LG SV-iC5 User Manual page 10

Ac inverter drive speed controller
Hide thumbs Also See for SV-iC5:
Table of Contents

Advertisement

◆ Common area
Address
Parameter
0x0004 Parameter Read/Write enable
Frequency Reference
0x0005
0x0006 Operatin command (Option)
0x0007
Accel time
0x0008
Decel time
0x0009
Output current
0x000A
Output frequency
0x000B
Output voltage
0x000C
DC Link Voltage
0x000D
Output power
0x000E
Status of Inverter
0x000F
Trip information
Scale
Unit R/W
R/W
0.01
Hz
R/W
R/W
0.1
sec R/W
0.1
sec R/W
0.1
A
R
0.01
Hz
R
0.1
V
R
0.1
V
R
0.1
kW
R
R
R
8
MODBUS-RTU user manual
Description
0: Parameter Lock
1: Parameter Read/Write Enable
Starting freq ~ Max freq
BIT 0 : Stop (S)
BIT 1 : Forward Run (F)
BIT 2 : Reverse Run (R)
BIT 3 : Fault reset (0->1)
BIT 4 : Emergency stop
BIT 5 : Not used
See function table
See function table
See function table
See function table
See function table
See function table
See function table
BIT 0 : Stop
BIT 1 : Forward running
BIT 2 : Reverse running
BIT 3 : Fault (Trip)
BIT 4 : Accelerating
BIT 5 : Decelerating
BIT 6 : Speed arrival
BIT 7 : DC Braking
BIT 8 : Stopping
Bit 9 : Not Used
BIT 10 : Brake Open
(I55: 3 or 4)
BIT13: REM. R/S
BIT14: REM. Freq.
BIT 0 : OCT
BIT 1 : OV
BIT 2 : EXT-A
BIT 3 : EST
BIT 4 : Option
BIT 5 : GF(Ground Fault)
BIT 6 : OH(Inverter overheat)
BIT 7 : ETH(Motor overheat)
BIT 8 : OLT(Overload trip)
BIT 9 : HW-Diag
BIT10: EXT-B
BIT11: EEP

Hide quick links: