3104A00P Huawei Technologies Co., Ltd. provides customers with comprehensive technical support and service. If you purchase the products from the sales agent of Huawei Technologies Co., Ltd., please contact our sales agent. If you purchase the products from Huawei Technologies Co., Ltd. directly, Please feel free to contact our local office, customer care center or company headquarters.
About This Manual Release Notes This manual applies to Quidway S8500 Series Routing Switches VRP3.10. Related Manuals The related manuals are listed in the following table. Manual Content Quidway S8500 Series Routing It includes getting started, port, VLAN, network Switches Operation Manual...
Page 5
One or none is selected. Alternative items are grouped in braces and separated by { x | y | ... } * vertical bars. A minimum of one or a maximum of all can be selected. Huawei Technologies Proprietary...
Page 6
Select and release the primary mouse button without Click moving the pointer. Press the primary mouse button twice continuously and Double-Click quickly without moving the pointer. Press and hold the primary mouse button and move the Drag pointer to a certain position. Huawei Technologies Proprietary...
Page 7
Note, Comment, Tip, Knowhow, Thought: Means a complementary description. Environmental Protection This product has been designed to comply with the requirements on environmental protection. For the proper storage, use and disposal of this product, national laws and regulations must be observed. Huawei Technologies Proprietary...
Page 10
4.3 Mounting the Switch in User-Supplied Cabinet ..............4-2 4.3.1 Cabinet Configuration Guideline ................4-2 4.3.2 Mounting the Switch in Cabinet................4-7 4.4 Mounting the Switch in Huawei B68 Cabinet..............4-8 4.4.1 Installing B68 Cabinet ..................... 4-8 4.4.2 Cabinet Remodel Introduction................. 4-8 4.5 Connecting PGND Wire and Power Cord................
Page 11
Installation Manual Quidway S8500 Series Routing Switches Table of Contents 4.11.1 Correct Labels ..................... 4-23 4.11.2 Cable Management Requirements ..............4-23 4.12 Verifying the Installation....................4-26 Chapter 5 System Debugging ...................... 5-1 5.1 Setting up Configuration Environment................5-1 5.1.1 Setting up Configuration Environment ..............5-1 5.1.2 Connecting Cables....................
Page 12
Installation Manual Quidway S8500 Series Routing Switches Table of Contents A.1.7 Remarks........................A-9 A.2 Engineering Labels for External Cables of Alarm Box ............A-9 A.3 Engineering Labels for Ethernet Cables .................A-10 A.4 Engineering Labels for Optical Fibers ................A-12 A.4.1 Labels for the Fiber that Connects Two Devices..........A-12 A.4.2 Labels for the Fiber that Connects the Device and the ODF........A-13...
Page 13
Installation Manual Quidway S8500 Series Routing Switches List of Figures List of Figures Figure 1-1 Quidway S8505 ....................1-1 Figure 1-2 Quidway S8508 ....................1-2 Figure 1-3 Quidway S8512 ....................1-2 Figure 1-4 S8505 slots ......................1-3 Figure 1-5 S8508 slots ......................1-4 Figure 1-6 S8512 slots ......................1-5 Figure 1-7 Three-input PoE power frame ................1-8...
Page 15
Installation Manual Quidway S8500 Series Routing Switches List of Figures Figure 4-18 Console cable....................4-19 Figure 4-19 AUX cable ......................4-20 Figure 4-20 RJ-45 connector ....................4-21 Figure 4-21 LC connector ....................4-22 Figure 4-22 Cable bundling example I .................4-24 Figure 4-23 Cable bundling example II ................4-25 Figure 4-24 Cable bundling example III ................4-25...
Page 16
Installation Manual Quidway S8500 Series Routing Switches List of Figures Figure A-4 Writing direction of the label................A-5 Figure A-5 Stick the label onto proper position of the signal cable........A-6 Figure A-6 Fold up the label....................A-7 Figure A-7 Appearance of affixed labels on signal cables ............ A-7 Figure A-8 Appearance of affixed labels on power cables............
Page 17
Installation Manual Quidway S8500 Series Routing Switches List of Figures Figure B-14 B68-22 cabinet installation on slide rail ............B-14 Figure B-15 Appearance of the H800 series supports............B-15 Figure B-16 Dimensions of slide rail ................... B-16 Figure B-17 Installation flowchart of the B68-22 cabinet (on raised floor)......B-17 Figure B-18 Installation hole locations of the H800 series supports........
Page 18
Installation Manual Quidway S8500 Series Routing Switches List of Figures Figure C-2 Installation diagram of lightning arrester for network port........C-4 Huawei Technologies Proprietary...
Page 19
Installation Manual Quidway S8500 Series Routing Switches List of Tables List of Tables Table 1-1 Specifications for the AC-input PSU ...............1-7 Table 1-2 Specifications for the DC-input PSU ..............1-7 Table 1-3 Technical specifications of the PoE power system..........1-8 Table 1-4 LEDs of PoE power system..................1-9 Table 1-5 LEDs on the faceplate of the fan tray..............1-10...
Page 20
Installation Manual Quidway S8500 Series Routing Switches List of Tables Table 1-26 Status LEDs for the management 10Base-T/100Base-TX port ......1-20 Table 1-27 RS232/485 port specifications................1-20 Table 1-28 Console port specifications ................1-21 Table 1-29 AUX port specifications ..................1-21 Table 1-30 CF status LED ....................1-22 Table 1-31 Status LEDs for LPU modules................1-22...
Page 21
Installation Manual Quidway S8500 Series Routing Switches List of Tables Table 2-11 Interface modules available for the GT8P module ..........2-7 Table 2-12 Pin assignment of the RJ-45 GE connector ............2-8 Table 2-13 F32G module specifications .................2-8 Table 2-14 1000 Mbps port LEDs on the F32G module............2-9 Table 2-15 100 Mbps port LEDs on F32G module..............2-9...
Page 22
Installation Manual Quidway S8500 Series Routing Switches List of Tables Table 2-39 SP4 module specifications .................2-22 Table 2-40 POS port LEDs for the SP4 module ..............2-22 Table 2-41 Optical port modules available for the SP4 module ...........2-23 Table 2-42 UP1 module specifications .................2-23 Table 2-43 POS port LEDs ....................2-24...
Page 23
Installation Manual Quidway S8500 Series Routing Switches List of Tables Table B-1 Table of height of the H800 series supports ............B-15 Huawei Technologies Proprietary...
Chapter 1 Product Overview 1.1 Preface Huawei S8500 Series Routing Switches are orientated to operate at the convergence layer of a large MAN, or at the core layer of a small MAN, or at the backbone of a large enterprise network or a campus network. They serve as the Layer 3 devices in the switching center and convergence center.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview Figure 1-2 Quidway S8508 S8512: provides up to 720 Gbps switching capacity and allows the concurrent wirespeed forwarding on 576 GE ports, or 48 × 10GE ports, or 576 FE electrical ports, or 240 FE optical ports.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview 1.2 General Architecture The S8500 series use integrated chassis, which can be subdivided into power supply area, board area, backplane and fan area. 1.2.1 Chassis and Slots I. For S8505...
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview II. For S8508 SRPU SRPU AC or DC power AC or DC power entry Figure 1-5 S8508 slots All modules in the cabinet are hot-swappable. The S8508 chassis provides ten slots: The middle two accommodate SRPU modules, which are in 1+1 redundancy;...
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview III. For S8512 SRPU SRPU AC or DC power AC or DC power entry Figure 1-6 S8512 slots All modules in the cabinet are hot-swappable. The S8512 chassis provides 14 slots: The two in the middle accommodate SRPU modules, which are in 1+1 redundancy;...
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview I. Functions The backplane mainly functions in Providing communication channels for signal exchange between boards Providing support for hot-swapping of boards Auto-identifying the slots Connecting PSUs, achieving distributed power supply for SRPU modules, LPU modules and PSUs and providing corresponding control channels.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview INPUT1 INPUT1 INPUT2 INPUT2 INPUT3 INPUT3 -54V 83.0A -54V 83.0A POE Power System PSE4500-A POE Power System PSE4500-A NEG (-) NEG (-) RTN (+) RTN (+) This device has more than one power input. Do This device has more than one power input.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview Table 1-4 LEDs of PoE power system Normal Abnormal Color Causes status status There is no AC input or the fuse Green is broken. Green There is no DC output.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview Table 1-5 LEDs on the faceplate of the fan tray Color Status The fan tray is faulty. Green The fan tray is running normally. The fan tray is running normally.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview Table 1-8 Status LEDs for the management 10Base-T/100Base-TX port Status No link is present. LINK A link is present. No packets are transmitted/received on the port. Blinking Packets are being transmitted/received on the port.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview AUX port The AUX port uses an RJ-45 connector. The port can serve as a backup port for the Console port to connect a background terminal, or directly connect a modem device, for remote system debugging, configuration, maintenance and management.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview Table 1-13 Status LEDs for LPU modules Status The module is faulty. The module is faulty or out of position. Blinking (1s) The module is running normally. Fast blinking (125 The module is booting or not registered successfully.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview Table 1-19 Console port specifications Attribute Description Connector RJ-45 Standard Asynchronous EIA/TIA-232 Baud rate 9600 bps (default) Transmission ≤ 15 m (49 ft) distance Connects a serial port of a local PC and runs terminal Service emulation on the PC.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview Table 1-21 CF status LED Status The CF card is in position and is idle. You cannot remove the card. The CF card is in position and reading/writing data. You Blinking cannot remove the card.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview SRP1N1 LED Status The SRP1N1 module has alarms. The SRP1N1 module has no alarms. Green The SRP1N1 module is active. The SRP1N1 module is standby. III. SRP1N2 module Specifications The S8505 uses SRP1N2 modules.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview The SRP1N2 module provides a CF port to accommodate a standard CF card, where you can save logging information, host version information, alarming and other diagnostic information and conveniently upgrade software online.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview Attribute Description The port for monitoring and communication with the external Service subsystem, such as external PoE power supply module Console port The Console port uses an RJ-45 connector. It can be connected to a background terminal for system debugging, maintenance, management, and host software loading.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview Status LEDs CF status LED You can check operating status of the CF card by reading the CF status LED on the panel. Table 1-30 CF status LED Status The CF card is in position and is idle.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview Table 1-32 Status LEDs for the SRP1N2 module SRP1N2 LED Status The switching fabric unit is active. The switching fabric unit is standby. Green The SRP1N2 module is faulty.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview Table 1-35 Status LEDs for the management 10Base-T/100Base-TX port Status No link is present. LINK Green A link is present. No packets are transmitted/received on the port. Packets are being transmitted/received on the Orange blinking port.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview AUX port The AUX port uses an RJ-45 connector. The port can serve as a backup port for the Console port to connect a background terminal, or directly connect a modem device, for remote system debugging, configuration, maintenance and management.
