Environmental; Battery; Calendar/Clock - GE IC754CSF15CTD Hardware User's Manual

15" quickpanel* view & quickpanel control
Table of Contents

Advertisement

Environmental

Operating Temperature*
Operating Humidity
Storage Temperature*
Storage Humidity
NEMA Rating
Operational Vibration
Operational Shock
*
Rated temperature limits refer to the ambient air temperature immediately
surrounding (less than 3" or 7.6 cm) the QuickPanel. Additional provisions for
remaining within the stated limits must be considered where additional, external
thermal loads are imposed on the QuickPanel. These could include large heat
producing motor drives, or power supplies in the same cabinet or in outdoor
applications involving direct sun exposure.

Battery

Type
Approximate life

Calendar/Clock

Resolution
Accuracy
Retention
GFK-2402D
32°F to 122°F
(0°C to 50°C)
10% to 85% RH (non-condensing) at less than
50°C; maximum 50% RH at greater than 50°C
-4 to 140°F
-20 to 60°C
10% to 85% RH (non-condensing) at less than
50°C; maximum 50% RH at greater than 50°C
4 and 4x (NEMA 4 is approximately equivalent to
IP66; visit www.nema.org)
IEC 60068-2-6
10–57Hz, 0.012" peak to peak displacement
57–500Hz, 1.0g acceleration
IEC 60068-2-27
15g, 11ms (sine wave)
Panasonic BR2032 (3V, 190mAh, lithium)
5 years
1 second
±2 to 3 minutes per month
Life of battery
Appendix A Design Specifications