m(8.9ft) 2.7m(8.9ft) 2m(6.6ft) 2m(6.6ft) 3.0(9.8) 2.5(8.2) 2.5(8.2) 1m(3.3ft) 1m(3.3ft) 2.0(6.6) 0.5(1.6) 2.0(6.6) 1.5(4.9) 1.5(4.9) 0.5(1.6) 0.5(1.6) 1.0(3.3) 1.0(3.3) 5m(16.4ft)
  • Page 34 ART COOL MIRROR ARNU243SCR4 Figure 27: ARNU243SCR4. Cooling Heating Discharge angle : 30° Discharge angle : 10° Air velocity [m/s(ft/s)] Air velocity [m/s(ft/s)] 2.7m(8.9ft) 2.7m(8.9ft) 2m(6.6ft) 2m(6.6ft) 2.5(8.2) 2.0(6.6) 2.0(6.6) 1.5(4.9) 1.5(4.9) 1.0(3.3) 1m(3.3ft) 1m(3.3ft) 1.0(3.3) 0.5(1.6) 0.5(1.6) 0.5(1.6) 5m(16.4ft) 4m(13.1ft) 3m(9.8ft) 2m(6.6ft)
  • Page 35: Capacity Tables

    ART COOL MIRROR ARNU053SBR4, ARNU073SBR4, ARNU093SBR4 Table 17: ARNU053SBR4, ARNU073SBR4, ARNU093SBR4 Cooling Capacity Table. Indoor Air Temperature (°F DB / WB) Outdoor Model No. / 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76 Air Temp.
  • Page 36 ART COOL MIRROR ARNU123SBR4, ARNU153SBR4, ARNU183SCR4 Table 18: ARNU123SBR4, ARNU153SBR4, ARNU183SCR4 Cooling Capacity Table. Indoor Air Temperature (°F DB / WB) Outdoor Model No. / 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76 Air Temp.
  • Page 37 ART COOL MIRROR ARNU243SCR4 Table 19: ARNU243SCR4 Cooling Capacity Table. Indoor Air Temperature (°F DB / WB) Outdoor Model No. / 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76 Air Temp.
  • Page 38 ART COOL MIRROR ARNU053SBR4, ARNU073SBR4, ARNU093SBR4, ARNU123SBR4 Table 20: ARNU053SBR4, ARNU073SBR4, ARNU093SBR4, ARNU123SBR4 Heating Capacity Table. Indoor Air Temperature (°F DB) Outdoor Air Temp. Model No. / Capacity Index °F DB °F WB -4.4 -0.4 10.0 15.0 14.0 20.0 19.0 25.0 23.0 ARNU053SBR4 /...
  • Page 39 ART COOL MIRROR ARNU153SBR4, ARNU183SCR4, ARNU243SCR4 Table 21: ARNU153SBR4, ARNU183SCR4, ARNU243SCR4 Heating Capacity Table. Indoor Air Temperature (°F DB) Outdoor Air Temp. Model No. / Capacity Index °F DB °F WB -4.4 11.5 11.5 11.5 11.5 11.3 11.3 11.3 11.3 -0.4 11.8 11.8...
  • Page 40 © 40 | ART COOL...
  • Page 41: Standard Wall-Mounted Indoor Units

    STANDARD WALL-MOUNTED Mechanical Specifications on page 42 General Data on page 43 Electrical Data on page 45 External Dimensions on page 46 Electrical Wiring Diagram on page 49 Refrigerant Flow Diagrams on page 51 Acoustic Data on page 52 Air Velocity / Temperature Distribution on page 56 Capacity Tables on page 61...
  • Page 42: Mechanical Specifications

    The unit is equipped with an infrared receiver designed is statically and dynamically balanced. The fan speed is controlled to communicate with an LG wireless remote controller. In lieu of using a microprocessor-based direct digital control algorithm that wireless remote or factory return air thermistor, screw terminals on...
  • Page 43: General Data

