Panasonic CU-J50DBE8 Service Manual
Hide thumbs Also See for CU-J50DBE8:
Table of Contents

Advertisement

TABLE OF CONTENTS

1 Service Information---------------------------------------------- 3
1.2. Caution of test operation--------------------------------- 3
1.4. Operation range-------------------------------------------- 4
2 Features ------------------------------------------------------------- 5
2.1. Ceiling Type------------------------------------------------- 5
2.2. Outdoor Unit ----------------------------------------------- 5
2.3. Wired Remote Control------------------------------------ 7
2.4. Wireless Remote Control -------------------------------- 7
2.5. Group Control Equipment ------------------------------- 8
3 Product Specification ------------------------------------------- 9
3.1. CS-F24DTE5 CU-J24DBE5 ---------------------------- 9
3.2. CS-F24DTE5 CU-J24DBE8 ---------------------------10
CS-F24DTE5 CU-J24DBE5
CS-F24DTE5 CU-J24DBE8
CS-F28DTE5 CU-J28DBE5
CS-F28DTE5 CU-J28DBE8
CS-F34DTE5 CU-J34DBE5
CS-F34DTE5 CU-J34DBE8
CS-F43DTE5 CU-J43DBE8
CS-F50DTE5 CU-J50DBE8
PAGE
3.3. CS-F28DTE5 CU-J28DBE5 --------------------------- 11
3.4. CS-F28DTE5 CU-J28DBE8 --------------------------- 12
3.5. CS-F34DTE5 CU-J34DBE5 --------------------------- 13
3.6. CS-F34DTE5 CU-J34DBE8 --------------------------- 14
3.7. CS-F43DTE5 CU-J43DBE8 --------------------------- 15
3.8. CS-F50DTE5 CU-J50DBE8 --------------------------- 16
3.9. Safety Devices-------------------------------------------- 17
4 Dimensions ------------------------------------------------------- 18
4.1. CS-F24DTE5 CS-F28DTE5 --------------------------- 18
CU-J28DBE8---------------------------------------------- 20
CU-J50DBE8---------------------------------------------- 21
© 2005 Panasonic HA Air-Conditioning (M) Sdn Bhd
(11969-T). All rights reserved. Unauthorized copying
and distribution is a violation of law.
Order No. MAC0509064C2
Air Conditioner
CU-J28DBE5
CU-J43DBE8
PAGE

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic CU-J50DBE8

  • Page 1: Table Of Contents

    3 Product Specification ------------------------------------------- 9 CU-J28DBE8---------------------------------------------- 20 3.1. CS-F24DTE5 CU-J24DBE5 ---------------------------- 9 4.4. CU-J34DBE5 CU-J34DBE8 CU-J43DBE8 3.2. CS-F24DTE5 CU-J24DBE8 ---------------------------10 CU-J50DBE8---------------------------------------------- 21 © 2005 Panasonic HA Air-Conditioning (M) Sdn Bhd (11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law.
  • Page 2 6.3. CU-J34DBE5 ---------------------------------------------- 25 14.2. CS-F24DTE5 CS-F28DTE5 ------------------------- 128 6.4. CU-J24DBE8 CU-J28DBE8 --------------------------- 25 14.3. CS-F24DTE5 CS-F28DTE5 ------------------------- 129 6.5. CU-J34DBE8 CU-J43DBE8 CU-J50DBE8 ------ 25 15 Replacement Part List (Indoor Unit)--------------------- 130 7 Wiring Diagram -------------------------------------------------- 26 15.1. CS-F24DTE5 CS-F28DTE5 ------------------------- 130 7.1.
  • Page 3: Service Information

    1 Service Information Notice of Address setting for NEW Ceiling / NEW Outdoor Unit. The new Ceiling / New Outdoor models are possible to have address setting for twin control by automatic when main power supply is switched on. (Manual address setting is also possible by using Dip switch on Indoor unit P.C. board.) However, this address setting is only possible when made proper wiring connection and also Indoor unit should be original virgin unit.
  • Page 4: Operation Range

    J28DBE8 3N~380 J34DBE8 3N~400 J43DBE8 3N~415 J50DBE8 1.4.2. Indoor and Outdoor Temperature • Model 50Hz CU-J24DBE5 CU-J28DBE5 CU-J34DBE5 CU-J34DBE8 CU-J28DBE8 CU-J34DBE8 CU-J43DBE8 CU-J50DBE8 Operating Indoor Temp. (D.B./W.B.) (°C) Outdoor Temp. (D.B./W.B.) (°C) Cooling 32/23 21/15 43/- -10/-* * -10°C is possible in non-residential computer rooms, etc., where the temperature is not less than 21°C and humidity is not more...
  • Page 5: Features

    2 Features 2.1. Ceiling Type 2.1.1. Easier Maintenance and Cleaning • Anti-Mould Long Life Air Filter. • 3-Direction Pipe Lead-Out. 2.1.2. Wide Air Discharge, Comfortable Control • Wide-Angle Airflow — 100 Degrees Horizontal. • Auto Swing Louver. 2.2. Outdoor Unit 2.2.1.
  • Page 6 • Long Pipe design with maximum piping length of 50m. • Flexible 4-way piping. • Centralized Drain Method gathered multiple outdoor unit’s drain pipes into a single drain pipe to makes installation easier and also improve appearance. • Side-by-Side Continuous Installation is possible even outdoor units with different capacities. 2.2.2.
  • Page 7: Wired Remote Control

    2.3. Wired Remote Control 1. The new design includes an easily-visible red pilot lamp. The power can be turned on and off at a single touch, without opening the cover. 2. Has a build-in thermistor, allowing indoor temperature detection in accordance with indoor conditions by switching with main unit thermistor.
  • Page 8: Group Control Equipment

    2.5. Group Control Equipment Group control by one remote control [Remote side] • All air conditioner units are • Optional wired remote controlled as a whole by remote control CZ-RD513C control. • All indoor units operate in the same [Local side] mode.
  • Page 9: Product Specification

