Fujitsu AB*30LBAG series Service Instruction page 33

Large ceiling type inverter
Table of Contents

Advertisement

3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time and
outdoor heat exchanger temperature as follows.
Compressor integrating
operation:
45 minutes and over
Outdoor temp. > -1°C
=
Outdoor heat exchanger
temperarure:
Below -8°C
Defrost start
Defrost Indicator:
[Operation lamp]
9 sec ON / 1 sec OFF
Heating operation start : Compressor ON
AB*30/ 36LBAG
Outdoor temp. < -1°C
Outdoor heat exchanger
temperarure:
Below -10°C
3 sec later Compressor OFF
3 sec later Outdoor fan motor OFF
28 sec later 4-way valve OFF
34 sec later compressor ON
(Frequency : 92 Hz)
Outdoor heat exchanger temperature: Over 12°C
Compressor ON time: Over 15 minutes
(Not defrosted for 6 or 10 minutes)
Outdoor temp. > -1°C
=
Outdoor heat exchanger
temperarure:
Below -8°C
Outdoor temp -
Outdoor heat exchanger
temperature:
Above 12 degC
or
Defrost end
05-15
AB*45LBAG
Compressor integrating
operation:
45 minutes and over
Outdoor temp. < -1°C
Outdoor heat exchanger
temperarure:
Below -10°C
Outdoor heat exchanger
temperarure:
Below -20°C
Defrost start
Defrost Indicator:
[Operation lamp]
9 sec ON / 1 sec OFF
Outdoor fan motor : Low
Compressor : 30 Hz
4-way valve OFF
Outdoor fan motor OFF
5
Compressor ON
(Frequency : 92 Hz)