Installation Manual Quidway S8500 Series Routing Switches Chapter 1 Product Overview Figure 1-13 Front panel of the NAT service processor card Figure 1-14 Rear panel of the NAT service processor card II. VPLS service processor card (LSB1VPNB) Technical specifications The VPLS service processor card provides no external port.
1.3 Software Features The software of the S8500 series is based on the idea of distributed processing and runs on Huawei network operating system VRP. The following table summaries the supported software features. Table 1-43 Software features of the S8500 series...
Page 54
Configuration through the command line interface (CLI) Configuration through the Console/AUX port Telnet configuration/maintenance through Ethernet ports Modem dialup configuration/maintenance through AUX port SNMP management [with Huawei Quidview system, RMON Management (remote monitoring), 1/2/3/9 groups of MIBs] maintenance MPLS VPN management tool (VPN Manager)
Page 55
Quidway S8500 Series Routing Switches Chapter 1 Product Overview Note: The features listed here are for VRP3.10. All specifications are subject to changes without notice. For up-to-date information, please contact Huawei marketing or technical support personnel. Huawei Technologies Proprietary 1-32...
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules Chapter 2 LPU Modules 2.1 Overview The S8500 series are modular switches that are designed following industry standards. The series provide auto-sensing 10/100 Mbps electrical ports, auto-sensing 10/100/1000 Mbps electrical ports, 1000 Mbps electrical ports, 100 Mbps (single mode/multimode) optical ports, 1000 Mbps (single mode/multimode) optical ports, and one 10GE optical port as well.
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules 2.3.2 Panel and LEDs Figure 2-2 XP4 module panel The XP4 module has two LEDs for each optical port on its panel. Table 2-5 1000 Mbps optical port LEDs on the XP4 module Status No link is present.
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules 2.4.2 Panel and LEDs Figure 2-3 XK1 module panel The XK1 module has two port LEDs for the 10GE port on its panel. Table 2-7 Port LEDs on the XK1 module Status No link is present.
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules 2.5.3 Matching Cable The GT8P module provides 1000 Mbps SFP optical ports and 10/100/1000 Mbps auto-sensing RJ-45 electrical ports. You can use these SFP optical modules: Table 2-11 Interface modules available for the GT8P module...
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules Table 2-12 Pin assignment of the RJ-45 GE connector 10Base-T/100Base-T/1000Base-TX Pin No. Signal Function MX_0+ Transmit and receive data. MX_0- Transmit and receive data. MX_1+ Transmit and receive data.
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules 2.6.2 Panel and LEDs Figure 2-6 F32G module panel The F32G module has two LEDs for each 1000 Mbps port on its panel. Table 2-14 1000 Mbps port LEDs on the F32G module Status No link is present.
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules 2.9.3 Matching Cable The ports on the GT12 module uses RJ-45 connectors (see Table 2-11) and category-5 twisted pair cables which allow the transmission distance of 100 m (328 ft).
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules Attribute GT24 Max. power consumption 110 W Number of ports Connector RJ-45 Rate 10/100/1000 Mbps 2.10.2 Panel and LEDs Figure 2-12 GT24 module panel The GT24 module has one LEDs for each port on its panel.
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules Attribute GV48 Number of ports Connector RJ-45 Rate 10/100/1000 Mbps 2.11.2 Panel and LEDs Figure 2-13 GV48 module panel The GV48 module has one LED for each port on its panel.
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules Attribute FP20 Port Connector SFP/LC Rate 100 Mbps full duplex 2.12.2 Panel and LEDs Figure 2-14 FP20 module panel The FP20 module has two LEDs for each port on its panel.
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules 2.13.2 Panel and LEDs FT48A Figure 2-15 FT48 module panel The FT48 module has one LED for each port on its panel. Table 2-33 Port LEDs on FT48 module Status A link is present.
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules 2.14.2 Panel and LEDs Figure 2-17 P4G8 module panel The P4G8 module has two LEDs for each port on its panel. Table 2-37 1000 Mbps port LEDs on the P4G8 module Status No link is present.
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules 2.16.2 Panel and LEDs Figure 2-19 UP1 module panel The UP1 module has two LEDs for each port on its panel. Table 2-43 POS port LEDs Status The link is normal.
Installation Manual Quidway S8500 Series Routing Switches Chapter 2 LPU Modules 2.17.2 Panel and LEDs Figure 2-20 VP2 module panel The VP2 module has two LEDs for each port on its panel. Table 2-45 Port LEDs of VP2 module Status The link is normal.
Installation Manual Quidway S8500 Series Routing Switches Chapter 3 Installation Preparation Chapter 3 Installation Preparation 3.1 Safety Recommendations To avoid possible bodily injury and device impairment, please read the following safety recommendations carefully before installing the S8500 series. The recommendations do not cover every possible hazardous condition.
Installation Manual Quidway S8500 Series Routing Switches Chapter 3 Installation Preparation Caution: You can only hold the handles at both sides of the chassis when moving the switch, but not the plastic panel of the chassis, the handle of the fan frame, the handle of the PSUs or the air vents of chassis.
Installation Manual Quidway S8500 Series Routing Switches Chapter 3 Installation Preparation density and is invisible to human eyes; when a beam of light enters the eye, retina may be burned. Caution: The laser inside the optical fiber may hurt your eyes.
Installation Manual Quidway S8500 Series Routing Switches Chapter 3 Installation Preparation Table 3-1 Limitation on dust content in equipment room Mechanical active Unit Content material ≤3 x 10 Dust particle particles/m³ (No visible dust on desk in three days) Note: Dust particle diameter ≥ 5µm Besides the dust specifications, the equipment room of the switch should also meet the rigorous requirements for the content of salt, acid and sulfide in the air.
Installation Manual Quidway S8500 Series Routing Switches Chapter 3 Installation Preparation anti-interference and ESD-prevention. The user must provide good grounding system for the switch. 3.2.5 Power Supply Requirements The S8500 series adopt redundant PSUs. Where, AC PSU: Rated voltage: 100 VAC to 240 VAC, 50 Hz or 60 Hz...
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation Chapter 4 Switch Installation The S8500 series shall be installed indoors in a fixed place. 4.1 Confirming Installation Preparation Make sure that you have read Chapter 3 Installation Preparation carefully.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation 4.3 Mounting the Switch in User-Supplied Cabinet 4.3.1 Cabinet Configuration Guideline Note: The S8500 chassis has two versions and their major difference lies in the power supply area at the bottom. On the chassis of the new version, the power supply is 3 U (1 U = 44.45 mm) high and there is a PoE entry area between two PSUs for connecting the...
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation (1) Blank filler panel (2) Cabling frame (3) Backward cabling frame (4) External PoE power supply slot (or reserved) Figure 4-2 Two old S8505 chassis in a cabinet Guideline: The space marked in Figure 4-2 must be reserved, and the remaining area is at your disposal.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation (1) Blank filler panel (2) Cabling frame (3) Backward cabling frame (4) External PoE power supply slot (or reserved) Figure 4-3 One new S8505 chassis in a cabinet Guideline: The space marked in Figure 4-3 must be reserved, and the remaining is at your disposal.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation (1) Blank filler panel (2) Cabling frame (3) Backward cabling frame (4) External PoE power supply slot (or reserved) Figure 4-4 Two new S8505 chassis in a cabinet Guideline: The space marked in Figure 4-4 must be reserved, and the remaining is at your disposal.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation (1) Blank filler panel (2) Cabling frame (3) Backward cabling frame (4) External PoE power supply slot (or reserved) Figure 4-5 One S8508 chassis in a cabinet Guideline: The space marked in Figure 4-5 must be reserved, and the remaining is at your disposal.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation (1) Blank filler panel (2) Cabling frame (3) Backward cabling frame (4) External PoE power supply slot (or reserved) Figure 4-6 One S8512 chassis in a cabinet Guideline: The space marked in Figure 4-6 must be reserved, and the remaining is at your disposal.
4.4 Mounting the Switch in Huawei B68 Cabinet When purchasing the S8500 series, you may also select a Huawei B68 Series Cabinet as needed. There are two types of B68 cabinets available for the S8500 series: B68-18 model: 1.8 m B68 cabinet (600 x 800 x 1800 mm, or 23.6 x 31.5 x 70.9 in.)
Page 95
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation Step 2: Wear the connector of the PGND wire accompanied with the switch on the grounding screw. Step 3: Insert the grounding screw into the grounding hole and screw it down.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation (1) Air filter (2) Grounding screw (3) PGND wire (4) Ground bar of the equipment room (5) Rear panel of the switch Figure 4-7 Ground the switch when ground bar is available If there is no ground bar but earth nearby and the grounding body is allowed to be buried, you can simply hammer an angle iron or steel pipe no shorter than 0.5 m...
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation (1) Live line (2) Neutral line (3) PE line (4) 3-core AC input cable (5) Transformer (6) AC power input (7) Front panel of the switch Figure 4-9 Ground the switch via AC PE wire...
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation 4.5.2 Connecting AC Power Cord Caution: For lightning protection, the AC power should be led through an external lightning device into the switch. Make sure the power switch on the PSU is at OFF position before connecting the power cord.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation (1) Connector-retention clamp (2) Input LED (3) Output LED (4) Fail LED (5) Power switch Figure 4-12 Connect AC power cord for the S8508/S8512 4.5.3 Connecting DC Power Cord Caution: Power OFF all the related parts of the switch before connecting the DC power cord.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation Step 4: Insert one end of the PGND OT terminal (with a yellow-green wire) of the DC power cord into the “PGND” connector on the PSU, and fasten the mounting nut.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation Note: This section only focuses on the cable connection between the external POE power supply and the S8500 series switch. For the installation of the external PoE power supply, see the manual shipped with the power supply.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation Caution: Observe the signs on devices and connect the cables correctly. Choose right cables based on the load. (1) DC output terminal: NEG(-) (2) DC output terminal: RTN(+) (3) AC input switch...
