Advertisement

5.
TROUBLE SHOOTING
If communications cannot be established with the drive, there are four LEDs on the Modbus card to aid in
troubleshooting. The CPU LED should blink once per second to indicate that the modbus card is interfacing
with the inverter main PCB properly. The RXD LED should blink each time a properly formed Modbus
message is received that is addressed to the inverter. The RXD LED will not blink when messages are
received that are addressed to other inverters or devices. The TXD LED should blink each time the inverter
responds to a Modbus message. The ERR LED indicates either an invalid request was received or there is a
problem with the Modbus card itself. The ERR LED should never light.
5.1.1. CPU LED
State
Indicates
Blinking
Card
normally
Off
Card is not installed properly
Inverter is not operating normally
5.1.2. RXD and TXD LEDs
State
Indicates
Blinking
Card is functioning normally and receiving and
sending messages
Off
Incorrect Modbus connection to the card
Master is not polling
Incorrect baud rate setting
Incorrect byte format
is
installed
properly
Corrective measures
and
working
Verify that the card is installed
properly
Verify that the inverter has power
Corrective measures
Verify
connected to terminal N and the
High signal is connected to terminal
P
Verify that the master (PLC or PC) is
polling the inverter.
Verify that the baud rate (I/O47) is
set to match the baud rate of the
inverter.
The inverter communicates using 8
data bits, 1 stop bit and no parity
bits. Verify that the master is set to
the same.
4
that
the
Low
signal
modbus-rtu iS5 manual.doc