Download Print this page

Technical Data - Panasonic 6295 Specification Sheet

Fire alarm systems enclosed heat detectors
Hide thumbs Also See for 6295:

Advertisement

6295
Enclosed heat detector, 57°C, class A2 S (54 to 70°C).
6296
Enclosed heat detector, 72°C, class B S (69 to 85°C).
6297
Enclosed heat detector, 87°C, class C S (84 to 100°C).
6298
Enclosed heat detector, 117°C, class E S (114 to 130°C).
3390
Label holder (100 holders per packet, excl. labels).
3391
Labels for 3390 (10 sheets à 132 labels)
Detector mounting holes, 2x(4x7 mm) c/c = 70 mm. E+/E- = Ext. LED. A/B = zone line in/out
(or end-of-line device). Connectors for wire diameter 0.6 - 1.2 mm (approx. 0.3 - 1.13 mm
Connection box mounting holes, 2x(5 mm) c/c = 108 mm. The connection box is prepared for
required number of compression glands, one, two or three. A gland is approx. 30 mm high.
Voltage (V DC)
rated
allowed
normal
Current consumption at nom.
voltage, quiescent (mA)
Current limitation required, when
active (mA)
(EBL equipment has current limitation.)
Ext. LED output
voltage (V)
current output (mA)
Alarm resistance (Ω)
Internal capacitance (nF)
Internal inductance
Ambient temperature (°C)
operating
(Min. / Typical / Max.)
storage
Ingress Protection rating
Static response temperature
Size ∅ x h (mm)
Weight (g)
Construction
Colour
Approvals
ATEX classification (for 6295 &
6296 only)
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet
MEW00132
Type numbers

Technical data

24
12-30
24 (zone line voltage)
0
6295-6297: Must be min. 6 and max. 40
6298: Must be min. 6 and max. 30
Zone line voltage minus 2 V
Max. 10 (no internal current limiter)
For 6295-6297: approx. 400. For 6298: approx. 680
For 6295-6296: max. 50
For 6295-6296: 0
6295 (A2 S):
6296 (B S):
-40 /+25 /+50
-40 /+40 /+65
-45 to +70
-45 to +70
IP67 (attached conn. box, silicon gasket and compression glands required)
57, 72, 87, or 117°C depending on detector / class. See text.
Detector: 95 x 42
Connection box: 100 x 35
Detector + Connection box: 100 x 75 (excl. compression glands)
Detector: 82
Connection box (incl. 3 glands): 134
Body (6295, 6296): ABS
Body (6297, 6298): Modified Polycarbonate.
Protector (on the body) & Connection box: Modified Polycarbonate.
Grey (N8, Munsell colour code)
05 EC Certificate no. 0845-CPD-232.1192 (6295); EN54-5
05 EC Certificate no. 0845-CPD-232.1193 (6296); EN54-5
05 EC Certificate no. 0845-CPD-232.1194 (6297); EN54-5
05 EC Certificate no. 0845-CPD-232.1195 (6298); EN54-5
6295:
II 3GD EEx nA II T5 (T100°C), -40°C ≤ T
6296:
II 3GD EEx nA II T5 (T100°C), -40°C ≤ T
Date of issue
2001-10-19
6297 (C S):
6298 (E S):
-40 /+55 /+80
-40 /+85 /+110
-45 to +70
-45 to +70
≤ 50°C
a
≤ 65°C
a
Revision / Date of revision
9 / 2008-10-10
2
).

Advertisement

loading

This manual is also suitable for:

629662976298