    ELECTRICAL DATA (50 Hz) ITEM / MODEL Condition by ISO5151 Volts Phase Single Single Single Power Consumption Cooling 2.58 2.63 2.68 Running Current Cooling 13.2 13.3 13.5 Starting Current Power Factor Cooling Panasonic Power source AC, 1~220V, 230V, 240V 50Hz...
  • Page 10: Cs-F24Dte5 Cu-J24Dbe8

    ELECTRICAL DATA (50 Hz) ITEM / MODEL Condition by ISO5151 Volts Phase Three Three Three Power Consumption Cooling 2.58 2.63 2.68 Running Current Cooling 4.55 4.60 4.65 Starting Current Power Factor Cooling Panasonic Power source AC, 3~380V, 400V, 415V 50Hz...
  • Page 11: Cs-F28Dte5 Cu-J28Dbe5

    Phase Single Single Single Power Consumption Cooling 2.85 Running Current Cooling 12.9 13.1 Starting Current Power Factor Cooling *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 1~220V, 230V, 240V 50Hz...
  • Page 12: Cs-F28Dte5 Cu-J28Dbe8

    35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.) ELECTRICAL DATA (50 Hz) ITEM / MODEL Condition by ISO5151 Volts Phase Three Three Three Power Consumption Cooling 2.85 Running Current Cooling 4.95 Starting Current Power Factor Cooling Panasonic Power source AC, 3~380V, 400V, 415V 50Hz...
  • Page 13: Cs-F34Dte5 Cu-J34Dbe5

    Single Power Consumption Cooling 3.97 4.02 4.07 Running Current Cooling 18.3 18.5 18.7 Starting Current Power Factor Cooling *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 1~220V, 230V, 240V 50Hz...
  • Page 14: Cs-F34Dte5 Cu-J34Dbe8

    Phase Three Three Three Power Consumption Cooling 3.84 3.89 3.94 Running Current Cooling Starting Current Power Factor Cooling *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3~380V, 400V, 415V 50Hz...
  • Page 15: Cs-F43Dte5 Cu-J43Dbe8

    Phase Three Three Three Power Consumption Cooling 4.84 4.89 4.94 Running Current Cooling Starting Current Power Factor Cooling *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 3~380V, 400V, 415V 50Hz...
  • Page 16: Cs-F50Dte5 Cu-J50Dbe8

    3.8. CS-F50DTE5 CU-J50DBE8 ITEM / MODEL Indoor Unit Outdoor Unit Main Body CS-F50DTE5 CU-J50DBE8 Remote CZ-RD513C (Wired) Control CZ-RL513T (Wireless) Cooling Capacity 13.5 BTU/h 46,000 Refrigerant Charge-less Standard Air Volume for High Speed /min 1130 3387 Outside Dimension (H x W x D)
  • Page 17: Safety Devices

    3.9. Safety Devices INDOOR UNIT Indoor Unit Heat Pump Model CS-F24DTE5 CS-F28DTE5 CS-F34DTE5 CS-F43DTE5 CS-F50DTE5 Cooling only Model For fan motor protection °C Internal °C protector (49F) For control protection Fuse 3.15 3.15 3.15 3.15 3.15 OUTDOOR UNIT Cooling Outdoor Unit only 50Hz J24DBE5...
  • Page 18: Dimensions

    4 Dimensions 4.1. CS-F24DTE5 CS-F28DTE5...
  • Page 19: Cs-F34Dte5 Cs-F43Dte5 Cs-F50Dte5

    4.2. CS-F34DTE5 CS-F43DTE5 CS-F50DTE5...
  • Page 20: Cu-J24Dbe5 Cu-J24Dbe8 Cu-J28Dbe5 Cu-J28Dbe8

    4.3. CU-J24DBE5 CU-J24DBE8 CU-J28DBE5 CU-J28DBE8...
  • Page 21: Cu-J34Dbe5 Cu-J34Dbe8 Cu-J43Dbe8 Cu-J50Dbe8

    4.4. CU-J34DBE5 CU-J34DBE8 CU-J43DBE8 CU-J50DBE8...
  • Page 22: Refrigeration Cycle

    5 Refrigeration Cycle 5.1. CS-F24DTE5 CU-J24DBE5/CU-J24DBE8, CS-F28DTE5 CU-J28DBE5/CU-J28DBE8...
  • Page 23: Cs-F34Dte5 Cu-J34Dbe5/Cu-J34Dbe8, Cs-F43Dte5 Cu-J43Dbe8, Cs-F50Dte5 Cu-J50Dbe8

    5.2. CS-F34DTE5 CU-J34DBE5/CU-J34DBE8, CS-F43DTE5 CU-J43DBE8, CS- F50DTE5 CU-J50DBE8...
  • Page 24: Block Diagram

    6 Block Diagram 6.1. CS-F24DTE5 CS-F28DTE5 CS-F34DTE5 CS-F43DTE5 CS-F50DTE5 6.2. CU-J24DBE5 CU-J28DBE5...
  • Page 25: Cu-J34Dbe5

    6.3. CU-J34DBE5 6.4. CU-J24DBE8 CU-J28DBE8 6.5. CU-J34DBE8 CU-J43DBE8 CU-J50DBE8...
  • Page 26: Wiring Diagram

    7 Wiring Diagram 7.1. CS-F24DTE5 CS-F28DTE5 CS-F34DTE5 CS-F43DTE5 CS-F50DTE5...
  • Page 27: Cu-J24Dbe5 Cu-J28Dbe5

    7.2. CU-J24DBE5 CU-J28DBE5...
  • Page 28: Cu-J34Dbe5

    7.3. CU-J34DBE5...
  • Page 29: Cu-J24Dbe8 Cu-J28Dbe8

    7.4. CU-J24DBE8 CU-J28DBE8...
  • Page 30: Cu-J34Dbe8 Cu-J43Dbe8 Cu-J50Dbe8

    7.5. CU-J34DBE8 CU-J43DBE8 CU-J50DBE8...
  • Page 31: Operation Instructions

    8 Operation Instructions 8.1. Wired Remote Control (Optional part) Name and function of each part Airflow direction setting display OFF/ON button Used to start and stop the operation. FAN SPEED button Used to select the fan speed of high (HI), medium (MED), low (LO) or auto (AUTO).
  • Page 32: Remote Control - Display

    8.2. Remote Control - Display...
  • Page 33: Remote Control - Panel

    8.3. Remote Control - Panel...
  • Page 34: How To Set Remote Control Day And Time

    8.4. How to set remote control day and time • The day and time needs to be set when you turn on the power for the first time or after a long time has elapsed since the power was last turned on. •...
  • Page 35: Daily Timer Setting

    CLOCK Display (To set current Day and Time) Note: • The above display is shown if no valid timer setting is made. • If valid timer setting is made. and setting will be displayed. - If you want to check the current time and day, press “MODE button” once. (However, after a few seconds, the display will change back to and the setting) 8.6.
  • Page 36: Weekly Timer Setting

    Final Display of Daily Timer: 8.7. Weekly Timer Setting • Display • How to Set Weekly Timer - You can set the Timer for 1 week (Monday to Sunday) with 6 programs per day. - ON-Timer can be set together with your desired temperature. However, this temperature will be used continuously. - Cannot set 2 programs with same time setting in a day.
  • Page 37 For example, if you want to set: A - Monday to Friday: Same time, 1st program ON 9:00 & 2nd program OFF 16:00. B - Only Wednesday: Additional 3rd program OFF 12:30 & 4th program ON 13:30. C - Only Saturday: 1st program ON 10:00 with 20°C & 2nd program OFF 14:00. D - Sunday: Holiday.
  • Page 38: Wireless Remote Control (Optional Part)

    8.8. Wireless Remote Control (Optional part) Name and function of each part Time/time setting display Shows the timer operation setting time or the current time. Address number display Operation selection display OFF/ON button Used to start and stop the operation. ODOUR WASH button FILTER RESET button Press to cancel the “FILTER”...
  • Page 39: Operation Details

    9 Operation Details 9.1. Cooling Operation • Cooling operation can be set using remote control. • This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control. • Cooling Operation Time Diagram. 9.2.
  • Page 40: Fan Operation

    9.4. Fan Operation • Fan operation can be set using remote control. • The indoor fan is operated at High, Medium or Low speed according to remote control setting. 9.5. Normal Control 9.5.1. Cooling Indoor Fan Control • Manual Fan Speed Operation starts at High, Medium or Low speed set by remote control.
  • Page 41: Operation Control

    9.6. Operation Control 9.6.1. Odour Cut Control • Odour cut operation removes the odour generated at indoor heat exchanger by using drain water come out from indoor heat exchanger. • Press “Odour” button at remote control to enable odour cut operation. •...
  • Page 42 9.6.7. Pump-down Control • To enable pump down operation, at outdoor PCB, set the DS1and DS2 to OFF position. • Press Test Run button for 1 second. • During Pump Down operation, push the Test Run button again for 1 second to stop the pump down operation. •...
  • Page 43: Protection Control

    Min. Capacity (kW) Max. Capacity (kW) Model Number Min. Capacity (kW) Max. Capacity (kW) CU-J14DBE5 CU-J28DBE8 CU-J18DBE5 CU-J34DBE8 12.3 CU-J24DBE5 CU-J43DBE8 10.2 13.8 CU-J28DBE5 CU-J50DBE8 12.7 15.8 CU-J34DBE5 12.3 • During this protection control, connection capacity error is displayed; all operations stopped.
  • Page 44: Test Run

    9.7.7. Sensor Disconnection Detection Control • The sensor disconnection detection control activates when the following condition comply: Sensor Detection Threshold Duration (Sec.) Detection Condition Discharge Temperature < -4.5°C or 201.8°C Other than compressor start control and compressor ON Outdoor Heat Exchanger <...
  • Page 45: Installation Instruction

    Add refrigerant = (main pipe + (branch pipe La + branch pipe Lb)/2.78-30) * 50...formula 2 • Calculation 2 In case of CU-J43DBE8, CU-J50DBE8 When pipe length exceed 30m calculated by formula 3, adding refrigerant amount should be calculated by formula 4. If calculation result is less than 30m, it is not necessary to add refrigerant.
  • Page 46: Refrigerant Additional Charge

    In case of 50m long pipe (one way), the amount of refrigerant to be replenished is: (50 - 30) x 50 = 1,000g Model Name Standard piping specification Liquid piping Gas piping Gas chargeless Additional gas (dia.mm) (dia.mm) length (m) volume (g/m) CU-J24DBE5 9.52 15.88 CU-J24DBE8 CU-J28DBE5 9.52 15.88 CU-J28DBE8 CU-J34DBE5 9.52 15.88 CU-J34DBE8 CU-J43DBE8 9.52 15.88 CU-J50DBE8 9.52 15.88...
  • Page 47: Position Of The Centre Gravity

    10.3. Position of the centre gravity MODEL NAME OUTSIDE DIMENSIONS NET WEIGHT CENTRE OF GRAVITY WIDTH (mm) DEPTH (mm) HEIGHT (mm) X (mm) Y (mm) Z (mm) CU-J24DBE5 CU-J24DBE8 CU-J28DBE5 CU-J28DBE8 CU-J34DBE5 1170 CU-J34DBE8 CU-J43DBE8 1170 CU-J50DBE8 1170...
  • Page 48: Indoor Unit Installation

    10.4. Indoor unit installation CEILING TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS Precautions in terms of safety Carry out installation work with reliability after throughout reading of this “Precautions in terms of safety”. • Precautions shown here are differentiated between Warnings and Cautions.
  • Page 49 Warnings The unit must be installed in accordance with applicable national When performing piping work do not mix air except for specified and local regulations.Any electrical work should only be carried refrigerant (R410A) in refrigeration cycle. it causes capacity down, out by qualified technician and use exclusive circuits without fail.
  • Page 50: Installation Of Indoor Unit

