SYSTEM SETUP
5.5.8.7 Modification of SYNC word in CFG-2 for TR 90-5 data sets
In the CFG-2 file, all relevant information about the data being streamed is included. However, this file does not include the
fact that it describes a 90-5 dataset or the number of Application Service Data Units (datasets).  In order to communicate
this information via the CFG-2 file for a given aggregator, when the aggregator is set to 90-5, the version number of the
CFG-2 file (found in bits 0-3 of the frame SYNC word, which is set presently to 2) is set as follows:
5
Value (decimal)
 11
12
 13
 14
5.5.8.8 Settings
The PMU settings are organized as follows.
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1
 PHASOR MEASUREMENT
 UNIT 1
5.5.8.9 Basic configuration
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  BASIC CONFIGURATION  PMU 1
 PMU 1 BASIC
 CONFIGURATION
5-172
Figure 5-89: CFG-2 based configuration solution
Number of ASDUs
 1
2
3
 4
 PMU 1 BASIC
 CONFIGURATION
 PMU 1
 CALIBRATION
 PMU 1
 TRIGGERING
 PMU 1
 RECORDING
PMU 1
FUNCTION: Disabled
PMU 1 IDCODE:
1
PMU 1 STN:
GE-UR-PMU
See below
See page 5-176
See page 5-177
See page 5-183
Range:
Enabled, Disabled
Range:
1 to 65534 in steps of 1
Range:
32-character ASCII string truncated to 16
characters if mapped into C37.118 Default: GE-UR-PMU
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS