TRANSDUCER INPUTS/OUTPUTS
The relay provides eight direct outputs that are conveyed on communications channel 1 (numbered 1-1 through 1-8) and
eight direct outputs that are conveyed on communications channel 2 (numbered 2-1 through 2-8). Each digital point in the
message must be programmed to carry the state of a specific FlexLogic operand. The settings are used to select the
operand that represents a specific function (as selected by the user) to be transmitted.
Direct outputs 2-1 to 2-8 are functional in three-terminal systems.
5
5.10 Transducer inputs/outputs
5.10.1 DCmA inputs
SETTINGS TRANSDUCER I/O DCMA INPUTS DCMA INPUT H1(U8)
DCMA INPUT H1
The L30 is provided with optional DCmA capability. This feature is specified as an option at the time of ordering.
See the Order Codes section in chapter 2 for details.
5-290
DIRECT OUTPUT 2-1:
Off
DIRECT OUTPUT 2-8:
Off
Figure 5-155: Direct inputs/outputs logic (example for L90 shown)
DCMA INPUT H1
FUNCTION: Disabled
DCMA INPUT H1 ID:
DCMA Ip 1
DCMA INPUT H1
UNITS: μA
DCMA INPUT H1
RANGE: 0 to -1 mA
DCMA INPUT H1 MIN
VALUE:
0.000
DCMA INPUT H1 MAX
VALUE:
0.000
Range: FlexLogic operand
Range: FlexLogic operand
Range: Disabled, Enabled
Range: up to 20 alphanumeric characters
Range: six alphanumeric characters
Range: 0 to –1 mA, 0 to +1 mA, –1 to +1 mA, 0 to 5
mA, 0 to 10mA, 0 to 20 mA, 4 to 20 m
Range: –9999.999 to +9999.999 in steps of 0.001
Range: –9999.999 to +9999.999 in steps of 0.001
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS