Troubleshooting; 9000 Series Basic Troubleshooting; Service Walk Test Shows Extra Points; Figure 20: Service Walk Test Flowchart - Bosch D8125 Operation And Installation Manual

Zone expansion module
Hide thumbs Also See for D8125:
Table of Contents

Advertisement

4.0

Troubleshooting

4.1

9000 Series Basic Troubleshooting

4. 1 . 1

Service Walk Test Shows Extra Points

The Service Walk Test differs from the standard Walk Test in that
POPITs whose switches are set for a point number not programmed in
the panel appear in the test.
The Service Walk Test allows a user to walk test all 246 points (75 in the
D7412 and D7212 panels) from a panel-wide Command Center
regardless of the Point Index type. Service Walk Tests may also be
initiated by account-wide or area-wide Command Centers but will only
test those points that fall within the scope of the Command Center that
initiated the function. The Service Walk Test will not test points in areas
that are currently armed.
Fire and other 24-hour points do not transmit reports during
Service Walk Test!
CAUTION
The steps below outline a simple Service Walk Test procedure. Figure 20
shows all the Service Walk Test options.
1.
Choose a command center with panel wide scope to
conduct the test. Be certain the display shows the idle
disarmed text.
2.
Enter a valid service passcode and press [ESC] to enter
the Function List. Press [NEXT] repeatedly until you
reach the SERVICE WALK ? prompt. Press [ENT].
3.
The display shows ### PTS TO TEST. Test the first
detection device.
4.
As you fault the detection devices, the Command Center
emits a brief tone and displays the point text of the point
tested for 60 seconds. After 60 seconds, the display
returns to the points to test message.
IDLE TEXT
Extra Points display default text: If you incorrectly set the
switches on a POPIT to a point number that is not in
your program for the panel, the default text for that
point number (PT ###) displays when you fault the
point. The Program Record Sheet shows the default text
for all points.
Faulting the point a second time produces the tone and
displays the point text, but does not reduce the PTS TO
TEST count.
© 2004 Bosch Security Systems, Inc.
ESC
D8125 Operation and Installation Guide
Page 39
Troubleshooting
SERVICE WALK ?
ENT
246 PTS TO TEST
Test a device
POINT TEXT
(Text displays 60 seconds)
245 PTS TO TEST
Test a device
POINT TEXT
(Text displays 60 seconds)
244 PTS TO TEST
Test a device
POINT TEXT
1 PTS TO TEST
Test a device
0 PTS TO TEST
VIEW UNTESTED ?
ENT
# PTS UNTESTED
NEXT
POINT TEXT

Figure 20: Service Walk Test Flowchart

D8125
ESC
ESC
ESC
74-04247-000-N

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents