LG RS 485 User Manual page 11

For sv-is5 series,sv-ih series
Table of Contents

Advertisement

Parameter
Parameter Name
Address
000E
Sequence Monitor
000F
Trip information
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
Unit
Read/Write
SV-iS5
Bit 0: Stop, Bit 1: Forward Running
Bit 2: Reverse Running Bit 3:Fault (Trip)
Bit 4: Accelerating Bit 5: Decelerating
Bit 6: Output Frequency Arrival
Bit 7:DC Braking, Bit 8: Stopping
Bit 9: Not used
Bit10: BrakeOpen
Bit 11: FWD Run Command ON,
Bit 12: REV Run command ON,
Bit13: Rem. Run/Stop
Bit14: Rem. Freq. Cmd
-
R
SV-iH
BIT 0 : Stop
BIT 1 : Forward Run
BIT 2 : Reverse Run
BIT 3 : Fault (Trip)
BIT 4 : Accelerating
BIT 5 : Decelerating
BIT 6 : Output Frequency Arrival
BIT 7 : DC Braking
BIT 8 : Stopping
BIT13: Rem. Run/Stop
BIT 14: Rem. Freq. Cmd
SV-iS5
Bit 0:OCT1,Bit 1: OV, Bit 2: EXT-A
Bit 3: BX, Bit 4:OCT2, Bit 5: GF,
Bit 6: OH,Bit 7: ETH, Bit 8: OLT, Bit 9:
HW-diag,Bit10:EXT-B,Bit11:FO
Bit12:OPT,Bit13:POBit,14:IOLT, Bit15:LV
-
R
SV-iH
Bit 0: OC Bit 1: OV Bit 2:EXT
Bit 3: BX Bit 4:LV Bit 5:FUSE OPEN Bit 6:
GF Bit 7: OH
Bit 8: ETH Bit 9:OLT Bit 10: MCF
Bit 12: SCT Bit 15: IOLT
9
Data Value (Hex)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents