RECORDS
Magnitudes of the third harmonic components of the machine neutral point voltage (VN), the zero-sequence voltage at the
machine terminals (V0), and in the vector sum of the neutral point voltage and zero-sequence voltage (VN + V0) are
available for display. The values are calculated for a signal source specified under the
These readings can be useful when selecting a pickup and supervision setting for the third harmonic neutral undervoltage
protection element.
6.4.12 Volts per hertz
ACTUAL VALUES METERING VOLTS PER HERTZ 1(2)
VOLTS PER HERTZ 1
This menu displays the data for volts per hertz.
6.4.13 Restricted ground fault
ACTUAL VALUES METERING RESTRICTED GROUND FAULT CURRENTS RESTRICTED GROUND FAULT 1(4)
RESTRICTED
GROUND FAULT 1
This menu displays the differential and restraint current values for the restricted ground fault element.
6.4.14 Transducer inputs and outputs
ACTUAL VALUES METERING TRANSDUCER I/O DCMA INPUTS DCMA INPUT xx
6
DCMA INPUT xx
Actual values for each DCmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
ACTUAL VALUES METERING TRANSDUCER I/O RTD INPUTS RTD INPUT xx
RTD INPUT xx
Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value.
6.5 Records
6.5.1 User-programmable fault reports
ACTUAL VALUES RECORDS USER-PROGRAMMABLE FAULT REPORTS
USER-PROGRAMMABLE
FAULT REPORTS
6-26
VOLTS PER HERTZ 1:
0.000 pu
RGF 1 DIFF Igd:
0.000 A
RGF 1 RESTR Igr:
0.000 A
DCMA INPUT xx
0.000 mA
RTD INPUT xx
-50 °C
NEWEST RECORD
NUMBER: 0
LAST CLEARED DATE:
2002/8/11 14:23:57
CHAPTER 6: ACTUAL VALUES
STATOR GROUND
G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
settings menu.