    STANDARD WALL-MOUNTED General Data Table 22: Standard Wall-Mounted (SB Frames) Indoor Unit General Data. Model No. ARNU053SBL4 ARNU073SBL4 ARNU093SBL4 ARNU123SBL4 ARNU153SBL4 Capacity (Btu/h) 5,500 7,500 9,600 12,300 15,400 Power Input Capacity (Btu/h) 6,100 8,500 10,900 13,600 17,100 Power Input Cooling Max (°F WB) Heating Min (°F DB) Refrigerant Type R410A...
  • Page 44 STANDARD WALL-MOUNTED General Data Table 23: Standard Wall-Mounted (SC and SV Frames) Indoor Unit General Data. Model No. ARNU183SCL4 ARNU243SCL4 ARNU303SVA4 ARNU363SVA4 Capacity (Btu/h) 19,100 24,200 30,000 35,500 Power Input 39.5 39.5 67.0 104.0 Capacity (Btu/h) 21,500 27,300 32 000...
  • Page 45: Electrical Data

    ARNU303SVA4 0.64 0.51 67.0 67.0 187-253 208-230 ARNU363SVA4 1.02 0.81 104.0 104.0 MCA : Minimum Circuit Ampacity. Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits. MOP : Maximum Overcurrent Protection.
  • Page 46: External Dimensions

    STANDARD WALL-MOUNTED SB Frame Figure 28: ARNU053SBL4, ARNU073SBL4, ARNU093SBL4, ARNU123SBL4, ARNU153SBL4 Dimensions. 13-7/16 12-3/4 5-1/16 Air Inlet Grille 35-1/4 8-1/16 Front Panel 1-13/ 1 6 8-5/16 31-1/8 Access Hole Display and Signal Receiver Access Hole 26-5/8 12-7/8 Installation Plate Unit: inches Note: All measurements 16-5/8 have a tolerance of 1/4 in.
  • Page 47 STANDARD WALL-MOUNTED SC Frame Figure 29: ARNU183SCL4, ARNU243SCL4 Dimensions. Air Inlet Grille 40-9/16 9-7/8 Front Panel Display and Signal Receiver Access Hole Access Hole Place a level on raised tab Unit Outline 18-1/8 22-1/2 2-13/16 2-13/16 Installation Plate Left rear Measuring Tape Right rear piping...
  • Page 48 STANDARD WALL-MOUNTED SV Frame Figure 30: ARNU303SVA4, ARNU363SVA4 Dimensions. 46-27/32 10-7/16 40-9/16 6-9/16 6-9/16 Unit Outline 1-11/16 1-11/16 Installation plate 5-1/2 5-29/32 [Unit : inch] Left rear piping Right rear piping Note 1. Unit should be installed in compliance with the installation manual in the product box.
  • Page 49: Electrical Wiring Diagram

    STANDARD WALL-MOUNTED Electrical Wiring Diagram Figure 31: ARNU053~153SBL4 and ARNU183-243SCL4 Wiring Diagram. Table 25: SB and SC Frame Wiring Diagram Legend. PCB Connection Purpose Function CN-POWER AC Power supply AC Power line input for indoor controller CN-MOTOR Fan motor output Motor output of BLDC CN-HVB* Air cleaner*...
  • Page 50 STANDARD WALL-MOUNTED Electrical Wiring Diagram Figure 32: ARNU303SVA4 and ARNU363SVA4 Wiring Diagram. Table 26: SV Frame Wiring Diagram Legend. PCB Connection Purpose Function CN-POWER AC Power supply AC Power line input for indoor controller CN-MOTOR Fan motor output Motor output of BLDC...
  • Page 51: Refrigerant Flow Diagrams

    ARNU123SBL4 ARNU153SBL4 ARNU183SCL4 1/4 Flare 1/2 Flare ARNU243SCL4 3/8 Flare 5/8 Flare ARNU303SVA4 3/8 Flare 5/8 Flare ARNU363SVA4 Table 28: SB, SC, SV Frame Thermistors. Thermistor Description Return air thermistor Pipe in thermistor Pipe out thermistor © STANDARD | 51...
  • Page 52: Acoustic Data

