Mitsubishi Electric PMFY-P20VBM-E1 Technical & Service Manual page 3

Ceiling cassettes pmfy series
Hide thumbs Also See for PMFY-P20VBM-E1:
Table of Contents

Advertisement

[1] Cautions for service
· After recovering all the refrigerant in the unit, proceed to working.
· Do not release refrigerant in the air.
· After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
[2] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder
· R407C cylinder are available on the market has a syphon pipe.
· Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
Gravimeter
(2) Recharge in refrigerant leakage case
· After recovering the all refrigerant in the unit, proceed to working.
· Do not release the refrigerant in the air.
· After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
[3] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No.
Tool name
Gauge manifold
1
Charge hose
2
Electronic scale
3
Gas leak detector
4
Adapter for reverse flow check
5
Refrigerant charge base
6
Refrigerant cylinder
7
Refrigerant recovery equipment
8
Specifications
· Only for R407C
· Use the existing fitting SPECIFICATIONS. (UNF7/16)
· Use high-tension side pressure of 3.43MPa·G or over.
· Use the existing fitting SPECIFICATIONS. (UNF7/16)
· Use pressure performance of 5.10MPa·G or over.
· Use the detector for R134a or R407C.
· Attach on vacuum pump.
· For R407C
· Top of cylinder (Brown)
· Cylinder with syphon
3 3
Unit