    10. Do not install the indoor unit at a laundry. Electric shocks may result. NOTE • Study throughly the following installation locations. 1. In places such as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, and the fin of the heat exchanger may result in heat exchange reduction, spraying or dispersing of water drops, etc.
  • Page 51 REMOVING THE SIDE COVER AND HANGING BRACKET 1. Open the inlet grille, and remove the side cover fixing screw (right and left) from the internal part of the unit. 2. Move the side cover to about 15mm forward to remove it. Use the packing material (Styrene foam) to support, when you reverse the top and bottom of the indoor unit.
  • Page 52: Refrigerant Piping

    Installing the unit 1. Insert the hanging bracket fastening bolts and both sides of the unit into the hanging brackets, and slide the unit to the rear. Fasten the bolts. 2. Tighten the slip prevention screws (M5) for brackets to prevent the unit from shifting. 3.
  • Page 53: Indoor Unit Drain Piping

    10.4.5. Indoor unit drain piping • Be sure to use the drain hose provided (accessory item.) • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port at the indoor unit.
  • Page 54 2. Precautions in high humidity circumstance. This air conditioner has been tested according to the “JIS Standard Conditions with Mist” and have been confirmed that there is no form of any faults. However, if it is operated for a long time in high humid atmosphere (dew point temperature: more than 23°C), water drops are liable to fall.
  • Page 55 CONNECTING THE WIRES TO THE CONTROL BOX Caution Make sure that screws of the terminal are securely tight- ened. • Remove a two mounting screw, remove the control box cover, and then connect the wires by following the procedure given in the illustration. 10.4.8.
  • Page 56 (Remote Control Address Setting) (Refer to the Operation Manual which is provided with the remote controller for details.) • Two remote controllers (including the wireless remote controller) can be connected. However, remote control thermistor setting is not possible. • As for [master/slave] setting of remote controller, the automatic setting and manual setting are possible. Since manual setting is priority.
  • Page 57: Hand Over

    10.4.11. Check the following items when installation is complete • After completing work, be sure to measure and record trial run properties, and store measuring data, etc. • Measuring items are room temperature, outside temperature, suction temperature, blow out temperature, wind velocity, wind volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping temperature, compressive pressure, airtight pressure.
  • Page 58: Outdoor Unit Installation

    10.5. Outdoor unit installation AIR CONDITIONERS OUTDOOR UNIT INSTALLATION INSTRUCTIONS Precautions in terms of safety Carry out installation work with reliability after thorough reading of this “Precautions in terms of safety”. • Precautions shown here are differentiated between Warnings and Cautions.
  • Page 59 Warnings The unit must be installed in accordance with applicable national Once installation work is completed, check that there are no and local regulations. refrigerant gas in the room that can come into contact with sparks Any electrical work should only be carried out by qualified or flames from a fan heater, stove or kitchen range, which will technician and use exclusive circuits without fail.
  • Page 60 b. Prevention measure for refrigerant piping Prevention measure for refrigerant piping is very important work to prevent water-dust-rubbish from getting in. All piping terminals needs sealing such as shown below. Place Period of work Method of seal Outside More than 1 month Pinch Less than 1 month Pinch or taping...
  • Page 61 For the use of a gas cylinder without siphon inside, turn it upside down and use it. (We recommend manifold with sight glass.) Do not use a “CHARGE CYLINDER”. Caution As a rule, please collect all existing refrigerants in the system outside the system when the refrigerant leakage occurs by the Caution system.
  • Page 62 12. Be sure to leave enough space around the outdoor unit to maintain proper performance and to allow access for routine maintenance. • Allow enough space from any obstacles as shown in Fig. 1.2 below in order to prevent short-circuits from occurring. (If installing more than one outdoor unit, make the necessary space available as outlined in 13.) However, there should be at least 1 meter of free space above the unit.
  • Page 63 • If a drain pipe needs to be installed, insert the accessory drain elbow into the mounting hole at the bottom of the outdoor unit, and connect a hose with an inside diameter of 15mm to this drain elbow. (The hose is not supplied.) If using the drain elbow, install the outdoor unit on a base which is at least 5cm high.
  • Page 64: Charging With Refrigerant

    3. Notes when connecting the refrigerant pipes. • Use clean copper, pipes with no water or dust on the insides. • Use phosphorus-free, unjointed copper pipes for the refrigerant pipes. • If it is necessary to cut the refrigerant pipes, be sure to use a pipe cutter, and use compressed nitrogen or an air blower to clean out any foreign particles from inside the pipe.
  • Page 65 • Pump down operation - Operate the pump down according to the following procedures. Procedure Notes 1. Confirm the valve on the liquid side and the gas side is surely open. 2. Press the PUMP DOWN switch on outdoor printed board for 1 second Perform the cooling operation for five minutes or more.
  • Page 66 CU-B43DBE8 CU-J43DBE8 380V-415V 3N~ 0.0374 CU-B50DBE8 CU-J50DBE8 380V-415V 3N~ 0.1017 NOTE 1. Where ground work (earth) is carried out, do not connect the ground return to the gas pipe, water line pipe, grounded circuit of the telephone and lightning rod, or ground circuit of other product in which earth leakage breaker is incorporated. (Such action is prohibited by statute, etc.)
  • Page 67 10.5.10. Connecting power supply cables CAUTION • For three phase model, never operate the unit by pressing the electromagnetic switch. • Never correct the phase by switching over any of the wires inside the unit. 10.5.11. Precautions with regard to test operation •...
  • Page 68 NOTE 2 Do not short the remote control unit wires to each other. (The protection circuit will be activated and the units will not operate.) Once the cause of the short is eliminated, normal operation will then be possible. NOTE 3 When running the units in heating mode during test operation, be sure to run the units in cooling mode first before selecting this mode.
  • Page 69: Wired Remote Control Installation

