PARAMETER DATA INPUT
AREA MAPPING
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
The explicit data can be further assigned to different attributes of parameter data input
mapping object B0h. Define the following four attributes out of eight bytes of explicit data.
Attribute
Bytes
Attribute 1
2 bytes
Attribute 2
2 bytes
Attribute 3
2 bytes
Attribute 4
2 bytes
This can be done by using I/O data input area mapping mailbox command (04h)
1.
Right click on the EndInit item and insert a new mailbox.
2.
Set the command code to 04 (row 3).
3.
The offset and length of attribute must be provided for each of the four attributes.
Enter 16 in the Data size field - it will automatically convert and display as 0x0010.
Figure 9-28: Offset and data length for parameter data input mapping attributes
4.
The offset and data length for each attribute in bytes in given below.
Attribute
Offset
1
0x0000
2
0x0002
3
0x0004
4
0x0006
5.
Enter the offset and data length values from the table above, then select the File >
Apply Changes menu item to save the changes.
Assignment
Switch input status
Motor load
Thermal capacity
Voltage
Data length
0x0002
0x0002
0x0002
0x0002
APPLICATION EXAMPLE
9–17