General
NOTICE
Component cooling
Provisions for component cooling must be made at the installation site. Power loss data is
given in the technical specifications.
Assignment of du/dt filter compact plus Voltage Peak Limiter and Power Module
Table 2- 1
Assignment of du/dt filter compact plus Voltage Peak Limiter and Power Module
Power Module
6SL3310-1PE33-0AA0
6SL3310-1PE33-7AA0
NOTICE
Maintain ventilation clearances
The 100 mm clearances above and below the components must be observed.
The du/dt filters compact plus Voltage Peak Limiter may only be mounted in a vertical
position, to enable cooling air to flow through the heat sink on the Voltage Peak Limiter
from the bottom to the top.
Note
Cable lengths
The motor cables between the Power Module and the du/dt filter compact, as well as the
cables to the DC link, must be kept as short as possible (max. 5 m).
NOTICE
Use only approved du/dt filters
If du/dt filters compact plus Voltage Peak Limiters are used that SIEMENS has not
approved for SINAMICS, these du/dt filters may be damaged.
Hot surfaces
The surface temperature of the du/dt filters may exceed 80 °C.
12
Rated power of the Power Module
Line voltage 380 – 480 V 3 AC
CAUTION
160 kW
200 kW
suitable du/dt filter compact plus Voltage
Peak Limiter
6SL3000-2DE35-0EA0
6SL3000-2DE35-0EA0
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 11/2013, A5E32847614B AA