    10.6. Wired remote control installation Wired Remote Control Installation Manual • Before installing the wired remote controller, be sure to thoroughly read the “Notes with regard to safety” section of the installation manual provided with the indoor unit. • After installing the wired remote controller, carry out a test operation to check that the remote controller functions properly, and also explain the operation and cleaning procedures to the customer in accordance with the details in instruction manual.
  • Page 70 Remote controller wiring • Connect the indoor unit and the remote controller as shown in the illustration below. • The remote control cable is non-polar. • At the time of shipment from the factory, the connector cable used to connect the terminal block and connector CN1 is disconnected.
  • Page 71 • Strip the end of the remote control cable which is to be connected to the remote controller. (Refer to the illustration below) • Route the remote control cable inside the lower case in accordance with the intended feeding- out direction. (Refer to the illustration below.) Securely connect connector CN1.
  • Page 72 If remote control cable is embedded If installing with the remote control cable exposed 1. Embed an outlet box (JIS C 8336) into the wall, and then secure 1. Secure the remote controller base plate to the wall with two the remote controller base plate to the outlet box with the two accessory 4 mm screws.
  • Page 73 Automatic address resetting for group control • The address settings for group control (air conditioner Nos. 1 to 16) can be reset automatically. 1. When operation is stopped, press for 5 seconds, continue the TEST RUN switch to display “00” (will be LOCAL MODE). 2.
  • Page 74: Test Operation

    10.6.5. Test operation • Turn on the main power. • After 3 minutes have passed since the power was turned on, press the OFF/ON switch on the remote controller. (No operation occurs within 3 minutes after the power was turned on.) •...
  • Page 75 If “CHECK” is not blinking on the timer • If the “CHECK” display on the wired remote controller is not blinking, press the CHECK switch continuously for 5 seconds or more to display the problem details for the last problem or the problem before that. •...
  • Page 76: Wireless Remote Control Installation Manual

    10.7. Wireless remote control installation manual Wireless Remote Control Installation Manual • Before installing the wireless remote controller, be sure to thoroughly read the “Notes with regard to safety” section of the installation manual provided with the indoor unit. • After installing the wireless remote controller, carry out a test operation to check that the remote controller functions properly, and also explain the operation and cleaning procedures to the customer in accordance with the details in the instruction manual.
  • Page 77 Attach the receptor unit onto the decorative panel of the indoor unit as shown in the figure below. 1. Remove the “corner cover” at the decorative panel indicate “Panasonic” logo left side. 2. Attach the receptor unit which same position.
  • Page 78 1. Route the joint cord for wiring as shown in the figure (figure of the back of decorative panel) below. Pass the cord through the hook of the decorative panel, taking care that the cord does not run on the heat insulator, etc. 2.
  • Page 79 Receptor unit (for ceiling type) assembly procedure Attach the receptor unit onto the indoor main unit as shown in the figure below. Remove the air-intake grille and the side cover. To remove the side cover, remove the fixing screw each on the left and the right and pull the side cover towards you. (Refer to the installation Manual supplied with the indoor main unit.) Remove the Decorative grille (component on which the brand name is shown) to the right on the air-blow opening.
  • Page 80 10.7.4. Address setting for wireless remote controller and receptor unit (only when using more than one indoor unit) • Only the air conditioner units which receptor unit address numbers match the remote controller address number can be operated. • At the time of shipment from the factory, the address numbers for both the wireless remote controller and the receptor unit are set to “1”.
  • Page 81 NOTE • If the batteries are replaced or the remote controller is reset, the address setting will return to ADDRESS1, so you will need to repeat the address setting again. All setting details which are stored in memory will be cleared, so you will need to repeat the setting. •...
  • Page 82: Emergency Operation

    [Manual setting] 10.7.5. Emergency operation • If you do not have the wireless remote controller (because the batteries are weak, or some other reason prevents the wireless remote controller from being used), emergency operation can be carried out at receptor unit. •...
  • Page 83: Twin Operation

    10.8. Twin Operation • Simultaneous air conditioning of wide spaces and corners is possible. Indoor units with same horsepowers can be used in combination. • Master unit and slave-unit can be set automatically in twin systems. No address setting is necessary. •...
  • Page 84: Installation And Servicing Air Conditioner Using R410A

    11 Installation and Servicing Air Conditioner Using R410A 11.1. Outline 11.1.1. About R410A refrigerant 1. Converting air conditioners to R410A Since it was declared in1974 that chlorofluorocarbons (CFC), hydro chlorofluorocarbons (HCFC) and other substances pose a destructive danger to the ozone layer in the earth’s upper stratosphere (20 to 40 km above the earth), measures have been taken around the world to prevent this destruction.
  • Page 85: Tools For Installing/Servicing Refrigerant Piping

    d. R410A refrigerating machine oil Conventionally, mineral oil or a synthetic oil such as alkylbenzene has been used for R22 refrigerating machine oil. Because of the poor compatibility between R410A and conventional oils like mineral oil, however, there is a tendency for the refrigerating machine oil to collect in the refrigerating cycle.
  • Page 86: R410A Tools

    11.2.2. R410A tools 1. Copper tube gauge for clearance adjustment (used when flaring with the conventional flaring tool (clutch type)) • This gauge makes it easy to set the clearance for the copper tube to 1.0-1.5 mm from the clamp bar of the flaring tool.
  • Page 87 5. Charging hose • The pressure resistance of the charging hose has been raised to match the higher pressure of R410A. The hose material has also been changed to suit HFC use, and the size of the fitting has been changed to match the manifold ports.
  • Page 88 8. Electronic scale for refrigerant charging • Because of the high pressure and fast vaporizing speed of R410A, the refrigerant cannot be held in a liquid phase inside the charging cylinder when charging is done using the charging cylinder method, causing bubbles to form in the measurement scale glass and making it difficult to see the reading.
  • Page 89: Refrigerant Piping Work

    11.3. Refrigerant piping work 11.3.1. Piping materials It is recommended that you use copper and copper alloy jointless pipes with a maximum oil adherence of 40 mg/10m. Do not use pipes that are crushed, deformed, or discolored (especially the inside surface). If these inferior pipes are used, impurities may clog the expansion valves or capillaries.
  • Page 90 Table 11 R410A flaring dimensions Nominal Outside Wall thickness A (mm) diameter diameter (mm) R410A flaring Conventional flaring tool (mm) tool, clutch type Clutch type Wing-nut type 6.35 0 - 0.5 1.0 - 1.5 1.5 - 2.0 9.52 0 - 0.5 1.0 - 1.5 1.5 - 2.0 12.70...
  • Page 91: Installation, Transferring, Servicing

    b. Copper pipes Use only copper pipes with the thickness given in table 10, and with minimal impurities. Because the surface of the pipe is exposed, you should take special care, and also take measures such as marking the pipes to make sure they are easily distinguished from other piping materials, to prevent mistaken use.
  • Page 92 11.4.2. Transferring (Using new refrigerant piping) 1. Removing the unit a. Collecting the refrigerant into the outdoor unit by pumping down The refrigerant can be collected into the outdoor unit (pumping down) by pressing the TEST RUN button, even when the temperature of the room is low.
  • Page 93 Precaution: Be sure to set up the cylinder for liquid charging. If you use a cylinder equipped with a siphon tube, you can charge the liquid without having to turn the cylinder around 6. Remove the charging hose of the manifold gauge from the vacuum pump adaptor, and connect it to the connection port of the electronic scale.
  • Page 94 11.4.6. Brazing As brazing requires sophisticated techniques and experiences, it must be performed by a qualified person. In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry nitrogen gas (N ) flow.
  • Page 95: Troubleshooting Guide

    12 Troubleshooting Guide If test operation does not proceed correctly Carry out test operation after approximately 12 hours have passed since the power was turned on (crankcase heater is energized). If operation is started by using the remote control within 1 minute of turning on the power, the outdoor unit settings will not be made cor- rectly and correct operation will not be possible.
  • Page 96 (When remote control display shows “power supply”) Clock setting, and no timer setting (When remote control display shows “No power supply”)
  • Page 97: During Twin Operation

    12.2. During twin operation System example 1. The main power is turned on while the transmission wires between the indoor units are not connected. (open circuit at A or B) Symptom Remote control unit: “check” flashes Error code: F30-01 (connected indoor capacity error) Indoor unit No.
  • Page 98: During Group Control Operation

    4. The main power is turned on and the connection wire is all ok. If operation starts in this condition, combination of the B50DBE8 outdoor unit and F24DTE5 indoor unit will result in abnormal operation. Symptom Remote control unit: “check” flashes Error code: F30-01 (connected indoor capacity error) Indoor unit: LED1 on P.C.B flashes Outdoor unit: LED6, 7 on P.C.B flashes (connected indoor capacity error)
  • Page 99: Test Operation And Self-Diagnosis

    Remedy 1. Turn off the main power. ↓ 2. Connect the disconnected wire correctly. ↓ 3. Turn on the main power. ↓ 4. After 1 minute, start the operation using the remote control. (Indoor unit operation will start according to the remote control setting.) (Outdoor unit operation will start after 3-5 minutes.) 12.4.
  • Page 100 12.4.3. Test operation using the wired remote control 1. Check that “COOL” is displayed on the LCD, and then press the OFF/ON button to start test operation. 2. After pressing the OFF/ON button, press the TEST RUN button within 1 minute. 3.
  • Page 101 12.4.4. Self-diagnosis function The wired remote control display and the self-diagnosis LEDs (green) on the outdoor unit printed circuit board indicate where the abnormality has occurred. Recalling the error display. The air conditioner No.”01” appears during normal installation and use. When using group control, a different number may appear.
  • Page 102 • How to display the past error message. If the CHECK display on the wired remote control is not flashing, press the CHECK button continuously for 5 seconds or more to display the past problem details. 12.4.5. Test operation using the receiver auto button (If using wireless remote controller)
  • Page 103: Emergency Operation

    12.5. Emergency operation When using the wireless remote control and losing the remote controller, emergency operation can be operated by pressing auto button in the receiver. • Press the auto button continuously within 5 seconds If there is an abnormality in the temperature thermistor (disconnect or shorted), indoor unit cannot be operated. If abnormality detected in the indoor or outdoor unit, turn off the main power supply and find the cause.
  • Page 104 Resistance value (kΩ)±5% During outdoor unit emergency operation or test operation, the LED on the P.C.B. will flash.
  • Page 105: Self-Diagnosis Error Code Table

    12.6. Self-diagnosis error code table • The display screen on the wired remote control unit and the self-diagnosis LEDs (green) on the outdoor unit printed circuit board in the outdoor unit can be used to indicate where the location of a problem is. Refer to the table below to remove the cause of the problem, and then re-start the air conditioner system.
  • Page 106: Technical Data

    13 Technical Data 13.1. Cooling capacity performance data Ambient Temperature Air Entering Condenser (°C D.B.) Model Power Return 25°C 30°C 35°C 40°C 43°C (CS-) Source D.B. W.B. F24DTE5 230V, 6.87 4.50 2.09 6.60 4.46 2.27 6.21 4.32 2.47 5.74 4.13 2.71 5.41 4.00...
  • Page 107 Ambient Temperature Air Entering Condenser (°C D.B.) Model Power Return 25°C 30°C 35°C 40°C 43°C (CS-) Source D.B. W.B. F34DTE5 230V, 10.41 6.82 3.20 10.00 6.75 3.47 9.41 6.54 3.77 8.70 6.26 4.14 8.19 6.06 4.39 50Hz, 10.99 5.61 3.39 10.65 5.64 3.67 10.11 5.56 4.00 9.42...
  • Page 108 Ambient Temperature Air Entering Condenser (°C D.B.) Model Power Return 25°C 30°C 35°C 40°C 43°C (CS-) Source D.B. W.B. F43DTE5 400V, 13.01 8.52 3.89 12.50 8.44 4.22 11.76 8.17 4.59 10.88 7.83 5.04 10.24 7.58 5.34 50Hz, 13.74 7.01 4.13 13.31 7.06 4.47 12.63 6.95 4.87 11.78 6.71 5.34 11.18 6.60...
  • Page 109: Capacity And Power Consumption

    13.2. Capacity and power consumption 13.2.1. Cooling Performance Model Cooling capacities are based on conditions CS-F24DTE5 Single phase, 50Hz 230V, Three phase, 50Hz 400V Cooling capacity Indoor temp. 27°C D.B. 19°C W.B. 6.6kW Outdoor temp. 35°C D.B. Standard air volume 17 m /min Ambient Temperature Air Entering Condenser (°C D.B.)
  • Page 110 Model Cooling capacities are based on conditions CS-F28DTE5 Single phase, 50Hz 230V, Three phase, 50Hz 400V Cooling capacity Indoor temp. 27°C D.B. 19°C W.B. 7.3kW Outdoor temp. 35°C D.B. Standard air volume 18 m /min Ambient Temperature Air Entering Condenser (°C D.B.) Ambient Temperature Air Entering Condenser (°C D.B.) Return...
  • Page 111 Model Cooling capacities are based on conditions CS-F34DTE5 Single phase, 50Hz 230V Cooling capacity Indoor temp. 27°C D.B. 19°C W.B. 10.0kW Outdoor temp. 35°C D.B. Standard air volume 29 m /min Ambient Temperature Air Entering Condenser (°C D.B.) Ambient Temperature Air Entering Condenser (°C D.B.) Return 25°C 30°C...
  • Page 112 Model Cooling capacities are based on conditions CS-F34DTE5 3 phase, 50Hz 400V Cooling capacity Indoor temp. 27°C D.B. 19°C W.B. 10.0kW Outdoor temp. 35°C D.B. Standard air volume 29 m /min Ambient Temperature Air Entering Condenser (°C D.B.) Ambient Temperature Air Entering Condenser (°C D.B.) Return 25°C 30°C...
  • Page 113 Model Cooling capacities are based on conditions CS-F43DTE5 3 phase, 50Hz 400V Cooling capacity Indoor temp. 27°C D.B. 19°C W.B. 12.5kW Outdoor temp. 35°C D.B. Standard air volume 31 m /min Ambient Temperature Air Entering Condenser (°C D.B.) Ambient Temperature Air Entering Condenser (°C D.B.) Return 25°C 30°C...
  • Page 114 Model Cooling capacities are based on conditions CS-F50DTE5 3 phase, 50Hz 400V Cooling capacity Indoor temp. 27°C D.B. 19°C W.B. 13.5kW Outdoor temp. 35°C D.B. Standard air volume 32 m /min Ambient Temperature Air Entering Condenser (°C D.B.) Ambient Temperature Air Entering Condenser (°C D.B.) Return 25°C 30°C...
  • Page 115: Reaching Distance

    13.3. Reaching distance Cooling Mode CS-F24DTE5 CS-F28DTE5 CS-F34DTE5 CS-F43DTE5 CS-F50DTE5...
  • Page 116: Sound Data

    13.4. Sound data...
  • Page 121: Sound Measuring Point

    13.5. Sound measuring point 13.5.1. Indoor Unit 13.5.2. Outdoor Unit...
  • Page 122: Fan Performance

    13.6. Fan performance CS-F24DTE5 ITEM/MODEL Indoor Unit Outdoor Unit CS-F24DTE5 CU-J24DBE5/8 MODE Air Volume /min Running Current 0.40 0.35 0.28 0.55/0.56/0.57 Power Consumption 0.08 0.07 0.06 0.12/0.12/0.13 Fan Speed r/min 1145 630/655/680 CS-F28DTE5 ITEM/MODEL Indoor Unit Outdoor Unit CS-F28DTE5 CU-J28DBE5/8 MODE Air Volume /min...
  • Page 123 CS-F34DTE5 (220/230/240V) ITEM/MODEL Indoor Unit Outdoor Unit CS-F34DTE5 CU-J34DBE5/8 MODE Air Volume /min Running Current 0.620 0.520 0.440 1.03 Power Consumption 0.153 0.123 0.098 223.30 Fan Speed r/min 1125 1000 781/774 CS-F43DTE5 ITEM/MODEL Indoor Unit Outdoor Unit CS-F43DTE5 CU-J43DBE8 MODE Air Volume /min Running Current...
  • Page 124 CS-F50DTE5 ITEM/MODEL Indoor Unit Outdoor Unit CS-F50DTB5 CU-J50DBE8 MODE Air Volume /min Running Current 0.95 0.69 0.48 1.16 Power Consumption 0.19 0.16 0.12 266.00 Fan Speed r/min 1260 1175 1080 808/818...
  • Page 125: Discharge And Suction Pressure

    13.7. Discharge and suction pressure SATURATION TEMPERATURE OF DISCHARGE AND SUCTION PRESSURE COOLING...
  • Page 126: Operating Characteristics

    8.20 4.89 6.78 4.56 0.65 0.15 0.97 0.23 8.40 4.94 CS-F50DTE5 7.77 4.82 0.89 0.19 0.99 0.22 8.40 5.23 CU-J50DBE8 7.96 4.85 0.91 0.20 1.02 0.23 8.60 5.28 8.14 4.87 0.94 0.21 1.04 0.25 8.80 5.33 Legend: S.C.: Starting Current R.C.: Running Current...
  • Page 127: Exploded View (Indoor Unit)

