Energy manager / heating controller
Hide thumbs Also See for RVP550:

Advertisement

Quick Links

Installation Instructions
en
Installation
Place of installation
In a dry room, e.g. the boiler room
Installation choices:
-
Control panel (in the panel front, on the inner wall, or
on a DIN rail)
-
Control cabinet
-
Sloping front of a control desk
Permissible ambient temperature
Electrical installation
The local regulations for electrical installations must
be complied with
Cable strain relief must be ensured
Cables from the controller to the actuators and
pumps carry mains voltage
Sensor cables should not be run parallel to mains car-
rying cables
To protect the solar collector sensor from voltage
surges (caused by lightning for example), the separately
available conduit box for overvoltage protection
(AGS2S.200/109) should be installed
Permissible cable lengths
For all sensors, thermostats and external contacts:
Copper cable 0.6 mm dia. max. 20 m
Copper cable 1.0 mm
Copper cable 1.5 mm
For room units:
Copper cable 0.25 mm
Copper cable 0.5 mm
For the data bus:
2
0.75...2.5 mm
Mounting and wiring the base
Wall mounting
1.
Separate base from the controller.
2.
Hold base against the wall. Marking TOP must be at
the top!
3.
Mark fixing holes on the wall.
4.
Drill holes.
5.
If required, knock out holes on the base for the cable
entry glands.
6.
Screw base to the wall.
7.
Wire up the base.
DIN rail mounting
1. Fit rail.
2. Separate base from the controller.
3. If required, knock out holes on the base for the cable
entry glands.
4. Fit base to the rail. Marking TOP must be at the top!
5. If required, secure the base (depending on the type of
rail).
6. Wire up the base.
Flush panel mounting
Panel cutout required: 92 x 138 mm
Maximum thickness: 3 mm
Siemens Building Technologies / HVAC Products
Energy Manager / Heating Controller
: 0...50 °C
2
max. 80 m
2
max. 120 m
2
max. 25 m
2
max. 50 m
according to Data Sheets
N2030E and N2032E
1.
Separate base from the controller.
2.
If required, knock out holes on the base for the cable
entry glands.
3.
Insert base in the panel cutout from behind until stop
is reached. Marking TOP must be at the top!
4.
Push lateral tongues behind the front panel (refer to
illustration below).
Wrong
Place tongues on both sides correctly – they may not be
located inside the cutout!
5.
Wire up the base. Make sure the cable lengths are
such that there is sufficient space to open the control
panel door.
Commissioning
Preparatory checks
1. DO NOT switch on power yet.
2. Check wiring according to the plant connection diagram.
3. Ensure correct position and location of the levers by
turning the fixing screws (refer to illustration on the lat-
eral wall of the unit).
4. Insert controller in the base until stop is reached.
Marking TOP must be at the top!
5. Tighten fixing screws alternately.
6. Check the motorized valves: See if
they are correctly installed (observe direction of flow
as indicated on the valve body)
the manual lever is disengaged.
7. Note with underfloor and ceiling heating systems:
The limit thermostat must be correctly adjusted. During
the functional test, the flow temperature may not ex-
ceed the maximum permissible level (usually 55 °C). If
it does, proceed immediately as follows:
-
Either close the valve manually, or
-
Switch off the pump, or
-
Close the pump isolating valve
74 319 0312 0 a
74 319 0312 0
G2488
RVP540
RVP550
Correct
19.08.2002
1/28

Advertisement

loading

Summary of Contents for Siemens RVP550

  • Page 1 6. Wire up the base. Switch off the pump, or Flush panel mounting Close the pump isolating valve • Panel cutout required: 92 x 138 mm • Maximum thickness: 3 mm Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 1/28...
  • Page 2 1. Make settings on the operating lines according to the 9. If one of the operating mode buttons flashes, a room instructions provided by your local Siemens HVAC unit or contact H1 overrides the controller. Select op- Products sales office.
  • Page 3 Phase Q102 Phase Q107 Q101 Multifunctional output Q106 Multifunctional output Phase Q101 Q105 Multifunctional output Live conductor AC 230 V Phase Q105 / Q106 Neutral conductor Electrical connections 74 319 0312 0 a 19.08.2002 3/28 Siemens Building Technologies / HVAC Products...
  • Page 4 Plant type The basic plant diagram for the required type of plant and additional setting information will be provided by your local Siemens Building Technologies / HVAC Products sales office. Designations of relays and sensors The relay designations used in the supplied basic diagram have the following meaning:...
  • Page 5 To leave programming mode “Enduser“, press any of the operating mode but- tons. display è Note: If no button is pressed for about 8 minutes, the controller will automatically re- turn to the operating mode selected last. Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 5/28...
  • Page 6 / min ..: ..- -:- - h / min Switch-off time period d.h.w. 00:00...24:00 h / min ..: ..- -:- - h / min 6/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products...
  • Page 7 86 = short-circuit PPS 100 = 2 clock time masters on the data bus (LPB) 127 = legionella temperature not reached 130 = maximum flue gas temperature exceeded Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 7/28...
  • Page 8 To leave programming level “Heating engineer“, press one of the operating mode buttons. display è Note: If no button is pressed for about 8 minutes, the controller will automatically return to the operating mode selected last. 8/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products...
  • Page 9 0 / 1 – ..Without sensor B71 With sensor B71 Reduction water / brine sensor B11 0 / 1 – ..Without sensor B11 With sensor B11 Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 9/28...
  • Page 10 Sensor B62 at sensor terminal B101...109 Solar flow sensor B63 for yield measurement (ZuFu14) 101...109 – ..- - - - - - None 101..109 Sensor B63 at sensor terminal B101...109 10/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products...
  • Page 11 101...110 – – – Query with the + / - buttons Display of sensor terminal assignment 101...109 – – – Query with the + / - buttons Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 11/28...
  • Page 12 Maximum value of the flue gas temperature display B8 –50...350 °C – No value available To reset the maximum value to the actual value, press the + / - but- tons simultaneously for 3 s 12/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products...
  • Page 13 Maximum value of collector temperature 2 (B61) –50...350 °C – To make a reset to the actual value, press the + / - buttons simulta- neously for 3 s Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 13/28...
  • Page 14 Absolute priority d.h.w. storage tank (heat exchanger 2) Solar yield / recooling measurement Type of antifreeze agent used 1...4 – ..None (only water) Ethylenglycol Propylenglycol Mixture of Ethylen- and Propylenglycol 14/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products...
  • Page 15 0 / 1 – ..fired boiler General frost protection for the plant does not act on this pump General frost protection for the plant acts on this pump Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 15/28...
  • Page 16 Function deactivated Frost protection for the heat pump circulator 0 / 1 – ..Frost protection does not act on this circulator Frost protection acts on this circulator 16/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products...
  • Page 17 Operating action of return diversion 1...2 – ..As return temperature setback As return temperature boost Storage tank sensor for return diversion 1...3 – ..Sensor B4 Sensor B41 Sensor B42 Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 17/28...
  • Page 18 Only for frost protection According to d.h.w. release Always Heat transfer strategy in the winter 0...2 – ..Only for frost protection According to d.h.w. release Always 18/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products...
  • Page 19 D.h.w. with lag heat source if released, lead heat source maintains the room temperature setpoint during d.h.w. heating. D.h.w. with lag heat source if released, lead heat source is shut down during d.h.w. heating. Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 19/28...
  • Page 20 Maximum speed of the heating circuit pump Line 741 ..% ...100 Speed reduction heating circuit pump 0 / 1 – ..According to the heating circuit operating level According to the characteristic 20/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products...
  • Page 21 ..tank Absolute priority Shifting priority No priority Automatic d.h.w. push 0 / 1 – ..Limitation of the d.h.w. charging time --- / 5...250 ..min Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 21/28...
  • Page 22 System clock (master) Changeover date winter- / summertime 01.01...31.12 tt.mm ..: ..25.03 dd.mm Changeover date summer- / wintertime 01.01...31.12 tt.mm ..: ..25.10 dd.mm 22/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products...
  • Page 23 Temperature setpoint wood-fired boiler Maximum value of heat demand 5...130 °C (when used as the temperature setpoint) Voltage signal logic 0 / 1 – ..Standard Inverted Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 23/28...
  • Page 24 Whether correct or incorrect, each push of a button represents irrevocably a digit of the code. As a confirmation, the respective digit changes to 1. You receive the code from your local Siemens Building Technologies / HVAC Products sales office. 24/28 19.08.2002...
  • Page 25 Maximum storage tank charging time 1...60 ..min Maximum waiting time 1...40 ..min Changeover / startup delay bypass valve / charging 1...15 ..min pump K9 Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 25/28...
  • Page 26 (without room sensor) Boost of the room temperature setpoint 0...20 ..K (with boost heating) Control mode of mixing valve 0 / 1 – ..2-position 3-position 26/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products...
  • Page 27 + / - buttons simultaneously for 3 s Display version table with basic diagrams 0...32‘767 – – – Dimensions max. 3 26 26 26 26 106,8 Dimensions in mm Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 27/28...
  • Page 28 ã 2002 Siemens Building Technologies Ltd. 28/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products...