Siemens SITRANS LR560 Operating Instructions Manual

Siemens SITRANS LR560 Operating Instructions Manual

Radar transmitters
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

Radar Transmitters
SITRANS LR560 (mA/HART)
Operating Instructions
Edition
03/2016

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS LR560

  • Page 1 Radar Transmitters SITRANS LR560 (mA/HART) Operating Instructions Edition 03/2016...
  • Page 2 Siemens AG Industry Sector 76181 Karlsruhe Deutschland • For a selection of Siemens level measurement manuals, go to: www. siemens.com/processautomation. Select Products & Systems, then under Process Level Measurement. Instrumentation, select Manual archives can be found on the Support page by product family.
  • Page 3: Table Of Contents

    Safety Notes ........................3 Safety marking symbols ........................3 Industry Canada ............................3 FCC Conformity ............................4 CE Electromagnetic Compatibility (EMC) Conformity ..............4 R&TTE Compliance (Europe) ......................5 SITRANS LR560 Overview ....................7 Programming ............................7 Local Display Interface (LDI) ......................8 Versions ..............................8 Applications ............................8 Approvals and Certificates .........................8 Specifications ........................9...
  • Page 4 The LCD Display ........................32 Handheld Programmer ......................33 Programming SITRANS LR560 ....................34 Quick Start Wizard via the LDI push buttons ................37 Quick Start Wizard via the handheld programmer ..............37 Requesting an Echo Profile ......................40 Level application example ........................42 Operating via SIMATIC PDM ..................43 Functions in SIMATIC PDM ......................43...
  • Page 5 Rate............................. 89 Fail-safe ..........................91 Analog Output Scaling ....................92 Signal Processing......................95 TVT setup........................100 TVT shaper........................101 Measured Values ......................102 Diagnostics ..........................103 Fault Reset ........................103 Echo Profile........................103 Trend ..........................104 Peak Values ........................104 Electronics Temperature ....................
  • Page 6 Loss of Echo (LOE) ........................141 Temperature derating curve ......................142 Loop power ............................143 Typical Connection Drawing ....................143 Allowable operating area of SITRANS LR560 ..............144 Startup Behavior ........................144 Appendix E: HART Communications .................145 SIMATIC PDM ...........................145 HART Electronic Device Description (EDD) ................145 HART Communicator 375 Menu Structure ................146...
  • Page 7: Introduction

    • Please follow the installation and operating procedures for a quick, trouble-free installation and to ensure the maximum accuracy and reliability of your SITRANS LR560. • This manual applies to the SITRANS LR560 (mA/HART) only. For other Siemens level measurement manuals, go to: www.siemens.com/level and look under Level Measurement.
  • Page 8: Abbreviations And Identifications

    Additional Support Please contact your local Siemens representative and offices if you have additional questions about the device. Find your contact partner at Your personal contact. Abbreviations and Identifications Short Long Form Description Units form CE / FM / Conformité Européene / Factory Mutual /...
  • Page 9: Safety Notes

    Industry Canada The SITRANSLR560 complies with Industry Canada standard RSS211 (March 2015). a. The installation of the SITRANS LR560 shall be done by trained installers, in strict compliance with the manufacturer’s instructions. b. The use of this device is on a "no-interference, no-protection" basis. That is, the user shall accept operations of high-powered radar in the same frequency band which may interfere with or damage this device.
  • Page 10: Fcc Conformity

    US Installations only: Federal Communications Commission (FCC) rules WARNING: Changes or modifications not expressly approved by Siemens could void the user’s authority to operate the equipment. Notes: • This device has been tested and found to comply with the limits Class B digital device part 15 of the FCC Rules.
  • Page 11: R&Tte Compliance (Europe)

    R&TTE Compliance (Europe) Hereby, Siemens, declares that the SITRANS LR560 is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC. The LR560 complies with EN 302 372 for use in closed storage vessels, when installed according to the installation requirements of EN 302 372, and may be used in all EU countries.
  • Page 12 Notes Page 6 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 13: Sitrans Lr560 Overview

    1,000,000 applications worldwide (ultrasonic and radar). Programming SITRANS LR560 is very easy to install and configure via an optional graphical local display interface. You can modify the built-in parameters either locally via the push buttons or using the infra-red handheld programmer, or from a remote location using one of the following options: •...
  • Page 14: Local Display Interface (Ldi)

    • cement powder, plastic powder/pellets, grain, flour, coal, and other applications Approvals and Certificates SITRANS LR560 is available with General Purpose approval, or for Hazardous areas. For Approvals details, see on page 12. Application...
  • Page 15: Specifications

    Specifications Siemens makes every attempt to ensure the accuracy of these specifications but Note: reserves the right to change them at any time. Power Nominal 24 V DC with Loop For other configurations, see the chart under max. 550 Ohm loop resis-...
  • Page 16: Interface

    ≤ 1500 m (4921 ft) • Protocol HART , Version 6.0 Configuration • remote Siemens SIMATIC PDM or AMS Device Manager (PC) or FDT such as PACTWARE • local Siemens infrared handheld programmer, local control buttons, or HART handheld communicator Optional removeable...
  • Page 17: Environmental

    (–40 to +392 °F) (–40 to +392 °F) (–40 to +248 °F) Maximum and minimum temperatures are dependent on the process connection, antenna and O-ring materials. Use of the Easy Aimer limits maximum temperature. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 11...
  • Page 18: Approvals