    14 Exploded View (Indoor Unit) 14.1. CS-F24DTE5 CS-F28DTE5...
  • Page 128: Cs-F24Dte5 Cs-F28Dte5

    14.2. CS-F24DTE5 CS-F28DTE5...
  • Page 129: Cs-F24Dte5 Cs-F28Dte5

    14.3. CS-F24DTE5 CS-F28DTE5...
  • Page 130: Replacement Part List (Indoor Unit)

    15 Replacement Part List (Indoor Unit) 15.1. CS-F24DTE5 CS-F28DTE5 PART DESCRIPTION QTY. CS-F24DTE5 CS-F28DTE5 ← CABINET TOP PLATE CWE001015 ← CABINET FRONT PLATE CWG07K1009 ← CABINET SIDE PLATE (L) CWD63K1001 ← VANE SUPPORTER (L) CWG071146 ← CATCHER CWH601005 ← CABINET SIDE PLATE (R) CWD63K1002 ←...
  • Page 131 PART DESCRIPTION QTY. CS-F24DTE5 CS-F28DTE5 ← FLEXIBLE PIPE-ACCESSORY CWH82C1297 ← WIRED REMOTE CONTROL COMPLETE CWA75C2586 ← WIRELESS REMOTE CONTROL COMP. CWA75C2588 ← RAY RECEIVER CWD76C1030 ← BEARING CWH641004 ← WIRED REMOTE CONTROL CO. (ACCESSORY) CWG50C2604 ← OPERATING INSTRUCTION CWF564437 ← OPERATING INSTRUCTION CWF564438 ←...
  • Page 132: Exploded View (Indoor Unit)

    16 Exploded View (Indoor Unit) 16.1. CS-F34DTE5 CS-F43DTE5 CS-F50DTE5...
  • Page 133: Cs-F34Dte5 Cs-F43Dte5 Cs-F50Dte5

    16.2. CS-F34DTE5 CS-F43DTE5 CS-F50DTE5...
  • Page 134: Cs-F34Dte5 Cs-F43Dte5 Cs-F50Dte5

    16.3. CS-F34DTE5 CS-F43DTE5 CS-F50DTE5...
  • Page 135: Replacement Part List (Indoor Unit)

    17 Replacement Part List (Indoor Unit) 17.1. CS-F34DTE5 CS-F43DTE5 CS-F50DTE5 PART DESCRIPTION QTY. CS-F34DTE5 CS-F43DTE5 CS-F50DTE5 ← ← CABINET TOP PLATE CWE001016 ← ← CABINET FRONT PLATE CWG07K1008 ← ← CABINET SIDE PLATE (L) CWD63K1003 ← ← VANE SUPPORTER (L) CWG071144 ←...
  • Page 136 PART DESCRIPTION QTY. CS-F34DTE5 CS-F43DTE5 CS-F50DTE5 ← ← CABINET SIDE COVER (R) CWE041024 ← ← CABINET SIDE COVER (L) CWE041025 ← ← FLEXIBLE PIPE-ACCESSORY CWH82C1297 ← ← WIRED REMOTE CONTROL COMPLETE CWA75C2586 ← ← WIRELESS REMOTE CONTROL COMP. CWA75C2588 ← ←...
  • Page 137: Exploded View (Outdoor Unit)

    18 Exploded View (Outdoor Unit) 18.1. CU-J24DBE5 CU-J24DBE8 CU-J28DBE5 CU-J28DBE8...
  • Page 138: Cu-J24Dbe5 Cu-J24Dbe8 Cu-J28Dbe5 Cu-J28Dbe8

    18.2. CU-J24DBE5 CU-J24DBE8 CU-J28DBE5 CU-J28DBE8...
  • Page 139: Replacement Part List (Outdoor Unit)

    19 Replacement Part List (Outdoor Unit) 19.1. CU-J24DBE5 CU-J24DBE8 CU-J28DBE5 CU-J28DBE8 PART DESCRIPTION QTY. CU-J24DBE5 CU-J28DBE5 CU-J28DBE5 CU-J28DBE8 ← ← ← BASE PAN ASS’Y CWD52K1102 COMPRESSOR 5JS315DAM21 5JS315PAA21 5JS330DAF21 5JS330PBA21 ← ← ← ANTI-VIBRATION BUSHING CWH50055 ← ← ← NUT FOR COMP. MOUNT. CWH561049 ←...
  • Page 140: Exploded View (Outdoor Unit)

    20 Exploded View (Outdoor Unit) 20.1. CU-J34DBE5 CU-J34DBE8 CU-J43DBE8 CU-J50DBE8...
  • Page 141: Cu-J34Dbe5 Cu-J34Dbe8 Cu-J43Dbe8 Cu-J50Dbe8

    20.2. CU-J34DBE5 CU-J34DBE8 CU-J43DBE8 CU-J50DBE8...
  • Page 142: Cu-J34Dbe5 Cu-J34Dbe8 Cu-J43Dbe8 Cu-J50Dbe8

    20.3. CU-J34DBE5 CU-J34DBE8 CU-J43DBE8 CU-J50DBE8...
  • Page 143: Replacement Part List (Outdoor Unit)

    21 Replacement Part List (Outdoor Unit) 21.1. CU-J34DBE5 CU-J34DBE8 CU-J43DBE8 CU-J50DBE8 PART DESCRIPTION QTY. CU-J34DBE5 CU-J34DBE8 CU-J43DBE8 CU-J50DBE8 ← ← ← BASE PAN ASS’Y CWD52K1103 COMPRESSOR JT125G-P4V1 JT125G-P4Y1 JT160G-P4Y1 JT170G-P4Y1 ← ← ← ANTI-VIBRATION BUSHING CWH501081 ← ← ← NUT FOR COMP. MOUNT.
  • Page 144: Print Pattern

    22 Print Pattern 22.1. Indoor Unit Printed (Main)
  • Page 145: Indoor Unit Printed (Indicator)

    22.2. Indoor Unit Printed (Indicator) 22.2.1. Outdoor Unit (Main) [PHAAM] Printed in Malaysia SSBZ0603-02...

Table of Contents