5.7

Provide project data offline for simulation

Simulations regardless of STEP 7
To perform simulations independent of STEP 7, you can save the user program and the
hardware configuration in STEP 7 in a directory.
Provide project data offline
1. Create a "User-defined Card Reader" for your project data under Card Reader/USB
storage in the project tree of STEP 7 for the CPU.
2. In the "Load preview" dialog for the target device, select "PLC Simulation Advanced" as
an action, click in the selection field for this.
→ The project is saved to the <Virtual Memory Card>\SIMATIC.S7S\OMSSTORE
directory.
3. Save the folder\SIMATIC.S7S with the project data to a medium of your choice.
Figure 5-6
Figure 5-7
S7-PLCSIM Advanced
Function Manual, 12/2017, A5E37039512-AB
Add card reader
Preview of download dialog
5.7 Provide project data offline for simulation