    • To estimate the lifetime expectancy, check the nameplate on the back for the serial number. The first six numbers show the production date (mmddyy), for example, serial number 032608101V. Siemens Infrared IS (Intrinsically Safe) Hand Programmer for hazardous and all other locations (battery is non-replaceable) • approval FM/CSA Class I, II, III, Div.
  • Page 19: Dimensions

    Dimensions SITRANS LR560 with stainless steel universal flat-faced flange Universal flat-faced flange Refer to on page 18 for bolt hole patterns and Note: dimensions. lid lock device label cable gland 176 mm grounding (6.93") purge inlet pressure/ temperature process related...
  • Page 20 SITRANS LR560 with stainless steel universal stamped flange Universal stamped flange Note: Refer to on page 19 for bolt hole patterns and dimensions. lid lock cable gland 176 mm grounding (6.93") purge inlet 6 mm process (0.24") connection: stamped flange 110 mm (4.33")
  • Page 21 SITRANS LR560 with 3" Aimer Flange Universal flat-faced flange Refer to on page 18 for bolt hole patterns and Note: dimensions. lid lock device cable gland label grounding 166.1 mm (6.54") purge inlet pressure/ temperature process related connection: information aimer flange 23.3 mm...
  • Page 22 SITRANS LR560 with 4 and 6" Aimer Flange Universal flat-faced flange Refer to on page 18 for bolt hole patterns and Note: dimensions. lid lock cable gland device label grounding 166.1 mm purge (6.54") inlet pressure/ temperature related information process...
  • Page 23 10/01/04 Date of Pressure Test (Year/Month/Day) PROCESS SERIES 25785 Pressure Tag Family Series WETTED NON-METALLIC Sensor Lens Material WETTED METALLICS 304L Process Connection Material(s) WETTED SEALS FKM / VQM Seal Material(s) A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 17...
  • Page 24: Universal Flat-Faced Flange

    285 mm 9.65 mm 242 mm 240 mm 11.5 mm (6") (11.22") (0.38") (9.53") (9.45") (0.45") Universal flanges mate with EN 1092-1 (PN16)/ASME B16.5 (150 lb)/JIS 2220 (10K) bolt hole pattern. Page 18 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 25: Universal Stamped Flange

    (4") (9.21") (7.5") (6.89") (0.37") 150 mm 290 mm 242 mm 240 mm 11.5 mm (6") (11.42") (5.59") (9.45") (0.45") Material: 304 stainless steel, gauge #12, finish to be RoHS compliant. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 19...
  • Page 26 Notes Page 20 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 27: Installation

    • Installation shall only be performed by qualified personnel and in accordance with local governing regulations. • SITRANS LR560 is to be used only in the manner outlined in this manual, otherwise protection provided by the device may be impaired.
  • Page 28: Mounting Location

    Emission cone • Keep emission cone free of interference from ladders, pipes, I-beams or filling streams. • Avoid central locations on tall, narrow vessels. Page 22 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 29 –40 to +200 °C (–40 to +392 °F) depending on the version Sun Shield The LR560 display can be protected by an optional sun shield if the instrument will be mounted in direct sunlight. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 23...
  • Page 30: Aimer Adjustment

    C spanner, until the LR560 drops down slightly. The enclosure can then be turned freely. Direct SITRANS LR560 so the antenna is pointed at an angle perpendicular to the material surface, if possible. When the desired position is reached, re-tighten the locking ring using the C spanner, and tighten set screws.
  • Page 31: Air Purging System

    • It is the customer’s responsibility to ensure that any vacuum or pressure in the mea- sured vessel is maintained, considering the hole that passes through the process connection and SITRANS LR560 antenna system. Air Consumption (Flow rate versus applied pressure) Air Pressure (psi) Approx.
  • Page 32 The optional display can be rotated as required, to one of 4 positions, 90 degrees apart. Connecting SITRANS LR560 (See on page 27.) Copy It can also be used to transfer parameters from one device to another. (See Parameters to Display on page 85.) Page 26 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 33: Wiring

    70 mm (2.75") from 3) ¼ turn the end of the cable, and thread the wires through the gland If cable is routed through conduit, use only approved suitable-size hubs for waterproof applications. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 27...
  • Page 34: Connecting Hart

    Depending on the system design, the power supply may be separate from the PLC, or integral to it. HART resistance (total loop resistance, that is, cable resistance plus 250 Ohm [resistor]) must be less than 550 Ohm for the device to function properly. Page 28 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 35: Wiring Setups For Hazardous Area Installations

    Sensors and Communication Ltd Siemens SAS . and Haguenau, France by FM/CSA Class 1, Div 2 connection drawing number A5E02795836 can be downloaded from the product page of our website at: www.siemens.com/sitransLR560. Temperature De-Rating For power demands, see on page 143.
  • Page 36: Instructions Specific To Hazardous Area Installations

    ‘e’ or flameproof ‘d’ . • The supply to the equipment shall be rated for a prospective short-circuit current of not more than 10 kA and shall be protected by a suitably-rated fuse. Page 30 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 37: Local Operation

    • To toggle between Measurement and Program Mode using the handheld programmer, press Mode Power up the device. A transition screen showing first the Siemens logo and then the current firmware revision is displayed while the first measurement is being processed.
  • Page 38: The Lcd Display

    Edit view parameter number parameter name parameter value/selection Press UP or DOWN arrow to switch Key functions in Measurement mode In response to a key press request. For details, see page 33. Page 32 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 39: Handheld Programmer

    LCD toggles between % or linear units RIGHT arrow Opens the top level menu. opens PROGRAM mode. UP or DOWN arrow LCD displays primary or secondary value. toggles between PV and SV. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 33...
  • Page 40: Programming Sitrans Lr560

    • While the device is in PROGRAM mode, the output remains active and continues to respond to changes in the device. • SITRANS LR560 automatically returns to Measurement mode after a period of Menu Timeout 2.1.9. inactivity in PROGRAM mode ( on page 87).
  • Page 41 Edit mode. The current selection is highlighted. Scroll to a new selection. Press RIGHT arrow to accept it. The LCD returns to parameter view and displays the new selection. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 35...
  • Page 42 Secondary Value to be displayed in secondary region of LCD. Plus or Numeric Changes the sign of the entered value. minus sign editing Numeric Numeral Enters the corresponding character. editing Page 36 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 43: Quick Start Wizard Via The Ldi Push Buttons

    1.1. Quick Start Wizard Point the programmer at the display from a maximum distance of 300 mm (1 ft), then press RIGHT arrow to activate PROGRAM mode and open menu level 1. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 37...
  • Page 44 10.0 m/min (32.8 ft/min) 0.75 It may be necessary to reduce this further for FAST applications Use a setting just faster than the maximum vessel filling or vessel emptying rate (whichever is greater). Page 38 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 45 Distance from High Calibration Point to material surface DISTANCE(3) Distance from Sensor Reference Point to material surface sensor reference point (flange face: High Calibration Dimensions Point page 13) distance space level Calibration Point A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 39...
  • Page 46: Requesting An Echo Profile

    DOWN arrow to scroll to an icon. When an icon is highlighted, that feature becomes active. • To move a cross-hair, press RIGHT arrow to increase the value, LEFT arrow to decrease. Page 40 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 47 . Press LEFT arrow to Zoom out. • To update the profile, select Measure and press RIGHT arrow • To return to the previous menu, select Exit then press RIGHT arrow A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 41...
  • Page 48: Level Application Example

    Resets Fill Rate/ Empty Rate to 0.1 m/minute. Units Sensor measurement units. Operation LEVEL (1) Material level referenced from Low Cal. Point. Low Calibration Point 15.5 Process empty level. High Calibration Point Process full level. Page 42 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 49: Operating Via Simatic Pdm

    Operating via SIMATIC PDM SIMATIC PDM is a software package used to commission and maintain SITRANS LR560 and other process devices. Please consult the operating instructions or online help for details on using SIMATIC PDM. (You can find more information at www.siemens.com/simatic-pdm.)
  • Page 50: Configuring A New Device

    To install a new EDD • Go to www.siemens.com/LR560 > Support > Software Downloads to download the most up-to-date EDD from the product page of our website. • Save the files to your computer and extract the zipped file to an easily accessed location.
  • Page 51 Click on Read Data from Device to upload Quick Start parameter settings from the device to the PC/PG and ensure PDM is synchronized with the device. Click on NEXT to accept the default values. (Description, Message, and Installation Date fields can be left blank.) A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 45...
  • Page 52 Select the application type (steel or concrete silo construction), operation type (level, space, or distance) and then click on NEXT. Step 3 – Ranges Note: Selecting SLOW Response Rate changes setting for Average Amount (2.7.5.3.) to 0.9. Set the parameters, and click on NEXT. Page 46 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 53: Changing Parameter Settings Using Simatic Pdm

    Many parameters are accessed via the 4-level menu in PDM. See pull-down menus below for the others. Launch SIMATIC PDM, connect to SITRANS LR560, and upload data from the device. Adjust parameter values in the parameter value field and then press Enter. The status fields read Changed.
  • Page 54: Parameters Accessed Via Pull-Down Menus

    Parameters accessed via pull-down menus You have access to a number of functions via pull-down menus from the menu bar under Device or View. For a complete list, see Pull-down menus below pull-down menus Page 48 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 55 50 View Saved Echo Profiles • on page 50 Echo Setup • on page 54 TVT Shaper • on page 51 Auto False Echo Suppression • on page 52 A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 49...
  • Page 56 • Click on the tab View Saved Echo Profiles to view the stored profiles View Saved Echo Profiles To view a saved profile, click on the tab View Saved Echo Profiles. Page 50 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 57 Note: If the TVT Shaper tab is closed without transferring new values to the device, the new values will appear in the PDM list even though they have not been transferred to the device. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 51...
  • Page 58 Determine Auto False Echo Suppression Range. Measure the actual distance from the sensor reference point to the material surface using a rope or tape measure. Subtract 0.5 m (20") from this distance, and use the resulting value. Page 52 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 59 Before Auto False Echo Suppression default TVT material level Hover false echo Level echo marker After Auto False Echo Suppression material level Auto False Echo Suppression Range default learned TVT echo false echo marker A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 53...
  • Page 60 Open the menu Device – Maintenance, and click on the Remaining Device/Sensor Lifetime tab. Modify desired values, and if desired, set reminders for either or both of Reminder 1 (Required)/Reminder 2 (Demanded) Page 54 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 61 When you are ready to end simulation, select End and click on OK to return the device to the actual output value. Configuration Flag Reset To reset the configuration flag to zero, open the menu Device – Configuration Flag Reset and perform a reset. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 55...
  • Page 62: Hart Communication

    To compare outputs in real time open the menu View – Process Variables and click on Overview to see reading (level, space, distance); analog output; device status; and current electronics temperature. Page 56 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 63 PV trend can be monitored. Primary Value (PV) (PV), and can be set to either Level, Space, or Distance. The mA Output follows Primary Value Select Analog Output on page 55. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 57...
  • Page 64: Security

    Open a project, double-click on the device icon, and in the User window select Specialist. Open the menu Options – Settings and click on the Password tab. Enter a new password and re-enter it in the Confirmation window. Click on OK. Page 58 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 65: Operating Via Fdt (Field Device Tool)

    Product Information/Automation Technology/Sensor systems/Process Instrumentation/Software & Communications. The Instrument EDD The SITRANS LR560 HART EDD for SITRANS DTM can be downloaded from the product page of our website. Go to www.siemens.com/sitransLR560 under Support and click on Software Downloads. Configuring a new device via FDT The full process to configure a field device via FDT is outlined in an application guide which can be downloaded from the product page of our website.
  • Page 66 Notes Page 60 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 67: Operating Via Ams Device Manager

    76 for a chart using AMS Device Manager on page 67 for more details. AMS Device Manager Features of The graphic interface in SITRANS LR560 makes monitoring and adjustments easy. Feature page Function Quick Start Device configuration for simple applications...
  • Page 68: Configuring A New Device

    Master Reset • Navigate to Configure/Setup > Operation • In the General field, click on Master Reset and accept the option Factory Defaults. Page 62 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 69: Pull-Down Menu Access

    In the General field, click on Master Reset and perform a reset to Factory Defaults. Open the pull-down menu Actions – Scan Device to synchronize parameters (upload parameters from the device to AMS). Configure the device via the Quick Start wizard. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 63...
  • Page 70: Quick Start Wizard Via Ams Device Manager

    • Selecting CONCRETE changes the setting for Position Detect (2.7.3.3.) to Rising Edge and for Algorithm (2.7.3.1.) to ALF. Click on Step 2. Select the application type (Steel or Concrete) and the operation (Level, Space, or Distance Page 64 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 71 Click on Step 3. Change units if desired (in meters by default). Set High and Low Calibration points. Set Response Rate. Click on Apply. Sensor Mode (2.2.2.) For details see on page 140. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 65...
  • Page 72 Step 4 – Summary Check parameter settings, and click on Cancel to abort, or Apply to transfer values to the device. Page 66 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 73 55) Master Reset • Master Reset (see on page 56) Simulation/Test Self Test • Self Test (see on page 55) Loop Test • Loop Test (see on page 55) A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 67...
  • Page 74 Sensor Offset Rate [see Rate (2.4.) on page 89] • Response Rate • Fill rate/minute • Empty rate/minute Fail-safe [see Fail-safe (2.5.) on page 91] • Material level • Timer • Level Page 68 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 75 Analog Output Scaling [see Analog Output Scaling (2.6.) on page 92] • Current Output Function • Start of scale (=4mA) • Full Scale (=20mA) • Control Range (lower limit) • Control Range (upper limit) Signal Processing A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 69...
  • Page 76 Echo Lock Window Echo Quality • Confidence • Echo Strength Filtering • Narrow Echo Filter • Reform Echo Shaper Mode Modify the TVT to screen out false echoes [see on page 101]. Page 70 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 77: Maintenance And Diagnostics

    Reminder 1 before Lifetime (Required) • Reminder 2 before Lifetime (Demanded) a) Open the window Remaining Device Lifetime. b) After modifying values/units as required, click on Apply to accept the change. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 71...
  • Page 78 After modifying values/units as required, click on Apply to accept the change. c) Click on Sensor Replaced to reset Remaining Lifetime to 0 hours. d) Click on Snooze for 1 Year to add a year to the Total Expected Sensor Life. Page 72 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 79: Communication

    See Remote Lockout on page 117 (5.2.) • Write Protection Local Access • Local Operation Enable Password Protection See also on page 75. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 73...
  • Page 80: Device Diagnostics

    Navigate to Process Variables>Echo Profile. • To view a previous profile, click the drop-down arrow on the Time field and select the desired profile (note: available only using AMS version 10.1 or later). Page 74 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 81: Password Protection

    The Add User Wizard dialog allows you to: • select a user type, standard (AMS Device Manager) or Window user. • enter the username and password, and set permissions • edit existing users A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 75...
  • Page 82: Ams Menu Structure

