CHAPTER 5: SETTINGS

5.12.4 Pulse Output

 PULSE
OUTPUT
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
period. The average value of the buffer is calculated and stored as the new demand value
every minute. Demand for real and reactive power is only positive quantities (+kW and
+kvar).
Demand
where: N = programmed demand period in minutes
n = time in minutes.
160
140
120
100
80
60
40
20
0
t=0
t+10
FIGURE 5–19: Rolling Demand (15 Minute Window)

PATH: SETTINGS
S11 MONITORING
[]
POS kWh PULSE OUTPUT
RELAY: Off
POS kWh PULSE OUTPUT
MESSAGE
INTERVAL: 1 kWh
POS kvarh PULSE OUT
MESSAGE
RELAY: Off
POS kvarh PULSE OUT
MESSAGE
INTERVAL: 1 kvarh
NEG kvarh PULSE OUT
MESSAGE
RELAY: Off
NEG kvarh PULSE OUT
MESSAGE
INTERVAL: 1 kvarh
RUNNING TIME PULSE
MESSAGE
RELAY: Off
RUNNING TIME PULSE
MESSAGE
INTERVAL: 0 s
N
1
Average
---
=
N
N
n
1
=
t+20
t+30
t+40
t+50
t+60
TIME

PULSE OUTPUT
(EQ 5.12)
t+70
t+80
t+90 t+100
808717A1.CDR
Range: Off, Alarm, Auxiliary2,
Auxiliary3
Range: 1 to 50000 kWh in steps of 1
Range: Off, Alarm, Auxiliary2,
Auxiliary3
Range: 1 to 50000 kvarh in steps of 1
Range: Off, Alarm, Auxiliary2,
Auxiliary3
Range: 1 to 50000 kvarh in steps of 1
Range: Off, Alarm, Auxiliary2,
Auxiliary3
Range: 1 to 50000 s in steps of 1
5–91