Iec 61580 Goose Analog Values; Phasor Measurement Unit - GE T60 Instruction Manual

Ur series transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

6.3 METERING
Table 6–2: FLEXELEMENT BASE UNITS (Sheet 2 of 2)
XFMR DIFFERENTIAL
HARMONIC CONTENT
(Xfmr Harm2 Iad, Ibd, and Icd Mag)
(Xfmr Harm5 Iad, Ibd, and Icd Mag)
XFMR RESTRAINING CURRENT
(Xfmr Iar, Ibr, and Icr Mag)
Z
BASE
PATH: ACTUAL VALUES
 IEC 61850
 GOOSE ANALOGS
6
The T60 Transformer Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. See the Order Codes section of chap-
ter 2 for details.
The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are received
via IEC 61850 GOOSE messages sent from other devices.
PATH: ACTUAL VALUES
 PMU 1
6-24
BASE = 100%
I
= maximum primary RMS value of the +IN and -IN inputs
BASE
(CT primary for source currents, and transformer reference primary current for transformer
differential currents)
Z
= PhaseVTSecondary / PhaseCTSecondary, where PhaseVTSecondary and
BASE
PhaseCTSecondary are the secondary nominal voltage and the secondary nominal current of the
distance source. In case multiple CT inputs are summed as one source current and mapped as
the distance source, use the PhaseCTSecondary value from the CT with the highest primary
nominal current.
Distance source is specified in setting under
GROUP 1(6) > DISTANCE
PhaseVTSecondary and PhaseCTSecondary are specified in setting under
SETUP > AC INPUTS


METERING
IEC 61850 GOOSE ANALOGS
ANALOG INPUT
0.000
ANALOG INPUT
MESSAGE
0.000
ANALOG INPUT
MESSAGE
0.000
ANALOG INPUT 32
MESSAGE
0.000


METERING

PHASOR MEASUREMENT UNIT

PMU 1 VA:
0.0000 kV, 0.00°
PMU 1 VB:
MESSAGE
0.0000 kV, 0.00°
PMU 1 VC:
MESSAGE
0.0000 kV, 0.00°
PMU 1 VX:
MESSAGE
0.0000 kV, 0.00°
PMU 1 V1:
MESSAGE
0.0000 kV, 0.00°
T60 Transformer Protection System
SETTINGS > GROUPED ELEMENTS > SETTING
.
.

6.3.8 IEC 61580 GOOSE ANALOG VALUES

1
2
3
PMU 1
Range: Va or Vab per VT bank connection
Range: Va or Vab per VT bank connection
Range: Va or Vab per VT bank connection
6 ACTUAL VALUES
SETTINGS > SYSTEM
6.3.9 PHASOR MEASUREMENT UNIT
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents