RBCTBPTS SMART Touch Controller
2.3. Digital Input / Output
The digital input and output currently have no functionality.
2.3.1. Digital Inputs
Global disable
1
Global on
2
Not assigned
3
Not assigned
4
2.3.2. Digital Ouputs
Any unit in alarm : active when any unit present on the system returns an error code.
1
Any unit on
2
Not assigned
3
Not assigned
4
Digital input 1 is permanently enabled and active 'open'.
All other inputs and outputs have an enable switch and a polarity selector.
2.4. USB
The USB interface located behind the cover plate is used for configuration via a PC
and for upgrading the firmware.
Ensure that the correct USB driver has been installed prior to
2.5. Ethernet
The SMART Touch Controller is a 10/100Base-T half/full duplex device. It supports auto-
negotiation and also features auto-crossover (Auto-MDIX), allowing the use of either a
straight-through or crossover cable.
It does not currently support DHCP and will therefore require the IP address, gateway
address and subnet-mask configuring to match the host network it is attached to.
If the unit is only being accessed via the local network then set the gateway address
to be
the same as the IP address, otherwise enter the address of the appropriate gateway or
router.
2.6. Firmware Updates *** IMPORTANT NOTICE ***
Please check our website on a regular basis to update controller software
: when active, turns all units off and inhibits the remote controllers.
: on becoming inactive, removes the inhibits from the remote controllers only.
: on becoming active, turns all units ON.
: on becoming inactive, turns all units OFF.
: active when any unit on the system returns an 'ON' state.
Relay ratings are 24v @ 1amp
connecting the SMART Touch Controller to a PC.
7
Installation & Owners Manual