GE Masoneilan SVI II ESD Installation And Maintenance Manual page 96

Smart valve interface with sil3 emergency shutdown pst controller
Table of Contents

Advertisement

Proceed with the following steps:
1. Press NEXT
2. Field device has more status available
3. Press NEXT
4. Ignore next 50 occurrences of status?
5. Press YES
6. Change to MANual mode
7. Scroll to line 6 "EXAMINE," press
8. Scroll down to line 5 read status.
9. Read message.
10. Press OK.
11. Repeat OK to read all messages until the display returns to "read status".
12. Scroll down to line 6 clear status, press
13. If clear fault codes not completed appears, press OK and read the message (Position
Error, for example) or go to the troubleshooting guide.
14. Correct the problem (Is the air supply on?), and then go to clear status until Clear Fault
codes Completed appears.
15. Press OK.