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation Figure 4-17 Install cabling rack 4.7 Installing Fan Tray The fan tray is hot swappable. Caution: In case of bodily injuries, do not touch any naked wire, terminal or other parts of the product with hazardous voltage labels.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation Note: The above installation steps are just for replacing your fan tray, since the fan tray is delivered together with the chassis and no initial installation is required. 4.8 Installing LPU The LPUs of the S8500 series are hot-swappable.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation Note: The PC serial port is not hot-swappable, so you are not allowed to insert or remove the console cable into or from the PC serial port. When connecting the console cable, first connect the DB9/DB25 end to the PC serial port and then the RJ45 end to the console port of the switch.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation Table 4-2 AUX cable pinouts RJ-45 Signal Direction DB-25 DB-9 → → → ← ← ← ← II. Connecting AUX cable Step 1: Plug the RJ-45 connector of the AUX cable into the AUX port of the switch.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation 4.9.4 Connecting Fiber Note: All the megabit and gigabit optical modules available for the S8500 series are SFP modules that provide LC user ports. I. Introduction to fiber connector...
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation Caution: When the optical interface has not been connected with a fiber connector or its dustproof mesh is open, there might be some invisible radiation emitted from the optical interface.
Use the right type of ties to bundle the cables. Do not bundle cables with joined ties. Huawei Technologies provides the following types of ties: 100 × 2.5 mm (3.9 in × 0.1 in), 150 × 3.6 mm (5.9 × 0.1 in), 300 × 3.6 mm (11.8 × 0.1 in), 530 × 9 mm (20.9 ×...
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation Figure 4-23 Cable bundling example II Bundle the cables wherever cable bending cannot be avoided. However, the cable ties cannot be placed inside the bending area in case of the likelihood of cable core break due to excessive stress.
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation For the cable terminals fixed using screw threads, the screws or nuts should be securely fastened and prevented from loosing. See the following figure; Flat Flat Flat Flat Spring...
Installation Manual Quidway S8500 Series Routing Switches Chapter 4 Switch Installation Caution: Confirm that you have turned off the power before checking, otherwise, improper connection will hurt people or impair the components of the switch. After installing the switch, verify the installation by the following list, ensuring all the checking results are normal.
Installation Manual Quidway S8500 Series Routing Switches Chapter 5 System Debugging Chapter 5 System Debugging 5.1 Setting up Configuration Environment 5.1.1 Setting up Configuration Environment Connect a terminal (a PC in this scenario) to the switch with a Console cable.
Installation Manual Quidway S8500 Series Routing Switches Chapter 5 System Debugging Click [Start/Programs/Accessories/Communications/HyperTerminal] to access the Hyper Terminal window. Click icon in the window to set up a new connection and the system will display the following Connection Description interface.
Installation Manual Quidway S8500 Series Routing Switches Chapter 5 System Debugging Figure 5-4 Set serial interface parameters Click <OK> upon the completion of the serial interface parameter setting and the system will access the following HyperTerminal interface. Figure 5-5 HyperTerminal Window Select [Properties] in the HyperTerminal dialog box to access the Quidway Properties Window.
Installation Manual Quidway S8500 Series Routing Switches Chapter 5 System Debugging Figure 5-6 Set the terminal emulation parameters 5.2 Powering and Booting the Switch 5.2.1 Verifying Installation before Powering the Switch You should verify the installation of the switch before powering it on, to make sure that The switch is stable enough.
Installation Manual Quidway S8500 Series Routing Switches Chapter 5 System Debugging 5.2.3 Verifying after Power-on (Recommended) To ensure the configuration works that you will make on the switch, you are recommended to check the switch after powering it on to make sure that: The cooling system is working.
Page 119
Installation Manual Quidway S8500 Series Routing Switches Chapter 5 System Debugging Booting from Flash... Decompress Image......................OK! Starting at 0x10000... User interface Con 0 is available Press ENTER to get started. Note: It will take about two minutes and five seconds for S8505 to access the configuration interface shown above after it is powered on and booted, but S8508 will take about three minutes and S8512 three minutes and 30 seconds.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Chapter 6 Switch Monitoring and Maintenance 6.1 Monitoring the Switch Although the S8500 series have undergone a comprehensive and strict factory test before delivery, there might be some fault occurring due to improper installation. This chapter describes how to troubleshoot the S8500 series.