    40.0 34.0 31.0 ARNU153SBL4 42.0 40.0 34.0 ARNU183SCL4 40.0 35.0 31.0 ARNU243SCL4 45.0 40.0 35.0 ARNU303SVA4 49.0 44.0 42.0 ARNU363SVA4 52.0 47.0 43.0 Figure 35: ARNU053SBL4, ARNU073SBL4, and ARNU093SBL4 Sound Pressure Level Diagrams. ARNU053SBL4 ARNU073SBL4 ARNU093SBL4 © 52 | STANDARD...
  • Page 53 STANDARD WALL-MOUNTED Figure 36: ARNU123SBL4, ARNU153SBL4, and ARNU183SCL4 Sound Pressure Level Diagrams. ARNU123SBL4 ARNU153SBL4 ARNU183SCL4 Figure 37: ARNU243SCL4, ARNU303SVA4, and ARNU363SVA4 Sound Pressure Level Diagram. ARNU183SCL4 ARNU303SVA4 ARNU363SVA4 © STANDARD | 53...
  • Page 54 (acoustic absorption coefficient) of particular area in ARNU073SBL4 54.0 which the equipment is installed. ARNU093SBL4 55.0 • ARNU123SBL4 55.0 ARNU153SBL4 58.0 ARNU183SCL4 57.0 ARNU243SCL4 62.0 ARNU303SVA4 61.0 ARNU363SVA4 63.0 Figure 38: ARNU053SBL4, ARNU073SBL4, and ARNU093SBL4 Sound Power Level Diagrams. ARNU053SBL4 ARNU073SBL4 ARNU093SBL4 © 54 | STANDARD...
  • Page 55 STANDARD WALL-MOUNTED Figure 39: ARNU123SBL4, ARNU153SBL4, and ARNU183SCL4 Sound Power Level Diagrams. ARNU183SCL4 ARNU123SBL4 ARNU153SBL4 Figure 40: AARNU243SCL4, ARNU303SVA4, and ARNU363SVA4 Sound Power Level Diagrams. ARNU303SVA4 ARNU363SVA4 ARNU243SCL4 © STANDARD | 55...
  • Page 56: Air Velocity / Temperature Distribution

    STANDARD WALL-MOUNTED ARNU053SBL4, ARNU073SBL4 Figure 41: ARNU053SBL4. Cooling Heating Discharge angle : 40° Discharge angle : 15° Air velocity [m/s(ft/s)] Air velocity [m/s(ft/s)] 2.7m(8.9ft) 2.7m(8.9ft) 2m(6.6ft) 2m(6.6ft) 2.5(8.2) 2.5(8.2) 2.0(6.6) 1m(3.3ft) 1m(3.3ft) 2.0(6.6) 1.5(4.9) 1.5(4.9) 1.0(3.3) 1.0(3.3) 5m(16.4ft) 4m(13.1ft) 3m(9.8ft) 2m(6.6ft) 1m(3.3ft) 5m(16.4ft)
  • Page 57: Arnu093Sbl4

