4 PROGRAMMING
SEE PREVIOUS PAGE
4
SEE NEXT PAGE
4-16
Courtesy of NationalSwitchgear.com
SEE PREVIOUS PAGE
| MECHANICAL JAM
|
MECHANICAL JAM
FUNCTION: OFF
MECHANICAL JAM
PICKUP ≥ 2.0 x FLC
MECHANICAL JAM
MESSAGE
DELAY: 2 s
MESSAGE
INHIBIT ON START
FOR: UNLIMITED s
| UNDERCURRENT
|
UNDERCURRENT
FUNCTION: OFF
UNDERCURRENT
PICKUP ≤ 50% FLC
MESSAGE
MESSAGE
UNDERCURRENT
DELAY: 2 s
| UNBALANCE
|
PHASE UNBALANCE
TRIP: ON
PHASE UNBALANCE
TRIP PICKUP ≥ 20 %
PHASE UNBALANCE
TRIP DELAY: 2 s
MESSAGE
PHASE UNBALANCE
MESSAGE
ALARM: ON
PHASE UNBALANCE
ALARM PICKUP ≤ 5 %
| HOT MOTOR
|
THERMAL CAPACITY
USED ALARM ≥ OFF %
MESSAGE
MESSAGE
SEE NEXT PAGE
239 Motor Protection Relay
4 PROGRAMMING
Range: OFF, TRIP, ALARM,
AUXILIARY, TRIP&AUX
Range: 0.1 to 10.0
Step 0.1 x FLC
Range: 0 to 250; Step: 1 s.
Range: 0 to 6000, UNLIMITED
Step: 1 s
Range: OFF, ALARM, AUXILIARY,
TRIP, ALARM & AUX, TRIP & AUX
Range: 5 to 100; Step: 1%
Range: 0 to 250; Step: 1 s.
Range: ON, OFF
Range: 5 to 100; Step: 1%
Range: 0 to 60; Step: 1 s
Range: ON, OFF
Range: 5 to 100
Step: 1%
Range: 0 to 100; Step: 1%
GE Multilin