Appendix A. Configuring Advanced User Parameters
Ethernet Redundancy Parameters (task q)
rdipckival
Interval between additional checks for Redundant IP address in
use (in milliseconds).
When activating the Redundant IP address, the ETM sends a
burst of three ARP requests at 20ms intervals.
If the ETM receives an SRP response, it delays for the interval
specified by rdipckival, plus an additional 20ms. After the
specified interval has passed, the ETM tries again, repeating the
cycle of three ARP requests. The ETM repeats the request cycle
after each SRP response; however the delay interval after a
response is received doubles each cycle, to a maximum of 2.0
seconds.
rdiparpivl
Interval between gratuitous ARP requests sent by the backup
unit on behalf of the new active unit (in ms).
rdipnumarp Number of gratuitous ARP requests to send out during
Redundant IP activation process.
rdiparplog
Number of gratuitous ARP requests to send by backup unit
before a "Redundant IP not available" exception is logged. (The
backup unit continues to send ARP requests as long as it
receives network packets addressed to the Redundant IP
Address.)
FTP Parameters (task t)
tpassword
Password for login for FTP access.
UDP Parameters (task u)
SRTP Parameters (task v)
SRTP inactivity timeout (in seconds). Amount of time to wait
vconn_tout
2
before cleaning up an abandoned privileged SRTP server
6
connection. Any non-zero value is rounded up to the next
multiple of 5 seconds. See "SRTP Inactivity Timeout" in Chapter
1 for details.
All privileged connections initially use the SRTP inactivity
timeout specified by this AUP parameter. Inactivity timeouts
established by an SRTP Client on an individual connection will
override any AUP specified inactivity timeout on that
connection.
0 = SRTP Inactivity Timeout disabled.
260
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
Default
Range
100
1 – 1000ms
(0064H)
100
1 – 1000ms
(0064H)
1
1 – 25
(0001H)
5
1 – 25
(0005H)
Default
Range
"system"
0 to 8 characters
None
None
Default
Range
30
0 – 420 seconds
seconds
GFK-2224Q