Excessive dust accumulated on the air filter will block the fan tray from free ventilation and even lead to power supply failure. If you cannot solve the problem yet after going through the above checking steps, contact Huawei technical support engineers rather than disassembling the PSU yourself. 6.1.3 Troubleshooting Fan Tray The S8500 series provide two LEDs on the fan tray.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Note: The ALM LED on the fan tray keeps ON for 2 to 3 seconds when the switch is powered If the RUN LED is OFF, check if: The fan tray has been well seated.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Caution: The PSU of the S8500 series is hot-swappable. When installing or replacing a PSU while power is being supplied, you must take care in the operation procedures and safety with electricity. Do not touch any naked wires, terminals or any parts of the product marked with a dangerous voltage label to avoid bodily injury.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Caution: The S8500 series use multiple power systems, and you must turn off all of them when removing the AC PSU. As the PSU of the S8500 series is heavy, use both hands to pull it out slowly and gently, with one holding its handle and the other holding its bottom.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Figure 6-2 Remove and install the DC PSU Removing DC PSU for S8508/S8512 Step 1: Turn the power switch on the DC PSU to the “OFF” position, and remove all the input power cords after disconnecting the input power.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance 6.2.3 Replacing and Cleaning the Air Filter of PSU The air filter of AC PSU and DC PSU can be replaced in a similar way even though they have different shapes.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance (1) PSU (2) Air filter (3) Air filter cover Figure 6-4 Remove the air filter of AC PSU II. Installing the air filter of PSU Step 1: Check that the black mesh has been nested in the air filter cover. If not, go ahead to do that.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance 6.2.4 Replacing and Cleaning the Air Filter of Chassis Caution: You are strongly recommended to clean the air filter semimonthly to guarantee adequate ventilation. The air filter of the S8500 series is installed at the air intake vents of the chassis. If you do not clean the air filter often, the dust accumulated on it will block the holes of the filter, hence affecting the ventilation of the chassis.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Caution: As the air filter is rather long, you should hold its front end with one hand, and bear its weight by putting another hand underneath it when sliding the air filter into the chassis.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Step 4: Fasten the captive screws to fix the card. Figure 6-8 Install a card 6.2.6 Replacing the Fan Tray Caution: Do not touch naked wires, terminals or the switch parts where dangerous voltage warning is given to avoid bodily injury.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Step 4: Hold the handle of the fan tray with one hand and its bottom with the other and pull them outward. Align the fan tray with the guides in the chassis and slide it gently into the slot until its positioning pin touches the positioning hole in the chassis.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Loading using FTP and through Ethernet port 10) Local or remote loading through CLI: Loading using FTP Loading using TFTP 6.3.2 Local Loading through Boot Menu I. Boot menu...
Page 133
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Note: To enter the Boot menu, you must press <Ctrl+B> within five seconds after the appearance of the prompt “Press Ctrl-B to enter Boot menu...”. Otherwise, the program decompression process will begin.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Figure 6-9 Attribute settings of HyperTerminal serial interface II. Upgrading software through console port (XModem) Brief introduction to XModem XModem, a type of file transfer protocol, is broadly applied for its simplicity and good performance.
Page 135
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance SERIAL SUBMENU 1. Download file to SDRAM through serial interface and boot 2. Download file to Flash through serial interface 3. Download file to HardDisk through serial interface 4.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Note: After changing the baud rate, you must close the terminal emulation program and start it again for at least once in order to validate the new baud rate.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Figure 6-11 Sending file page Step 8: After downloading the program successfully, the system begins to write the data into the Flash. The downloading operation will end upon a successful write operation.
Page 138
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance receives the ACK from the server. The TFTP transmission files have two forms, i.e., binary for program transmission and ASCII for text transmission. Following is the upgrading procedure described taking the S8512 working as a TFTP Client as an example.
Page 139
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance host name : 8500 , file name : 8500.app inet on ethernet (e) : 1.1.1.1 inet on backplane (b): host inet (h) : 1.1.1.2 gateway inet (g)
Page 140
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance delete it?(Y/N):y Deleting file-------------------------------------------------------- -------------------------------------------------Done Free flash Space : 15862784 bytes Writing Flash-------------------------------------------------------- -------------------------------------------------------------------------- --------------------------------------------Done Step 8: The information displayed in the last step means a successful file downloading operation.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Note: If you want to download files using FTP, please set the flags to 0x0 when setting the Ethernet interface parameters. After downloading the host program through the Boot menu, you must specify it as the...
Page 142
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance Trying ... Press CTRL+K to abort Connected. 220 WFTPD 2.0 service (by Texas Imperial Software) ready for new user User(none):8500 331 Give me your password, please Password: 230 Logged in successfully [ftp] get SWITCH002.app SWITCH002.app...
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance <Quidway> reboot Caution: You must reboot the switch using the reboot command to validate the host program. If Flash memory space is not enough, you can delete some of the program files in Flash after completing the Boot ROM loading.
Installation Manual Quidway S8500 Series Routing Switches Chapter 6 Switch Monitoring and Maintenance 6.3.5 Troubleshooting Software Upgrade These types of problems may occur during software upgrade: I. No response from SRPU serial interface Check if the serial interface cable is in good condition and if its attributes are set correctly.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables Appendix A Engineering Labels for Cables Engineering labels are affixed to both ends of the various cables to identify the physical positions of cables on different devices. Labels on the cables facilitate correct and orderly connection of cables, and easy maintenance after the installation.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables 84.0 11.0 10.0 11.0 37.0 (1) Dividing line (2) Cut dotted line Figure A-1 Label for signal cables The dividing lines on the label help to specify more clearly the position of a cable. For example, there is one between the cabinet number and the frame number and another one between the frame number and the slot number.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables 26.2 R1.0 12.2 (1) Cable tie (2) Label (3) Dividing line on the label Figure A-2 Label for power cables A.1.3 Printing Labels The contents can be printed or written on the labels. Printing is recommended for the sake of high efficiency and eye-pleasant layout.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables If two merged cells are still not enough to accommodate the characters, use multiple lines. III. Requirements on the printer To print the labels, laser jet printer must be used, although there is no restriction on the model of the printer.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables Contents in the cells should be aligned in the center. In a single-line printout, the dividing lines and the mark “TO” should not be covered by the printed characters.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables A.1.5 Affixing Labels After printing or writing the label, remove the label from the bottom page and affix it to the signal cable, or the identification plate of the power cable.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables Cable Cable Stick side Stick side Fold up Fold to right Figure A-6 Fold up the label After the printed part of the label has been folded up, the narrow part of the label should be covered completely, as shown in Figure A-7.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables Cable -48V2 Cable Figure A-8 Appearance of affixed labels on power cables A.1.6 Information Carried on Labels I. For power cables Labels for power cables are only affixed on one side of the identification plates. On the labels, there is information (the part after the mark “TO:”) about the location of the...
