Operating mode Fast / Standard
You can use this parameter to determine the operating mode for the module.
● Fast mode; easy integration time with less frequency suppression (minimal integration
time 2.5 ms)
● Standard mode; triple integration time with higher frequency suppression (minimal
integration time 7.5 ms)
Measuring range adjustment
With this parameter, you disable or enable the measuring range adjustment function.
Measuring range adjustment high limit
With this parameter, you specify the high limit of the measuring range.
Measuring range adjustment low limit
With this parameter, you specify the low limit of the measuring range.
Scaled high nominal range limit
With this parameter, you set the desired display value (in REAL) for the high nominal range
limit of the measuring range.
Scaled low nominal range limit
With this parameter, you set the desired display value (in REAL) for the low nominal range
limit of the measuring range.
Analog Input Module AI 8xU/I HF (6ES7531-7NF00-0AB0)
Manual, 09/2016, A5E36649087-AB
Parameters/address space
4.3 Declaration of parameters
31