Issue 08/03
Please refer to the troubleshooting section for information on how to use r0722.
Parameters P0701 – P0706 (P0707 – P0708)
Parameter
value
0
1
2
3
4
9
10
11
12
13
14
15
16
17
25
29
33
99
NOTE
If an analog input has been configured as digital input, then the following limit values apply:
< 1.7 V DC = "0", > 3.9 V DC = "1"
BICO parameterization
If the available settings above are not sufficient for your application, then refer to the operating
instructions and parameter lists for comprehensive information about BICO parameterization.
NOTE
Only experienced users should use the BICO parameterization and for applications where the
possibilities provided by P0701 – P0708 are no longer adequate.
54
Function
Digital input disabled
ON / OFF1
ON+reverse / OFF1
OFF2 – coast to standstill
OFF3 – quick ramp-down
Fault acknowledge
JOG right
JOG left
Reverse
MOP up (increase frequency)
MOP down (decrease frequency)
Fixed setpoint (direct selection)
Fixed setpoint (direct selection + ON)
Fixed setpoint (binary-coded selection + ON)
Enable DC braking
External trip
Disable additional frequency setpoint
Enable BICO parameterization
Table 5-6 Standard Selectable Functions for Digital Inputs