    Step 2 of 4: Application (tab) Application Type Operation Step 3 of 4: Ranges (tab) Unit Low Calibration Point (X) High Calibration Point (Y) Response Rate Step 4 of 4: Summary (tab) Long tag Page 76 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 83 Operating Mode Damping Filter Low Calibration Point (X) High Calibration Point (Y) Sensor Offset Response Rate Fill Rate per Minute Empty Rate per Minute Material Level Timer Level Analog Output Scaling A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 77...
  • Page 84 Auto False Echo Suppression 2.8.4 Range Hover Level 2.8.2 Shaper Mode 2.8.4 TVT Shaper 1 (tab) Long tag Breakpoints 2.9.2 TVT Shaper 2 (tab) Long tag Breakpoints 2.9.5 TVT Shaper 3 (tab) Long tag Page 78 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 85 Remaining Lifetime 3.7.2 Activation of Reminders 3.7.5 Reminder 1 before Lifetime (Required) 3.7.3 Reminder 2 before Lifetime (Demanded) 3.7.4 Sensor Replaced Snooze for 1 Year Service Schedule Service Schedule (tab) Long tag A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 79...
  • Page 86 Wear (tab) Long tag Time in Operation Poweron Resets OMMUNICATION Communication Communication (tab) Long tag Manufacturer’s ID Device ID Product ID Device Revision EDD Revision Universal Command ECURITY Security Security (tab) Page 80 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 87: Distance Measurement Confidence

    Distance Range (%) Analog Output (PV) = Trend View (tab) Long tag Primary Variable Secondary Variable Echo Profile Echo Profile (tab) Long tag Echo Profile/TVT Curve Distance Measurement Confidence Near Range A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 81...
  • Page 88 Identification (tab) Descriptor Message Date Manufacturer Product Name Universal Command Revision Device Revision Device ID Final Assembly Number Hardware Revision Software rev Distributor Order Number Setup (tab) Long tag Status listing Page 82 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 89: Parameter Reference

    Quick Start Wizard via the LDI push buttons on page 37 • Quick Start Wizard via the handheld programmer on page 37 • Quick Start Wizard via SIMATIC PDM on page 44 • A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 83...
  • Page 90: Afes (Auto False Echo Suppression) Wizard

    If you have a vessel with known obstructions, we recommend using AFES to prevent false echo detection. This feature can also be used if SITRANS LR560 displays a false high level, or the reading is fluctuating between the correct level and a false high level.
  • Page 91: Copy Parameters To Display

    • Press RIGHT arrow to Edit. • Press DOWN arrow to select Start and RIGHT arrow to begin the transfer. SW UPLOAD is displayed, then the device returns to Measurement mode. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 85...
  • Page 92: Copy Firmware From Display

    Date the device was first commissioned. Read only locally. Can be written via HART (dd mm yyyy). 2.1.6. Hardware Revision Read only. Corresponds to the electronics hardware of the SITRANS LR560. Page 86 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 93: Sensor

    Read only. Corresponds to the firmware that is embedded in the SITRANS LR560. 2.1.8. Loader Revision Read only. Corresponds to the software used to update the SITRANS LR560. 2.1.9. Menu Timeout Time menu stays visible before switching back to Measurement view if no key is pressed.
  • Page 94: Calibration

    Any change to High Calibration Point will cause the mA setpoints to be updated. The point from which level measurement is referenced (see Sensor Mode (2.2.2.) on page 87 for an illustration). Page 88 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 95: Rate

    The value produced by the echo processing which represents the distance from sen- sor reference point to the target. (see Sensor Mode (2.2.2.) on page 87 for an illustra- tion). A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 89...
  • Page 96 2.4.2. Fill Rate/Min Defines the maximum rate at which the reported sensor value is allowed to decrease. Allows you to adjust the SITRANS LR560 response to increases in the actual material level. Fill Rate is automatically updated whenever Response Rate is altered.
  • Page 97: Fail-Safe

    • Material Level (2.5. 1 .) must be set to VALUE to enable the Level value to be reported. Allows the user to define the mA value to be reported when the Fail-safe timer expires. Range 3.56 mA to 22.6 mA Values Default 3.56 mA A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 91...
  • Page 98: Analog Output Scaling

    To view the mA reading in the secondary region of the LCD, press on the handheld programmer. To modify Current Output Function via SIMATIC PDM: • Open the menu Device – Select Analog Output. Page 92 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 99 Prevents the mA output from rising above this maximum level for a measurement value. This does not restrict the Fail-safe or Manual settings. Range: 3.56 to 22.6 (mA) Values Default: 20.50 (mA) A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 93...
  • Page 100 2.6.8. mA Output Value Allows you to view the simulated value entered to test the functioning of the loop. Range: 3.56 mA to 22.6 mA Values Read Only. Related Manual Value (2.6.7.) parameter Page 94 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 101: Signal Processing

    Largest Echo First Echo Echo Area Largest Echo Area First Options Echo Largest First BLF Best of First and Largest echo Best Largest Echo Best First Echo LAST Last True First Echo A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 95...
  • Page 102: Position Detect

    If the vessel bottom is being reported as the level instead of the actual material level (at low conditions), we recommend setting Position to Hybrid and using it in combination with CLEF Range (2.7.3.4.) Page 96 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 103: Clef Range

    Enter the value (in percent of echo height) to ensure the Echo Lock window intersects the Echo Profile at the sharpest rising portion of the Echo Profile representing the true echo. This value is preset to 70%. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 97...
  • Page 104: Echo Lock

    2.7.4.3. Down Sampling Specifies the number of consecutive echoes that must appear below the echo currently selected, before the measurement is accepted as valid. Range: 1 to 50 Values Default: 2 Page 98 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 105: Echo Lock Window

    2.7.5.2. Reform Echo Smooths jagged peaks in the echo profile. Reforms fragmented echoes into one echo. 0 = OFF greater = wider Values Range: 0 to 255 samples Recommended: 10 samples A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 99...
  • Page 106: Tvt Setup

    137 for a more detailed explanation. Auto False Echo Suppression • To set via SIMATIC PDM, see on page 52. AFES (Auto False Echo Suppression) Wizard • To set via local operation, see on page 84. Page 100 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 107: Tvt Shaper

    Go to Level Meter > Setup > Signal Processing > TVT setup > Shaper Mode and select On. Open the menu Device – Echo Profile Utilities and click on TVT Shaper. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 101...
  • Page 108: Measured Values

    The value for Level/Volume, always displayed here in percent. 2.10.2. Ouput No Linearization The value for Level, always displayed here in percent. 2.10.3. Output No Offsets The value for distance, displayed in sensor units. Page 102 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 109: Diagnostics

    In PROGRAM mode, navigate to LEVEL METER > DIAGNOSTICS (3) > ECHO PROFILE (3.2) Press RIGHT arrow to request a profile. Requesting an Echo Profile (For more detail see on page 40.) A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 103...
  • Page 110: Trend

    Displays (in degrees C) the maximum temperature recorded by the internal electronics. The high and low values are maintained over a power cycle. Via SIMATIC PDM navigate to Maintenance and Diagnostics > Electronics Temperature. Page 104 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 111: Remaining Device Lifetime

    Selectable only via SIMATIC PDM. 3.6.1. Time in Operation Read only. The amount of time the device has been operating. 3.6.2. Remaining Lifetime Read only. less Time in Operation (3.6.1.). Lifetime Expected (3.6.6.) A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 105...
  • Page 112: Lifetime Expected

    Remaining Device Lifetime parameters in SIMATIC PDM. Allows you to override the factory default. Units : hours, days, years Range: 0 to 20 years Values Default: 10.00 years Units are selectable only via SIMATIC PDM. Page 106 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 113: Remaining Sensor Lifetime

    The device monitors the predicted lifetime of the sensor (the components exposed to the vessel environment). You can modify the expected sensor lifetime, set up schedules for maintenance reminders, and acknowledge them. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 107...
  • Page 114: Remaining Lifetime

    If Remaining Lifetime (3.7.2.) is equal to or less than this value, the device generates a Maintenance Demanded reminder. Range: 0 to 20 years Values Default: 0.019 years a) Modify values as required. b) Set Reminder Activation (3.7.5.) to the desired option. Page 108 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 115 To acknowledge a reminder via the local control buttons or handheld programmer: a) Press RIGHT arrow twice to open parameter view and activate Edit Mode. b) Press RIGHT arrow to acknowledge the reminder. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 109...
  • Page 116: Service

    In SIMATIC PDM, open the menu Device – Wear. 4.5. LCD Backlight Time the backlight remains on. Range: 0 (backlight off) to 128 seconds (>120 means backlight always on) Options Default: 128 seconds Page 110 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 117: Lcd Contrast

    Read to view the effect of the change. • Click on Service Performed to restart the timer and clear any fault messages. Time Units Hours; days; years Options Default: years Selectable only via SIMATIC PDM. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 111...
  • Page 118 Values inders 1 and 2 checked inder 2 (Maintenance Demanded) checked a) First set the values in Reminder 1 (Required) (4.7.3.)/Reminder 2 (Demanded) (4.7.4.). b) Select the desired Reminder Activation option. Page 112 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 119 To acknowledge a reminder via the local control buttons or handheld programmer: a) Press RIGHT arrow twice to open parameter view and activate Edit Mode. b) Press RIGHT arrow to acknowledge the reminder. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 113...
  • Page 120: Calibration Schedule

    • Via the handheld programmer, manually reset Time since Last Calibration (4.8.1.) to zero. 4.8.2. Time until Next Calibration Read only. Calibration Interval (4.8.6.) less Time since Last Calibration (4.8.1.). Page 114 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 121 Calibration Interval parameters in SIMATIC PDM. User-configurable recommended time between product calibrations. Units : hours, days, years Range: 0 to 20 years Values Default: 1.0 year Units are selectable only via SIMATIC PDM. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 115...
  • Page 122: Stored Software Version

    • Set the Device Address to a non-zero value. Note: For HART 5 devices, this was a one step process. With HART 6 and above, this is a two step process. Page 116 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 123: Remote Lockout

    To turn Lock On, key in any value other than the Unlock Value 2457. • To turn Lock Off, key in the Unlock Value 2457. 7. Language Selects the language to be used on the LCD. ENGLISH DEUTSCH FRANÇAIS Options ESPAÑOL 简体中文 A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 117...
  • Page 124 Notes Page 118 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 125: Appendix A: Alphabetical Parameter List

    Copy Parameters from Display (1.4.) Copy Parameters to Display (1.3.) Current Output Function (2.6.1.) Damping Filter (2.2.3.) Date of Manufacture (2.1.10.) Demo Mode (4.1.) Descriptor (2.1.3.) Device Address (5.1.) Down Sampling (2.7.4.3.) A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 119...
  • Page 126 Measured Values (2.10.) Menu Timeout (2. 1 .9.) Message (2.1.4.) Min. mA limit (2.6.4.) Narrow Echo Filter (2.7.5.1.) Near Range (2.7. 1 .) Ouput No Linearization (2.10.2.) Output No Offsets (2.10.3.) Page 120 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 127 Sampling (2.7.4.) Sensor Mode (2.2.2.) Sensor Offset (2.3.3.) Shaper Mode (2.8.4.) Stored Software Version (4.9.) Tag (2.1.2.) Temperature Units (2.2.4.) Timer (2.5.2.) Trend (3.3.) Units (2.2.1.) Up Sampling (2.7.4.2.) Write Protection (6.1.) A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 121...
  • Page 128 Notes Page 122 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 129: Appendix B: Troubleshooting

    Try pressing Mode to put the device into PROGRAM mode. If you continue to experience problems, go to our website at: www.siemens.com/sitransLR560, and check the FAQs for SITRANS LR560, or contact your Siemens representative. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS...
  • Page 130: Device Status Icons

    • Simulation or substitute value • Communication is good; device is in simulation mode or works with substi- tute values. • Out of operation • Communication is good; device is out of action. Page 124 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 131: General Fault Codes

    S: 3 Device is nearing its lifetime limit according to the value set in Maintenance Required Replacement is recommended. Limit. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 125...
  • Page 132 Internal device failure caused by an Repair required: contact your local External RAM memory error. Siemens representative. S: 28 Internal device failure caused by a RAM Repair required: contact your local Sie- memory error. mens representative. Page 126 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 133 Device error. Possible causes: increase source voltage accordingly (see 1) Voltage too low at the LR560 “Typical Connection Drawing” on page 143) 2) Hardware defect For 2): Repair required. Contact your local Siemens representative. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 127...
  • Page 134: Operation Troubleshooting

    • check distance from sensor reference Pt. (2.3.1.) not correct tently off by a constant point to Low Calibration Pt. (2.3.1.) • setting for Sensor Offset amount • check Sensor Offset (2.3.3.) (2.3.3.) not correct Page 128 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 135 • ensure Algorithm (2.7.3.1.) is set to F (First Level reading lower than processed echo) actual material level • vessel near empty and • set CLEF Range (2.7.3.4.) to 0.5 m low dK material A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 129...
  • Page 136 Notes Page 130 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 137: Appendix C: Maintenance

    Appendix C: Maintenance SITRANS LR560 requires no maintenance or cleaning under normal operating conditions. Under severe operating conditions, the antenna may require periodic cleaning. If cleaning becomes necessary: • Note the antenna material and the process medium, and select a cleaning solution that will not react adversely with either.
  • Page 138 Notes Page 132 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 139: Appendix D: Technical Reference

    Electromagnetic waves are not attenuated by dust. SITRANS LR560 consists of an enclosed electronic circuit coupled to an antenna and process connection. The electronic circuit generates a radar signal (78 GHz) that is directed to the lens antenna.
  • Page 140: Echo Processing

    Echo Processing Process Intelligence The signal processing technology embedded in Siemens radar level devices is known as Process Intelligence. Process intelligence provides high measurement reliability regardless of the dynamically changing conditions within the vessel being monitored. The embedded Process Intelligence dynamically adjusts to the constantly changing material surfaces within these vessels.
  • Page 141 The echo profile shows these echoes merging. The device may then report a material level equal to or lower than empty The CLEF algorithm enables the device to report the level correctly. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 135...
  • Page 142 Confidence (2.7.6.1.) describes the quality of an echo. Higher values represent higher quality. Echo Threshold defines the minimum confidence value required for an echo to be accepted as valid and evaluated. Page 136 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 143 In radar applications, two measurement verification options are used: Lock Off SITRANS LR560 responds immediately to a new selected echo (within the restrictions set by the Maximum Fill / Empty Rate), but measurement reliability is affected. Material Agitator A new measurement outside the Echo Lock Window must meet the sampling criteria before the window will move to include it.
  • Page 144: Measurement Range

    Measurement Range Near Range (2.7.1.) Near Range programs SITRANS LR560 to ignore the zone in front of the antenna. The default blanking distance is 27.8 cm (0.91 ft) from the sensor reference point. Near Range allows you to increase the blanking value from its factory default. But Shaper Mode (2.8.4.) is generally recommended in preference to extending the blanking distance...
  • Page 145: Measurement Response

    4 mA equals 0% and 20 mA equals 100%. While the device is in PROGRAM mode, the output remains active and continues to respond to changes in the device. SITRANS LR560 automatically returns to Measurement mode after a period of inactivity in PROGRAM mode. A5E34647946 SITRANS LR560 (mA/HART) –...
  • Page 146: Sensor Mode (2.2.2.)