    STANDARD WALL-MOUNTED ARNU093SBL4, ARNU123SBL4 Figure 43: ARNU093SBL4. Cooling Heating Discharge angle : 40° Discharge angle : 15° Air velocity [m/s(ft/s)] Air velocity [m/s(ft/s)] 2.7m(8.9ft) 2.7m(8.9ft) 2m(6.6ft) 2m(6.6ft) 3.0(9.8) 2.0(6.6) 2.5(8.2) 1m(3.3ft) 1m(3.3ft) 1.5(4.9) 2.0(6.6) 1.5(4.9) 1.0(3.3) 1.5(4.9) 1.0(3.3) 5m(16.4ft) 4m(13.1ft) 3m(9.8ft) 2m(6.6ft) 1m(3.3ft)
  • Page 58 STANDARD WALL-MOUNTED ARNU153SBL4, ARNU183SCL4 Figure 45: ARNU153SBL4. Cooling Heating Discharge angle : 40° Discharge angle : 15° Air velocity [m/s(ft/s)] Air velocity [m/s(ft/s)] 2.7m(8.9ft) 2.7m(8.9ft) 2m(6.6ft) 2m(6.6ft) 3.0(9.8) 2.5(8.2) 2.5(8.2) 1m(3.3ft) 1m(3.3ft) 2.0(6.6) 0.5(1.6) 2.0(6.6) 1.5(4.9) 1.5(4.9) 0.5(1.6) 0.5(1.6) 1.0(3.3) 1.0(3.3) 5m(16.4ft) 4m(13.1ft)
  • Page 59 STANDARD WALL-MOUNTED ARNU243SCL4, ARNU303SVA4 Figure 47: ARNU243SCL4. Cooling Heating Discharge angle : 30° Discharge angle : 10° Air velocity [m/s(ft/s)] Air velocity [m/s(ft/s)] 2.7m(8.9ft) 2.7m(8.9ft) 2m(6.6ft) 2m(6.6ft) 2.5(8.2) 2.0(6.6) 2.0(6.6) 1.5(4.9) 1.5(4.9) 1.0(3.3) 1m(3.3ft) 1m(3.3ft) 1.0(3.3) 0.5(1.6) 0.5(1.6) 0.5(1.6) 5m(16.4ft) 4m(13.1ft) 3m(9.8ft) 2m(6.6ft)
  • Page 60 STANDARD WALL-MOUNTED ARNU363SVA4 Figure 49: ARNU363SVA4. Cooling Heating Discharge angle: 25° Discharge angle: 35° Air velocity [m/s (ft/s) Air velocity [m/s (ft/s) 2.7m(8.9ft) 2.7m(8.9ft) 0.5(1.6) 0.5(1.6) 2m(6.6ft) 2m(6.6ft) 0.5(1.6) 0.5(1.6) 0.5(1.6) 1.5(5) 1m(3.3ft) 1m(3.3ft) 0.5(1.6) 0.5(1.6) 3.0(9.8) 1.0(3.3) 2.0(6.6) 1.0(3.3) 2.5(8.2)
  • Page 61: Capacity Tables

    STANDARD WALL-MOUNTED ARNU053SBL4, ARNU073SBL4, ARNU093SBL4 Table 31: ARNU053SBL4, ARNU073SBL4, ARNU093SBL4 Cooling Capacity Table. Indoor Air Temperature (°F DB / WB) Outdoor Model No. / 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76 Air Temp.
  • Page 62: Arnu123Sbl4

    STANDARD WALL-MOUNTED ARNU123SBL4, ARNU153SBL4, ARNU183SCL4 Table 32: ARNU123SBL4, ARNU153SBL4, ARNU183SCL4 Cooling Capacity Table. Indoor Air Temperature (°F DB / WB) Outdoor Model No. / 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76 Air Temp.
  • Page 63 STANDARD WALL-MOUNTED ARNU243SCL4, ARNU303SVA4, ARNU363SVA4 Table 33: ARNU243SCL4, ARNU303SVA4, ARNU363SVA4 Cooling Capacity Table. Indoor Air Temperature (°F DB / WB) Outdoor Model No. / 68 / 57 73 / 61 79 / 64 80 / 67 85 / 70 88 / 73 91 / 76 Air Temp.
  • Page 64 STANDARD WALL-MOUNTED ARNU053SBL4, ARNU073SBL4, ARNU093SBL4, ARNU123SBL4 Table 34: ARNU053SBL4, ARNU073SBL4, ARNU093SBL4, ARNU123SBL4 Heating Capacity Table. Indoor Air Temperature (°F DB) Outdoor Air Temp. Model No. / Capacity Index °F DB °F WB -4.4 -0.4 10.0 15.0 14.0 20.0 19.0 25.0 23.0 ARNU053SBL4 / 30.0...
  • Page 65 STANDARD WALL-MOUNTED ARNU153SBL4, ARNU183SCL4, ARNU243SCL4, ARNU303SVA4 Table 35: ARNU153SBL4, ARNU183SCL4, ARNU243SCL4, ARNU303SVA4 Heating Capacity Table. Indoor Air Temperature (°F DB) Outdoor Air Temp. Model No. / Capacity Index °F DB °F WB -4.4 11.5 11.5 11.5 11.5 11.3 11.3 11.3 11.3 -0.4 11.8...
  • Page 66 STANDARD WALL-MOUNTED ARNU363SVA44 Table 36: ARNU363SVA4 Heating Capacity Table. Indoor Air Temperature (°F DB) Outdoor Air Temp. Model No. / Capacity Index °F DB °F WB -4.0 -4.4 24.8 24.8 24.8 24.8 24.4 24.4 24.4 24.4 -0.4 25.5 25.5 25.5 25.5...
  • Page 67: Application Guidelines