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables Therefore, the information in Area 1 at one end is the same as the information in Area 2 at the other end of the cable, and vice versa. In other words, the local information at one end is called the opposite information at the other end.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables The label on the alarm cable carries simple information, and only part of the text area needs to be filled in. It is recommended to keep the whole length of the label instead of cutting out the blank area.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables Content Meaning Example Cabinet For example, B02 number Valid location number of the terminal device onsite. If the cable is connected to a router in a cabinet, the serial numbers of the cabinet, the...
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables “B02-03-12” indicates that the opposite end of the Ethernet cable is connected with Ethernet Port 12, Frame 03 of the cabinet on Row B, Column 02 in the machine room.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables Figure A-12 Example of the label on the optical fiber between two devices “A01-01-05-05-R” indicates that the local end of the optical fiber is connected with Optical Receiving Interface 05 on Slot 5, Frame 01 in the cabinet on Row A, Column 01 in the machine room.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables Content Meaning Example Numbered in the same rule as that MN: row number and of the cabinets, for example, G01 is the ODF of Row G and Column...
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables A.5.1 Labels for the Trunk Cable that Connects Two Devices I. Meaning of the label Table A-6 shows the information on both sides of the labels affixed to the trunk cable that connects two devices.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables A.5.2 Labels for the Trunk Cable that Connects the Device and the DDF I. Meaning of the label Table A-7 shows the information on both sides of the labels affixed to the trunk cable that connects the device and the DDF.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables Figure A-15 Example of the label on the trunk cable between the device and the DDF “A01-03-01-01-R” indicates that local end of the trunk cable is connected with the receiving terminal of Trunk Cable 01 in Slot 01, Frame 03 of the cabinet on Row A, Column 01 in the machine room.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables II. Example of the label Figure A-16 shows the label on the subscriber cable. Figure A-16 Example of the label on the subscriber cable “A01-03-01-01” indicates that local end of the subscriber cable is connected with Terminal 01 on Slot 1, Frame 03 of the cabinet on Row A, Column 01 in the machine room.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables A-9 lists the information of two -48V power supplies on the label. The information for other DC voltages (such as 24V, 60V) should be given in similar methods.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables Note: In the power distribution box (or the first power cabinet of a row in the transmission machine room), every terminal block on the -48V connector bar has a numeric identification.
Installation Manual Quidway S8500 Series Routing Switches Appendix A Engineering Labels for Cables II. Example of the label Make sure that labels are affixed in correction direction. That is, after the cable ties are bundled onto the cable, the identification plates with the labels should face up, and the...
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet Appendix B Installation of B68 Cabinet Note: Except for the height, B68-18 (1.8m in height) cabinet and B68-22 (2.2m in height) cabinet have the same installation requirements in space planning, cabinet positioning, and fixing.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet Caution: The feet are insulated. The anchor plate components include insulating units. During construction, make sure that the insulating units are correctly installed so that the whole set of equipment is insulated from the ground before the ground wire is connected, thus effectively meeting the insulation requirement.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet B.2.2 Installation Flow The cabinet installation flow on the cement ground is shown in Figure B-3: Start C abinet positioning C abinet lev eling C abinet fastening...
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet (1) M12 expansion bolt hole mark (2) Cabinet foot location mark (3) Cabinet outline (4) Rear of cabinet (5) Wall or reference body Figure B-4 Installation holes and cabinet foot location marks of a single cabinet...
Page 170
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet III. Drilling holes Use a percussion drill with 16 bit to drill holes for the installation of the expansion bolts to fix the anchor plate. When using the percussion drill, be sure to hold the bit perpendicular to the ground.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet (1) Upper enclosure frame of the cabinet (2) Combining plate (3) Bolt M6×10 (4) Top cover of the cabinet Figure B-8 Removal and installation of the top cover of B68-22 cabinet (1) Nut M8 (2) Flat washer Φ8...
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet Caution: It is required to remove the top covers before combining cabinets. After combination, top covers are to be installed again. B.2.6 Cabinet Fastening I. Installing anchor plate Install the anchor plate of the B68-22 cabinet according to Figure B-10.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet (1) Retaining nut of anchor plate (2) Cabinet M16 foot (3) Anchor plate of the B68-22 cabinet Figure B-10 Installation of anchor plate of the B68-22 cabinet II.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet from the earth. In this case, remove all anchor plate parts to check whether the insulating covering or insulating washer is installed or whether the insulating parts are damaged.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet Figure B-13 Installation of two cabinets on the cement ground B.3 Cabinet Installation on Raised Floor When the B68-22 cabinet is installed in the equipment room with the raised floor, the H800 series supports are adopted.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet B.3.1 Introduction to Support and Slide Rail I. Brief Introduction to Support The support is to raise the cabinet for the convenience of floor paving and cable wiring in the equipment room.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet (1) Upper support (2) Lower support (3) Ground installation hole (4) Slide rail connection hole (5) Height scale Figure B-15 Appearance of the H800 series supports Installing support components There are four models of H800 series supports, three of which are height-adjustable and the other one is of fixed-height.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet The model IV of the H800 series is a fixed height support, which is suitable for the ultra high and ultra low supports. The suitable lowest floor height of the component is 100mm.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet Start Support positioning Install support Install slide rail Install an ti-static floor su pporting acce ssories Lev el cabinet Fasten cabinet Insulation test Test passed? Recov er floor Figure B-17 Installation flowchart of the B68-22 cabinet (on raised floor) B.3.3 Support Positioning...
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet installation hole locations of two cabinets and Figure B-21 shows the installation hole locations of multiple cabinets. Figure B-18 Installation hole locations of the H800 series supports...
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet (1) M12 expansion bolt hole mark (2) Cabinet outline (3) Rear of cabinet (4) Wall or reference body Figure B-20 Installation hole locations of two cabinets (1) M12 expansion bolt hole mark...
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet III. Drilling holes Use a percussion drill with Φ16 bit to drill holes for the installation of the expansion bolt M12 to anchor the support. When using the percussion drill, be sure to hold the bit perpendicular to the ground.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet Figure B-24 Appearance of T nut Leveling and fixing slide rail Fix the slide rail on the support with T nut, flat washer, spring washer and bolt M12 × 20.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet B.3.5 Installing Supporting Accessories of Raised Floor The supporting accessories of raised floor are to support the raised floor around the cabinet. I. Installing angle plate for the floor bracket and angle supports for slide rails Fix the angle plate and angle supports with bolt, flat washer and spring washer according to installation location, shown in Figure B-27.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet (1) Flat washer Φ12 (2) Spring washer Φ12 (3) Bolt M12%35 (4) Nut M12 (5) Side floor bracket (6) Angle support of right slide rail (7) Angle support of left slide rail (8) Angle plate for floor bracket...
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet (1) Retaining nut of the cabinet (2) Cabinet foot (3) Retaining nut of anchor plate (4) Lower enclosu re frame of the cabinet igure B-29 Cabinet feet fasten B.3.7 Cabinet Combination Connection...
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet (1) Upper enclosure frame of the cabinet (2) Combining plate (3) Bolt M6%10 (4) Top cover of cabinet Figure B-30 Removal and installation of top cover of the B68-22 cabinet (1) Nut M8 (2) Flat washer Φ8...
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet Caution: It is required to remove the top covers before combining cabinets. After combination, top covers are to be installed again. B.3.8 Cabinet Fastening I. Installing T nuts Before the cabinet is fixed, install the T nuts fixing the cabinet anchor plate into the upper trough of the slide rail.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet III. Installing insulating parts and fixing anchor plate First put the insulating washer under the anchor plate (Two insulating washers are required for one anchor plate) and align it with T nut in the upper trough of the slide rail.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet IV. Fastening retaining nut of anchor plate Fasten the retaining nut of the anchor plate on the anchor plate according to part B in Figure B-33, and then fasten the bolt force moment to 45 Nm.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet Figure B-35 B68-22 cabinet installation in the equipment room with raised floor B.4 Quakeproof Reinforcement of Cabinet Note: For the areas subject to earthquake risk, in order to improve the quakeproof performance of the cabinet, reinforcement measures should be followed for the cabinet according to the following procedures.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet II. Installing quakeproof lever Connect the angle connector and channel beam with the quakeproof angle plate or the ceiling of the equipment room according to Figure B-38. Figure B-39 shows the quakeproof reinforcement for multiple cabinets.
Installation Manual Quidway S8500 Series Routing Switches Appendix B Installation of B68 Cabinet (1) Quakeproof angle plate Figure B-37 Position of quakeproof angle plate after reinforcement Huawei Technologies Proprietary B-35...
Installation Manual Quidway S8500 Series Routing Switches Appendix C Lightning Protection of the Switch Appendix C Lightning Protection of the Switch C.1 Installation of Lightning Arrester for AC Power (Socket Strip with Lightning Protection) Caution: Lightning arrester will not be shipped with the switch. You should purchase it by yourself if needed.
Installation Manual Quidway S8500 Series Routing Switches Appendix C Lightning Protection of the Switch Caution: Make sure that the arrester is well grounded before using the lightning arrester for power. After inserting AC power cord plug of switch into the socket of lightning arrester, if the green LED is on and the red LED does not alarm, it means that the lightning arrester of power is running and the function of lightning protection has taken effect.
Page 205
Installation Manual Quidway S8500 Series Routing Switches Appendix C Lightning Protection of the Switch I. Required tools Phillips screwdriver or Flat-blade screwdriver Multimeter Tilted wire cutter II. Installation procedure Step 1: Tear the protection paper at one side of the double faced adhesive tape apart from the tape, and stick the tape on the surface of the arrester.
Page 206
Installation Manual Quidway S8500 Series Routing Switches Appendix C Lightning Protection of the Switch Network cable indoors Network cable led into from outdoor Lightning arrester for network port (attached onto the chassis) Switch Ground wire of lightning arrester Power input...