Utz-Bd035B - Fujitsu UTZ-BD035B Technical Manual

Energy recovery ventilators
Hide thumbs Also See for UTZ-BD035B:
Table of Contents

Advertisement

2-2. UTZ-BD035B

② ⑤
EA
(Exhaust Air)
OA
(Outside Air)
Maintenance Space
Wiring Diagram
NO.
Parts Name
Qty.
1 Frame
1 Galvanized sheets
2 Adapter
4 ABS
3 Electrical Equipment Box
1
4 Inspection Cover
1 Galvanized sheets
5 Fan
2 ABS
6 Motor
2
7 Heat Exchange Element
2 Special paper + Resin
8 Filter
2 Nylon-Polyester Fiber Collection Efficiency AFI 82%
9 Damper
1
10 Damper Motor
1
11 Ceiling Suspension Fixture 4 Galvanized sheets
 BE CAREFUL OF DEWING AND
FROSTING
As shown in the Figure, suppose a high temp absorbing air condition
A and a low temp absorbing air condition B are plotted on the air line
figure, then a high temp air A is heat-exchanged by the unit and goes
out of the saturation curve as shown by Point C.
In this case, the unit will be dewed or frosted.
To aboid this, you are required to heat a low temp air B up to B' so as
to get C' below the saturation curve, before using the unit.
C
C'
B
B'
Dry-bulb temperature(˚C)
978
1050
470
70
Material
Remarks
A
RA
(Room Air)
SA
(Supply Air)
4-13×30 Oval hole · Suspension Fittings
Inspection Opening □450
(For the inspection of the filters, heat exchange elements, fans, motors, and damper)
Earth Terminal
70
122
157
 REFERENCE SKETCH
Pipe Hood
Outside Intake Duct
EA
(Exhaust
Air)
OA
(Outside intake Air)
The two outside ducts(the Outside Intake Duct and the
Exhaust Duct)must be insulated to prevent condensation.
(Material;Glass wool, Thickness;25)
 Duct size (Nominal Diameter): ø150
 The above dimensions do not include the thickness of
the insulasion material on the unit body.
- (01-05) -
317
35
An inspection opening is necessary to
clean the heat exchange element and
filter once or twice a year.
Ceilling Suspension Bolts
Supply Air Duct
RA
(Room Air)
Room Intake Duct
Inside Supply Opening
Heat Insulation Material
(Supply/Exhaust Air Grill)
Room Intake Opening
(Supply/Exhaust Air Grill)
Exhaust Air Duct
247
159
182
SA