    Current Output Function (2.6.1.) controls the mA output and applies any relevant scaling. By default it is set to Distance. Other options are Space and Level. To view the mA reading in the secondary region of the LCD, press on the handheld programmer. Page 140 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 147: Loss Of Echo (Loe)

    Upon receiving a reliable echo, the loss of echo condition is aborted, the Service Required icon and error message are cleared, and the reading and mA output return to the current material level. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 141...
  • Page 148: Temperature Derating Curve

    The process pressure boundary assembly comprises the components that act as a barrier against pressure loss from the process vessel: that is, the combination of process connec- tion body and lens. Page 142 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 149: Loop Power

    Loop voltage is the voltage at the terminals of the power supply (not the Note: voltage at the terminals of the device). Loop resistance RL Loop Power SITRANS LR560 voltage supply Loop current IL A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 143...
  • Page 150: Allowable Operating Area Of Sitrans Lr560

    Allowable operating area of SITRANS LR560 Loop Voltage versus Loop Resistance LR 560 HART Loop Operating Area Operation - with HART Loop Voltage (V) Startup Behavior • The device draws less than 3.6 mA at startup. • Time to first measurement is 60 seconds nominal.
  • Page 151: Appendix E: Hart Communications

    In order to configure a HART device, the configuration software requires the HART Electronic Device Description for the instrument in question. You can download the HART EDD for SITRANS LR560 from the product page of our website. Go to: www.siemens.com/sitransLR560 and click on Support>Software Downloads.
  • Page 152: Hart Communicator 375 Menu Structure

    HART Communicator 375 Menu Structure HART Communicator 375 is supported by SITRANS LR560 HART. The menu structure Note: is aligned with the menu structure of SIMATIC PDM. SITRANS LR560 1 Configure/Setup 1 Identification 1 Identification 1 Long Tag 2 Tag...
  • Page 153 3 Empty Rate per Minute 4 Fail-safe 1 Material Level 2 Timer 3 Level 5 Device Status Icon 2 Analog Output Scaling 1 Current Output Function 2 Start of Scale (=4 mA) A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 147...
  • Page 154 5 Reminder 1 before Lifetime (Required) 6 Reminder 2 before Lifetime (Demanded) 7 Snooze for 1 Year 8 Device Status Icon 2 Remaining Sensor Lifetime 1 Lifetime (Expected) 2 Time in Operation 3 Remaining Lifetime Page 148 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 155 1 Local Operation Enable 3 Device Status Icon 2 Device Diagnostics 1 Device Status 1 Device status 2 Device Status Icon 2 HW/FW-Status 1 Status group 0 2 Status group 1 A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 149...
  • Page 156: Hart Version

    2 Secondary 2 Trend View 3 Device Status Icon HART Version SITRANS LR560 conforms to HART rev. 6. Burst Mode SITRANS LR560 does not support burst mode. HART Multidrop Mode HART Multidrop Mode allows the connection of multiple field devices via HART. Details...
  • Page 157: Appendix F: Firmware Revision History

    1.00.00 19 Oct.. 2010 Initial release 1.00.02-06 1.00.02-06 18 Nov. 2011 Maintenance release 1.00.02-08 1.00.02-08 07 Feb. 2012 Damping Filter Parameter default change to 1.00.03-02 1.00.02-08 28 Oct. 2015 Maintenance release A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 151...
  • Page 158 Page 152 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 159: Glossary

    (dK): the ability of a dielectric to store electrical potential energy under the influence of an electric field. Also known as Relative Permittivity. An increase in the A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 153...
  • Page 160 Near Blanking: see Blanking nozzle: a length of pipe mounted onto a vessel that supports the flange. Page 154 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 161 TVT (time varying threshold): a time-varying curve that determines the threshold level above which echoes are determined to be valid. waveguide antenna: a hollow, metallic tube that transmits a microwave signal to the product target. A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 155...
  • Page 162 Notes Page 156 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 163: Index

    Auto False Echo Suppression 137 data logging Far Range time-based echo profile storage 50 explanation 138 Device Address 116 setup 95 device description function keys HART 145 measurement mode 33 A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 157...
  • Page 164 128 calibration schedules via PDM 54 repair 131 cleaning 131 reset service schedules via PDM 54 see Master Reset 110 maintenance settings 103 Response Rate see Calibration Interval 114 Page 158 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 165 142 test loop test 55 trend view trend line 57 troubleshooting communication 123 operation 128 TVT (time varying threshold) explanation 134 TVT Shaper manual adjustment via PDM 51 uploads/downloads accelerated 101 A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 159...
  • Page 166 Notes Page 160 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS A5E34647946...
  • Page 167: Lcd Menu Structure

    2.5 FAIL-SAFE 2.9.14 BREAKPOINT 118-120 2.5.1 MAT. LEV 2.10 MEASURED VALUES 2.5.2 TIMER 2.10.1 MAIN OUTPUT 2.5.3 LEVEL 2.10.2 O/P NO LINEAR 2.10.3 O/P NO OFFSETS A5E34647946 SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS SITRANS LR560 (mA/HART) – OPERATING INSTRUCTIONS Page 161...
  • Page 168 4.7.8 ACK STATUS 4.7.9 ACK 4.8 CALIB. SCHEDULE 4.8.1 TIME LAST CALIB 4.8.2 TIME NEXT CALIB 4.8.3 REMINDER 1 (REQ) 4.8.4 REMINDER 2 (DEM) 4.8.5 REMINDER ACTIVATION Page 162 SITRANS LR560 (mA/HART) OPERATING INSTRUCTIONS SITRANS LR560 (mA/HART) OPERATING INSTRUCTIONS A5E34647946...
  • Page 170: For More Information

    For more information www.siemens.com/level www.siemens.com/weighing Siemens Canada Limited 1954 Technology Drive Printed in Canada P.O. Box 4225 Subject to change without prior notice A5E34647946 Rev. AC Peterborough, ON Canada K9J 7B1 © Siemens AG 2016 www.siemens.com/processautomation...