Monitoring Elements - GE L60 Instruction Manual

Line phase comparison relay, ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

5 SETTINGS
a) MAIN MENU
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING
ELEMENTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
b) BREAKER ARCING CURRENT
PATH: SETTINGS
CONTROL ELEMENTS
BREAKER 1
ARCING CURRENT
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin

MONITORING ELEMENTS

BREAKER 1
ARCING CURRENT
BREAKER 2
ARCING CURRENT
BREAKER
FLASHOVER 1
BREAKER
FLASHOVER 2
CT FAILURE
DETECTOR
VT FUSE FAILURE 1
VT FUSE FAILURE 2
OPEN POLE
MONITORING ELEMENTS
BKR 1 ARC AMP
FUNCTION: Disabled
BKR 1 ARC AMP
SOURCE: SRC 1
BKR 1 ARC AMP INT-A:
Off
BKR 1 ARC AMP INT-B:
Off
BKR 1 ARC AMP INT-C:
Off
BKR 1 ARC AMP
DELAY:
0.000 s
BKR 1 ARC AMP LIMIT:
1000 kA2-cyc
BKR 1 ARC AMP BLOCK:
Off
BKR 1 ARC AMP
TARGET: Self-reset
BKR 1 ARC AMP
EVENTS: Disabled
L60 Line Phase Comparison Relay
5.6 CONTROL ELEMENTS
5.6.8 MONITORING ELEMENTS
See below.
See below.
See page 5–201.
See page 5–201.
See page 5–205.
See page 5–207.
See page 5–207.
See page 5–208.
BREAKER 1(2) ARCING CURRENT
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.000 to 65.535 s in steps of 0.001
2
Range: 0 to 50000 kA
-cycle in steps of 1
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5
5-199