    APPLICATION GUIDELINES Selecting the Best Location on page 68 General Mounting on page 69 General Drain Piping Information on page 71 Wiring Guidelines on page 73 Wired Remote Controller Location on page 75 Acronyms on page 76...
  • Page 68: Selecting The Best Location

    APPLICATION GUIDELINES Figure 50: Minimum Clearance Requirements for SF Selecting the Best Location Frame Gallery Indoor Units. Do’s • Place the unit where air circulation will not be blocked. More than 8 inches • Place the unit where drainage can be obtained easily. •...
  • Page 69: General Mounting

    APPLICATION GUIDELINES General Mounting Figure 53: Using the SF Frame General Mounting - Gallery Gallery Indoor Unit Installation Using the Installation Guide Guide. 1. Choose an appropriate location for the indoor unit. To hang the installation guide, verify that it is level Horizontal and plumb, and then tape it to the wall.
  • Page 70 APPLICATION GUIDELINES General Mounting General Mounting - Wall-Mounted Wall-mounted indoor units have several options on how the piping and wiring can be routed (see figures below). Whichever way the piping and wiring are routed out of the indoor units, the mounting wall on which the indoor unit is installed should be strong and solid enough to protect it from vibration.
  • Page 71: General Drain Piping Information

    APPLICATION GUIDELINES General Drain Piping Information Figure 60: Diagram of an Indoor Unit with a Gravity Drain. General Drain Piping Information All Gallery and Wall-mounted indoor units generate water during cooling operation, therefore, properly handling this condensation Drain hose must be considered. Gallery and Wall-mounted indoor units apply Insulation the gravity drain method, but a field-supplied condensate pump can be installed (optional, sold separately).
  • Page 72 APPLICATION GUIDELINES General Drain Piping Information Common Indoor Unit Drainage System It is usual work practice to connect individual indoor unit drain pipes to one common indoor unit drainage system. The diameter of the com- mon vertical drain pipe should be as large as necessary. The diameter of the horizontal pipe should be the same or larger than the vertical drain pipe.
  • Page 73: Wiring Guidelines

    APPLICATION GUIDELINES General Power Wiring / Communications Cable Guidelines • Follow manufacturer’s circuit diagrams displayed on the inside of the control box cover. • Have a separate power supply for the indoor units. • Provide a circuit breaker switch between the power source and the indoor unit. •...
  • Page 74 APPLICATION GUIDELINES Power Wiring and Communications Cable Connections 1. Insert the power wiring / communications cable from the outdoor unit or heat recovery unit (Heat Recovery systems only) through the access hole of the indoor unit (ground wire should be longer than the other wires / cables) and to the control board using the designated path.
  • Page 75: Wired Remote Controller Location

    APPLICATION GUIDELINES Figure 69: Outdoor Unit Terminal Block Indoor Unit Terminal Block To Outdoor Unit SODU INTERNET DRY1 DRY2 L(L1) N(L2) 3(A) 4(B) Ground Power Input 208-230V / 60 Hz / 1 Phase Figure 68: Proper Location for the Wired Controller. Wired Controller Placement Gallery and Wall-mounted indoor units can be used with various wired controllers (optional;...
  • Page 76: Acronyms

    Aq inches water Air Handling Unit International Standards Organization ASHRAE American Society of Heating, Refrigeration, and Air Conditioning LATS LG Air Conditioning Technical Solution software ASTM American Society for Testing and Materials Light Emitting Diode American Wire Gauge LEED...
  • Page 77 LG Electronics Commercial Products Support 1-888-865-3026 USA Follow the prompts for commercial A/C products. LG Electronics, U.S.A., Inc. EM_MultiV_WallMounted_IndoorUnits_3_16 Commercial Air Conditioning Division Supersedes: EM_MultiV_WallMounted_IndoorUnits_1_16 4300 North Point Parkway EM_MultiV_WallMounted_IndoorUnits_05_15 Alpharetta, Georgia 30022 EM-MultiV-WallMounted-IndoorUnits-04-15 www.lg-vrf.com...