Outdoor M-Net Board (Optional); Function Of Switches, Connectors And Jumpers - Mitsubishi Electric PUZ-ZM35VKA Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUZ-ZM35VKA:
Table of Contents

Advertisement

Outdoor M-NET board (optional)

CN2M
Connect to M-NET
LED2
Energizing
display of
M-NET board
(5 V power supply)
CND
Power supply (5V/12V) input
2 to 3 5 V DC Input
1 to 3 12 V DC Input

10-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS

(1) Function of switches
Type
No.
Switch
Function
of
switch
1
Manual defrost *1
2
Abnormal history clear
3
4
SW1
DIP
Refrigerant address setting
switch
5
6
1
Test run
SW4
2
Test run mode setting
Push
SWP
Pump down
switch
*1 Manual defrost should be done as follows.
1 Change the DIP SW1-1 on the outdoor controller board from OFF to ON.
2 Manual defrost will start by the above operation 1 if all these conditions written below are satisfied.
• Heat mode setting
• 10 minutes have passed since compressor started operating or previous manual defrost is finished.
• Pipe temperature is less than or equal to 8°C.
Manual defrost will finish if certain conditions are satisfied.
Manual defrost can be done if above conditions are satisfied when DIP SW1-1 is changed from OFF to ON.
After DIP SW1-1 is changed from OFF to ON, there is no problem if DIP SW1-1 is left ON or changed to OFF again.
This depends on the service conditions.
OCH653
LED13
Receiving
LED1
Energizing display
)
[
]
of M-NET board
1, 2 : +
(12 V power supply)
3 : –
Action by the switch operation
ON
Start
Clear
ON
1 2 3
4 5 6
0
ON
1 2 3
4 5 6
4
ON
1 2 3
4 5 6
8
ON
1 2 3
4 5 6
12
Operating
Heating
Start
LED11
LED12
Outdoor unit
Transmitting
connecting display
SW12
M-NET address
(10s digit)
The black square ( ) indicates a switch position.
OFF
Normal
Normal
ON
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
1
2
ON
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
5
6
ON
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
9
10
ON
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
13
14
OFF
Cooling
Normal
69
SW1
Switch for communication
display between
M-NET and outdoor board
CN5
Serial communication
with outdoor board
SW11
M-NET address (1s digit)
Effective timing
When compressor is working
in heating operation. *1
off or operating
1 2 3 4 5 6
3
1 2 3 4 5 6
7
When power supply ON
1 2 3 4 5 6
11
1 2 3 4 5 6
15
Under suspension
Under suspension
Continue to the next page