GE AF-600 FP Operating Instructions Manual page 73

Fan and pump drive 460v/575v 150hp and above
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

How to Operate the Frequenc...
Press and hold [Main Menu] key for 3 seconds for
access to any parameter
For service purposes it is recommended to copy
all parameters to the keypad, see K-50 Keypad
Copy for further information
5.1.7 Quick Transfer of Parameter Settings
when using Keypad
Once the set-up of a frequency converter is complete, it is
recommended to store (backup) the parameter settings in
5
5
the or on a PC via DCT 10 software.
WARNING
Stop the motor before performing any of these operations.
Data storage in keypad:
1.
Go to K-50 Keypad Copy
2.
Press the [OK] key
3.
Select "All to keypad"
4.
Press the [OK] key
All parameter settings are now stored in the keypad
indicated by the progress bar. When 100% is reached,
press [OK].
The keypad can now be connected to another frequency
converter and the parameter settings copied to this
frequency converter.
Data transfer from keypad to Frequency converter:
1.
Go to K-50 Keypad Copy
2.
Press the [OK] key
3.
Select "All from keypad"
4.
Press the [OK] key
The parameter settings stored in the graphical keypad are
now transferred to the frequency converter indicated by
the progress bar. When 100% is reached, press [OK].
5.1.8 Restore Factory Settings
There are two ways to restore the drive to factory settings:
Recommended restore and manual restore.
Please be aware that they have different impact according
to the below description.
Recommended restore (via H-03 Restore Factory Settings)
1.
Select H-03 Restore Factory Settings
2.
Press [OK]
3.
Select [2] Restore Factory Settings
4.
Press [OK]
72
AF-600 FP High Power Operating Instructions
5.
6.
7.
H-03 Restore Factory Settings restores all except:
SP-50 RFI Filter
O-30 Protocol
O-31 Address
O-32 Drive Port Baud Rate
O-35 Minimum Response Delay
O-36 Max Response Delay
O-37 Maximum Inter-Char Delay
ID-00 Operating Hours to ID-05 Over Volt's
ID-20 Historic Log: Event to ID-22 Historic Log: Time
ID-30 Alarm Log: Error Code to ID-32 Alarm Log: Time
Manual restore
NOTE
When carrying out manual restore, serial communication,
RFI filter settings and fault log settings are reset.
.
The Manual Restore restores all except:
ID-00 Operating Hours
ID-03 Power Up's
ID-04 Over Temp's
ID-05 Over Volt's
Remove power to unit and wait for display to
turn off.
Reconnect power and the frequency converter is
reset. Note that first start-up takes a few more
seconds
Press [Reset]
1. Disconnect from mains and wait until the
display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the
same time while power up for keypad
3. Release the keys after 5 sec.
4. The frequency converter is now programmed
according to default settings