CHAPTER 5: SETTINGS
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism holds all of the latched indicators or messages in the set state after the initiating condition
has cleared until a
command is received to return these latches (not including FlexLogic latches) to the reset state.
RESET
The
command can be sent from the faceplate
RESET
programmed operand.
When the
command is received by the relay, two FlexLogic operands are created. These operands, which are stored
RESET
as events, reset the latches if the initiating condition has cleared. The three sources of
FlexLogic operand. Each individual source of a
RESET OP
,
or
(PUSHBUTTON)
RESET OP (COMMS)
selects the operand that creates the

5.9.6 Direct inputs and outputs

5.9.6.1 Direct inputs
SETTINGS  INPUTS/OUTPUTS  DIRECT INPUTS  DIRECT INPUT 1(32)
 DIRECT INPUT 1
These settings specify how the direct input information is processed.
— This setting allows the user to assign a descriptive name to the direct input.
DIRECT INPUT 1 NAME
— Represents the source of direct input 1. The specified direct input is driven by the device
DIRECT INPUT 1 DEVICE ID
identified here.
— The bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
DIRECT INPUT 1 BIT NUMBER
identified as
DIRECT INPUT 1 BIT NUMBER
DIRECT INPUT 1 DEFAULT STATE
following choices are available:
On — Defaults the input to Logic 1
Off — Defaults the input to Logic 0
Latest/On — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 1. When communication resumes,
the input becomes fully operational.
Latest/Off — Freezes the input in case of lost communications. When the latest state is not known, such as after relay
power-up but before the first communication exchange, the input defaults to Logic 0. When communication resumes,
the input becomes fully operational.
5.9.6.2 Direct outputs
SETTINGS  INPUTS/OUTPUTS  DIRECT OUTPUTS  DIRECT OUTPUT 1(32)
 DIRECT OUTPUT 1
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
RESET
RESET
to identify the source of the command. The
RESET OP (OPERAND)
operand.
RESET OP (OPERAND)
DIRECT INPUT 1
NAME: Dir Ip 1
DIRECT INPUT 1
DEVICE ID: 1
DIRECT INPUT 1
BIT NUMBER: 1
DIRECT INPUT 1
DEFAULT STATE: Off
DIRECT INPUT 1
EVENTS: Disabled
. This corresponds to the direct output number of the sending device.
— Represents the state of the direct input when the associated direct device is offline. The
DIRECT OUT 1 NAME:
Dir Out 1
button, a remote device via a communications channel, or any
RESET
command also creates its individual operand
Range: up to 12 alphanumeric characters
Range: 1 to 16
Range: 1 to 32
Range: On, Off, Latest/On, Latest/Off
Range: Enabled, Disabled
Range: up to 12 alphanumeric characters
INPUTS/OUTPUTS
commands each create the
RESET OP
setting here
RESET OPERAND
5-261