Technical specifications
Parallel connection of two outputs
For logic operations
For performance increase
For redundant activation of a load
Switching frequency
with resistive load, max.
with inductive load, max.
with lamp load, max.
Total current of the outputs
Current per channel, max.
Current per group, max.
Current per power supply, max.
for technological functions
Cable length
shielded, max.
unshielded, max.
Analog inputs
Number of analog inputs
permissible input voltage for voltage input (de-
struction limit), max.
permissible input current for current input (destruc-
tion limit), max.
Cycle time (all channels), min.
Technical unit for temperature measurement, can
be set
Input ranges (rated values), voltages
0 to +10 V
Input resistance (0 to 10 V)
1 V to 5 V
Input resistance (1 V to 5 V)
-10 V to +10 V
Input resistance (-10 V to +10 V)
-5 to +5 V
Input resistance (-5 to +5 V)
134
Current per channel, max.
for current measurement
for voltage measurement
for resistance/resistance-type thermometer
measurement
6ES7512-1CK00-0AB0
Yes; For technological functions: No
No
Yes; For technological functions: No
100 kHz; with high-speed output, 10 kHz with
standard output
0.5 Hz; acc. to IEC 60947-5-1, DC13; note derat-
ing curve
10 Hz
0.5 A; see additional description in the manual
8 A; see additional description in the manual
4 A; two power supplies per group, current per
power supply max. 4 A, see additional description
in the manual
0.5 A; see additional description in the manual
1000 m; 600 m for technological functions; de-
pendent on output frequency, load and cable
quality; max. 50 m at 100 kHz
600 m; For technological functions: No
5; 4x for U/I, 1x for R/RTD
4; max.
4; max.
1
28.8 V
40 mA
1 ms; dependent on the configured interference
frequency suppression, for details see Conver-
sion method in the manual
Yes; °C / °F / K
Yes; physical measuring range: ±10 V
100 kΩ
Yes; physical measuring range: ±10 V
100 kΩ
Yes
100 kΩ
Yes; physical measuring range: ±10 V
100 kΩ
CPU 1512C-1 PN (6ES7512-1CK00-0AB0)
Manual, 09/2016, A5E35306440-AB

Hide quick links: