10.4 Modbus RTU commands

FC3 Read Holding Register
With this command, any number (1-127) of holding registers can be read out. The start register,
from which the readout should start, and the number of registers are transmitted.
Request:
Parameter
Function Code
Start Address
Number of Registers
Response:
Parameter
Function Code
88
Type
Note
DWord
Primary Variable in Byte Order BACD (Middle Endian)
DWord
Secondary Variable in Byte Order BACD (Middle En-
dian)
DWord
Third Variable in Byte Order BACD (Middle Endian)
DWord
Quarternary Variable in Byte Order BACD (Middle En-
dian)
Measurement Unit
Degree Celsius
Degree Fahrenheit
US Gallon
Liters
Imperial Gallons
Cubic Meters
Feet
Meters
Barrels
Inches
Centimeters
Millimeters
Cubic Yards
Cubic Feet
Cubic Inches
Length
1 Byte
2 Bytes
2 Bytes
Length
1 Byte
SITRANS LG270 - Operating Instructions
Code/Data
0x03
0x0000 to 0xFFFF
1 to 127 (0x7D)
Code/Data
0x03
PBD-51041066