FM — The default function assigned to this output terminal is Output Frequency. This output terminal
produces an output current or voltage that is proportional to the magnitude of the Output Frequency of
the Q9 ASD (or the function assigned to this terminal). The Voltage/Current output selection is
performed at F681. This output terminal may be programmed to provide an output that is a function of
any of the functions listed in the Q9 ASD Installation and Operation Manual.
P24 — +24 VDC @ 200 mA power supply for customer use.
PP — The function of output PP is to provide a 10 VDC/10 mADC output that may be divided using a
potentiometer. The tapped voltage is applied to the RR input to provide manual control of the RR
programmed function.
FP — The default function assigned to this open collector output terminal is Output Frequency. This
output terminal produces an output pulse train that has a frequency which is proportional to the
magnitude of the Output Frequency of the ASD (or the function assigned to this terminal). This output
terminal may be programmed to provide an output pulse train of a frequency that is a function of the
user-selected function in the Q9 ASD Installation and Operation Manual.
CC — Control Common (Do Not connect to Earth Gnd).